Bathroom Fan CFM Calculator & Humidity Timer
Model the period after a shower with a fixed room volume and fixed replacement-air moisture. Enter two measured CFM values and a timer, then compare their humidity curves and find when each reaches your stated target.
Compare delivered bathroom fan airflow and timing
Check humidity at the timer for two measured exhaust flows.
Only Case B meets the timer target.
Room dimensions
Modeled humidity during the timer
Case A · 60.66% RH
Case B · 50.25% RH
Delivered airflow at the timer
44.3615 CFM or higher
Minimum flow at four-decimal input precision for this timer.
- Enclosed volume
- 640 ft³
Exhaust and target ledger
Case A · 30 CFM
2.8125 air changes per hour
First at target after 29.5743 min.
Case B · 65 CFM
6.09375 air changes per hour
First at target after 13.6497 min.
Humidity trace CSV
How to use this calculator
- Measure the enclosed bathroom footprint and average ceiling height.
- Record initial and target humidity at a stable indoor temperature. Use the replacement air’s humidity expressed at that same temperature.
- Enter two delivered CFM values measured under the conditions you want to compare, plus the planned timer duration.
- Compare humidity at timer shutoff, the modeled flow threshold and the two curves. Review the calculation ledger and export it if needed.
The Formula
The mathematical logic powering this calculation is:
Use an enclosed room volume V in cubic feet from measured length × width × average ceiling height. Use delivered exhaust airflow Q in cubic feet per minute under your entered conditions. Air changes per hour equal 60Q/V. Replacement air humidity must be expressed at the same indoor temperature as the initial and target values. For example, enter the measured humidity of replacement air at that indoor temperature, or convert its moisture state before using such a value.
With continued moisture production and temperature changes outside the model, let initial room humidity be H₀ and replacement humidity be Hₛ. The well-mixed mass balance with a fixed air exchange gives H(t) = Hₛ + (H₀ − Hₛ) exp(−Qt/V) at t minutes. This applies the constant-volume ventilation-decay relationship to moisture concentration at fixed temperature. Moisture re-release from wet surfaces, simultaneous uncontrolled air changes, or a varying supply state can shift the observed curve.
When the room starts above the target Hₜ and Hₛ is lower than Hₜ, the minimum modeled airflow for positive time t is V/t × ln[(H₀ − Hₛ)/(Hₜ − Hₛ)]. Conversely, elapsed time at a measured positive Q is V/Q × that log ratio. If the incoming air is at the target, a room that starts above approaches the target from above. If the incoming air is above the target, reaching it from above is infeasible in this model.
If the room starts at or below the target and replacement air is above it, increasing air exchange can raise humidity. For positive time, maximum flow to remain at or below the target is V/t × ln[(Hₛ − H₀)/(Hₛ − Hₜ)]. For zero timer duration, the initial reading is the result. For zero delivered flow, the calculated moisture state stays at its starting value. Exact equality at the entered target is within the target. A displayed rounded value can differ from the unrounded comparison.
Inputs allow four decimal places. Dimensions span 0.0001–100 ft, humidity 0–100% RH, airflow 0–5,000 CFM and timer 0–240 min. The model compares moisture under these assumptions; follow local mechanical ventilation requirements and verify actual airflow independently.Worked Example
If you input:
- Bathroom: 10 × 8 × 8 ft
- Humidity: 85% initial, 45% replacement and 55% target at the same temperature
- Delivered airflow: 30 and 65 CFM
- Timer: 20 minutes
Result:
The 640 ft³ example needs about 44.36 CFM to reach the 55% target within 20 minutes. Case A ends around 60.66% and Case B around 50.25%. Case B first reaches the target after about 13.65 minutes.
Frequently Asked Questions
Should I enter measured airflow or the fan label?
Use measured delivered airflow at the bathroom grille under the compared conditions. Duct and opening differences can make installed airflow differ from the label.
Should I use outdoor relative humidity directly?
Express the replacement air at the same temperature as the room. Relative humidity changes when air temperature changes even when its moisture content stays the same.
Why could higher airflow increase the humidity?
If replacement air contains more moisture than the starting room at the shared temperature, ventilation moves the room toward that wetter replacement state.
Why might reaching the target take longer in practice?
Evaporation from wet surfaces, an ongoing shower and weaker mixing can alter the observed room curve. Treat the result as a one-zone comparison and check real readings.
What if the replacement humidity equals my target?
A room starting above approaches that humidity from above. It takes a finite time to get within an entered margin above it, while exact equality is asymptotic in this model.
What happens at zero timer duration?
The timer result is the initial humidity for both cases. Any time-to-target shown refers to continued operation at the entered delivered airflow.
Similar Calculators
HVAC Duct Pressure & Airflow Planner
Compare round and rectangular duct paths at a prescribed airflow. Visualize pressure losses, check entered pressure and velocity preferences, and export energy estimates.
Psychrometric Calculator
Compare moist-air properties and dry-air mixing on a pressure-specific temperature and humidity chart, with explicit saturation and phase limits.
Room Heat Loss & Retrofit Calculator
Explore room heat loss and sensible cooling, compare envelope and ventilation retrofits, and visualize heat flows and outdoor-temperature sensitivity with exact CSV ledgers.
Air Conditioner Electricity Cost & Duty Cycle Calculator
Compare two air conditioner schedules using measured watts and time-of-use prices. See daily kWh, billing cost and the compressor duty that fits a cost cap.
Dehumidifier Water Removal & Energy Calculator
Compare measured dehumidifier water removal and electricity. Check whether each unit can reach your entered target within its daily powered hours.
Range Hood CFM & Published Pressure Calculator
Compare two ducted range hood airflow tables at an entered static pressure. Find the last supported pressure at a target CFM and review a separate field measurement.