Psychrometric Calculator
Compare two air states at the same pressure, inspect their moisture and thermal properties, and explore mixing by dry-air mass share on one chart.
2 valid air states. Mixture outcome: single-phase.
Examples and reset
Illustrative conditions, not measured design data.
Shared conditions
Converts the entered dimensional quantities.
Absolute pressure shared by both air states.
Explore a mixture
Adiabatic mixing at the shared pressure. A supersaturated candidate requires a separate condensation model; the tool does not invent a final fog state.
Explore the diagram
A circle marks State A, a square marks State B, and a triangle marks the selected mixture. Curves show relative humidity at the entered pressure. This is a rectangular temperature–humidity-ratio diagram. Select a state to identify its marker when points overlap.
Horizontal: dry bulb (°C) · Vertical: humidity ratio (g/kg dry air)
The mixing line joins sampled no-condensation candidates. Dashed red segments include a condensation-required or near-saturation sample; they do not predict the final fog equilibrium. Unsampled shares are not certified by the line.
Rectangular dry-bulb/humidity-ratio diagram at the entered common pressure; not an enthalpy-coordinate chart.
The mixing locus uses sampled no-condensation bookkeeping. An unsampled share is not certified feasible; inspect the selected share directly.
Choose a sampled dry-air mass share to calculate and inspect it as the current mixture.
Air properties
Humidity ratio
≈ 8.22424 g/kg dry air
Relative humidity
≈ 50 %
Dry-bulb temperature
≈ 22 °C
Specific enthalpy
≈ 43.0374 kJ/kg dry air
Specific volume
≈ 0.847182 m³/kg dry air
Water vapor pressure
≈ 1.32238 kPa
Dew / frost point
≈ 11.1101 °C
Dew point, liquid-water saturation reference.
Thermodynamic wet / ice bulb
≈ 15.4256 °C
Thermodynamic bulb result; not a calibrated psychrometer reading.
Relative humidity references liquid-water saturation at this temperature. Enthalpy and volume are per unit mass of dry air. Both unit systems use the same 0°C enthalpy reference.
Inverse calculation detail
These brackets and residuals describe the numerical calculation, not measurement accuracy. Brackets use °C in both display systems.
| Quantity | Phase | Temperature | Bracket (°C) | Residual | Iterations |
|---|---|---|---|---|---|
| Dew/frost point | liquid | ≈ 11.1100929713 °C | 11.110092967841776 to 11.110092974825532 | 2.1082335877053993e-10 log-pressure-ratio | 34 (bisection) |
| Thermodynamic bulb | liquid | ≈ 15.4255747583 °C | 15.425574755761772 to 15.425574760884047 | 1.3456787767429645e-12 kg/kg | 33 (bisection) |
State B compared with State A
Temperature change
≈ 13 °C
Moisture change
≈ 13.2168 g/kg dry air
Enthalpy change
≈ 47.1926 kJ/kg dry air
Sensible term at State A moisture
≈ 13.2769 kJ/kg dry air
B minus A. The sensible term holds State A humidity ratio fixed; these differences are not actual coil duty or a guaranteed physical process.
Mixing result
Single-phase mixture
Conserved humidity ratio
≈ 11.5284 g/kg dry air
Conserved specific enthalpy
≈ 54.8355 kJ/kg dry air
Mixture temperature
≈ 25.3083 °C
Mixture relative humidity
≈ 57.126 %
Air-state comparison table
| State | Dry bulb | Relative humidity | Humidity ratio | Specific enthalpy | Specific volume | Saturation reference |
|---|---|---|---|---|---|---|
| State A | ≈ 22 °C | ≈ 50 % | ≈ 8.22423934597 g/kg dry air | ≈ 43.0373584783 kJ/kg dry air | ≈ 0.847182229601 m³/kg dry air | liquid |
| State B | ≈ 35 °C | ≈ 60 % | ≈ 21.4410696333 g/kg dry air | ≈ 90.2299287859 kJ/kg dry air | ≈ 0.903047654188 m³/kg dry air | liquid |
Values describe the entered states under the named approximation. Complete reports include inverse statuses and the current diagram range.
Mixing comparison table
Every row conserves dry-air-basis moisture and enthalpy. Temperature and RH are provisional no-condensation values wherever the outcome is not single-phase.
| State B share | Temperature | Relative humidity | Humidity ratio | Enthalpy | Outcome |
|---|---|---|---|---|---|
| ≈ 0 % | ≈ 22 °C | ≈ 50 % | ≈ 8.22423934597 g/kg dry air | ≈ 43.0373584783 kJ/kg dry air | single phase |
| ≈ 1 % | ≈ 22.1330971496 °C | ≈ 50.3823886336 % | ≈ 8.35640764884 g/kg dry air | ≈ 43.5092841814 kJ/kg dry air | single phase |
| ≈ 2 % | ≈ 22.2661302553 °C | ≈ 50.7556223509 % | ≈ 8.48857595172 g/kg dry air | ≈ 43.9812098845 kJ/kg dry air | single phase |
| ≈ 3 % | ≈ 22.3990993633 °C | ≈ 51.1198489276 % | ≈ 8.62074425459 g/kg dry air | ≈ 44.4531355875 kJ/kg dry air | single phase |
| ≈ 4 % | ≈ 22.5320045198 °C | ≈ 51.4752138524 % | ≈ 8.75291255746 g/kg dry air | ≈ 44.9250612906 kJ/kg dry air | single phase |
| ≈ 5 % | ≈ 22.6648457709 °C | ≈ 51.8218603632 % | ≈ 8.88508086033 g/kg dry air | ≈ 45.3969869937 kJ/kg dry air | single phase |
| ≈ 6 % | ≈ 22.7976231626 °C | ≈ 52.1599294825 % | ≈ 9.01724916321 g/kg dry air | ≈ 45.8689126968 kJ/kg dry air | single phase |
| ≈ 7 % | ≈ 22.9303367411 °C | ≈ 52.4895600524 % | ≈ 9.14941746608 g/kg dry air | ≈ 46.3408383998 kJ/kg dry air | single phase |
| ≈ 8 % | ≈ 23.0629865522 °C | ≈ 52.8108887696 % | ≈ 9.28158576895 g/kg dry air | ≈ 46.8127641029 kJ/kg dry air | single phase |
| ≈ 9 % | ≈ 23.195572642 °C | ≈ 53.1240502188 % | ≈ 9.41375407182 g/kg dry air | ≈ 47.284689806 kJ/kg dry air | single phase |
| ≈ 10 % | ≈ 23.3280950563 °C | ≈ 53.4291769061 % | ≈ 9.5459223747 g/kg dry air | ≈ 47.7566155091 kJ/kg dry air | single phase |
| ≈ 11 % | ≈ 23.4605538411 °C | ≈ 53.7263992919 % | ≈ 9.67809067757 g/kg dry air | ≈ 48.2285412121 kJ/kg dry air | single phase |
| ≈ 12 % | ≈ 23.5929490421 °C | ≈ 54.0158458235 % | ≈ 9.81025898044 g/kg dry air | ≈ 48.7004669152 kJ/kg dry air | single phase |
| ≈ 13 % | ≈ 23.7252807051 °C | ≈ 54.2976429659 % | ≈ 9.94242728332 g/kg dry air | ≈ 49.1723926183 kJ/kg dry air | single phase |
| ≈ 14 % | ≈ 23.8575488758 °C | ≈ 54.571915234 % | ≈ 10.0745955862 g/kg dry air | ≈ 49.6443183214 kJ/kg dry air | single phase |
| ≈ 15 % | ≈ 23.9897535999 °C | ≈ 54.8387852229 % | ≈ 10.2067638891 g/kg dry air | ≈ 50.1162440244 kJ/kg dry air | single phase |
| ≈ 16 % | ≈ 24.1218949231 °C | ≈ 55.0983736377 % | ≈ 10.3389321919 g/kg dry air | ≈ 50.5881697275 kJ/kg dry air | single phase |
| ≈ 17 % | ≈ 24.2539728909 °C | ≈ 55.3507993239 % | ≈ 10.4711004948 g/kg dry air | ≈ 51.0600954306 kJ/kg dry air | single phase |
| ≈ 18 % | ≈ 24.3859875489 °C | ≈ 55.5961792961 % | ≈ 10.6032687977 g/kg dry air | ≈ 51.5320211337 kJ/kg dry air | single phase |
| ≈ 19 % | ≈ 24.5179389427 °C | ≈ 55.834628767 % | ≈ 10.7354371006 g/kg dry air | ≈ 52.0039468367 kJ/kg dry air | single phase |
| ≈ 20 % | ≈ 24.6498271176 °C | ≈ 56.0662611755 % | ≈ 10.8676054034 g/kg dry air | ≈ 52.4758725398 kJ/kg dry air | single phase |
| ≈ 21 % | ≈ 24.7816521191 °C | ≈ 56.2911882146 % | ≈ 10.9997737063 g/kg dry air | ≈ 52.9477982429 kJ/kg dry air | single phase |
| ≈ 22 % | ≈ 24.9134139926 °C | ≈ 56.5095198586 % | ≈ 11.1319420092 g/kg dry air | ≈ 53.419723946 kJ/kg dry air | single phase |
| ≈ 23 % | ≈ 25.0451127834 °C | ≈ 56.7213643902 % | ≈ 11.264110312 g/kg dry air | ≈ 53.891649649 kJ/kg dry air | single phase |
| ≈ 24 % | ≈ 25.1767485368 °C | ≈ 56.9268284269 % | ≈ 11.3962786149 g/kg dry air | ≈ 54.3635753521 kJ/kg dry air | single phase |
| ≈ 25 %Current | ≈ 25.3083212981 °C | ≈ 57.1260169468 % | ≈ 11.5284469178 g/kg dry air | ≈ 54.8355010552 kJ/kg dry air | single phase |
| ≈ 26 % | ≈ 25.4398311124 °C | ≈ 57.3190333147 % | ≈ 11.6606152207 g/kg dry air | ≈ 55.3074267583 kJ/kg dry air | single phase |
| ≈ 27 % | ≈ 25.571278025 °C | ≈ 57.5059793067 % | ≈ 11.7927835235 g/kg dry air | ≈ 55.7793524614 kJ/kg dry air | single phase |
| ≈ 28 % | ≈ 25.7026620808 °C | ≈ 57.6869551356 % | ≈ 11.9249518264 g/kg dry air | ≈ 56.2512781644 kJ/kg dry air | single phase |
| ≈ 29 % | ≈ 25.8339833251 °C | ≈ 57.8620594746 % | ≈ 12.0571201293 g/kg dry air | ≈ 56.7232038675 kJ/kg dry air | single phase |
| ≈ 30 % | ≈ 25.9652418029 °C | ≈ 58.0313894818 % | ≈ 12.1892884322 g/kg dry air | ≈ 57.1951295706 kJ/kg dry air | single phase |
| ≈ 31 % | ≈ 26.096437559 °C | ≈ 58.1950408238 % | ≈ 12.321456735 g/kg dry air | ≈ 57.6670552737 kJ/kg dry air | single phase |
| ≈ 32 % | ≈ 26.2275706386 °C | ≈ 58.3531076985 % | ≈ 12.4536250379 g/kg dry air | ≈ 58.1389809767 kJ/kg dry air | single phase |
| ≈ 33 % | ≈ 26.3586410864 °C | ≈ 58.5056828584 % | ≈ 12.5857933408 g/kg dry air | ≈ 58.6109066798 kJ/kg dry air | single phase |
| ≈ 34 % | ≈ 26.4896489474 °C | ≈ 58.6528576326 % | ≈ 12.7179616436 g/kg dry air | ≈ 59.0828323829 kJ/kg dry air | single phase |
| ≈ 35 % | ≈ 26.6205942663 °C | ≈ 58.7947219494 % | ≈ 12.8501299465 g/kg dry air | ≈ 59.554758086 kJ/kg dry air | single phase |
| ≈ 36 % | ≈ 26.751477088 °C | ≈ 58.9313643576 % | ≈ 12.9822982494 g/kg dry air | ≈ 60.026683789 kJ/kg dry air | single phase |
| ≈ 37 % | ≈ 26.8822974572 °C | ≈ 59.0628720485 % | ≈ 13.1144665523 g/kg dry air | ≈ 60.4986094921 kJ/kg dry air | single phase |
| ≈ 38 % | ≈ 27.0130554185 °C | ≈ 59.1893308761 % | ≈ 13.2466348551 g/kg dry air | ≈ 60.9705351952 kJ/kg dry air | single phase |
| ≈ 39 % | ≈ 27.1437510166 °C | ≈ 59.3108253786 % | ≈ 13.378803158 g/kg dry air | ≈ 61.4424608983 kJ/kg dry air | single phase |
| ≈ 40 % | ≈ 27.2743842961 °C | ≈ 59.4274387982 % | ≈ 13.5109714609 g/kg dry air | ≈ 61.9143866013 kJ/kg dry air | single phase |
| ≈ 41 % | ≈ 27.4049553016 °C | ≈ 59.5392531018 % | ≈ 13.6431397638 g/kg dry air | ≈ 62.3863123044 kJ/kg dry air | single phase |
| ≈ 42 % | ≈ 27.5354640776 °C | ≈ 59.6463489999 % | ≈ 13.7753080666 g/kg dry air | ≈ 62.8582380075 kJ/kg dry air | single phase |
| ≈ 43 % | ≈ 27.6659106685 °C | ≈ 59.7488059668 % | ≈ 13.9074763695 g/kg dry air | ≈ 63.3301637106 kJ/kg dry air | single phase |
| ≈ 44 % | ≈ 27.7962951189 °C | ≈ 59.8467022592 % | ≈ 14.0396446724 g/kg dry air | ≈ 63.8020894136 kJ/kg dry air | single phase |
| ≈ 45 % | ≈ 27.926617473 °C | ≈ 59.9401149353 % | ≈ 14.1718129752 g/kg dry air | ≈ 64.2740151167 kJ/kg dry air | single phase |
| ≈ 46 % | ≈ 28.0568777753 °C | ≈ 60.029119873 % | ≈ 14.3039812781 g/kg dry air | ≈ 64.7459408198 kJ/kg dry air | single phase |
| ≈ 47 % | ≈ 28.1870760701 °C | ≈ 60.1137917884 % | ≈ 14.436149581 g/kg dry air | ≈ 65.2178665229 kJ/kg dry air | single phase |
| ≈ 48 % | ≈ 28.3172124015 °C | ≈ 60.1942042534 % | ≈ 14.5683178839 g/kg dry air | ≈ 65.6897922259 kJ/kg dry air | single phase |
| ≈ 49 % | ≈ 28.4472868139 °C | ≈ 60.2704297138 % | ≈ 14.7004861867 g/kg dry air | ≈ 66.161717929 kJ/kg dry air | single phase |
| ≈ 50 % | ≈ 28.5772993515 °C | ≈ 60.342539506 % | ≈ 14.8326544896 g/kg dry air | ≈ 66.6336436321 kJ/kg dry air | single phase |
| ≈ 51 % | ≈ 28.7072500583 °C | ≈ 60.4106038746 % | ≈ 14.9648227925 g/kg dry air | ≈ 67.1055693352 kJ/kg dry air | single phase |
| ≈ 52 % | ≈ 28.8371389784 °C | ≈ 60.4746919889 % | ≈ 15.0969910954 g/kg dry air | ≈ 67.5774950382 kJ/kg dry air | single phase |
| ≈ 53 % | ≈ 28.966966156 °C | ≈ 60.5348719597 % | ≈ 15.2291593982 g/kg dry air | ≈ 68.0494207413 kJ/kg dry air | single phase |
| ≈ 54 % | ≈ 29.0967316349 °C | ≈ 60.5912108551 % | ≈ 15.3613277011 g/kg dry air | ≈ 68.5213464444 kJ/kg dry air | single phase |
| ≈ 55 % | ≈ 29.2264354593 °C | ≈ 60.643774717 % | ≈ 15.493496004 g/kg dry air | ≈ 68.9932721475 kJ/kg dry air | single phase |
| ≈ 56 % | ≈ 29.356077673 °C | ≈ 60.6926285766 % | ≈ 15.6256643068 g/kg dry air | ≈ 69.4651978505 kJ/kg dry air | single phase |
| ≈ 57 % | ≈ 29.48565832 °C | ≈ 60.7378364699 % | ≈ 15.7578326097 g/kg dry air | ≈ 69.9371235536 kJ/kg dry air | single phase |
| ≈ 58 % | ≈ 29.6151774439 °C | ≈ 60.779461453 % | ≈ 15.8900009126 g/kg dry air | ≈ 70.4090492567 kJ/kg dry air | single phase |
| ≈ 59 % | ≈ 29.7446350888 °C | ≈ 60.8175656172 % | ≈ 16.0221692155 g/kg dry air | ≈ 70.8809749598 kJ/kg dry air | single phase |
| ≈ 60 % | ≈ 29.8740312983 °C | ≈ 60.8522101035 % | ≈ 16.1543375183 g/kg dry air | ≈ 71.3529006629 kJ/kg dry air | single phase |
| ≈ 61 % | ≈ 30.0033661161 °C | ≈ 60.8834551175 % | ≈ 16.2865058212 g/kg dry air | ≈ 71.8248263659 kJ/kg dry air | single phase |
| ≈ 62 % | ≈ 30.132639586 °C | ≈ 60.9113599433 % | ≈ 16.4186741241 g/kg dry air | ≈ 72.296752069 kJ/kg dry air | single phase |
| ≈ 63 % | ≈ 30.2618517516 °C | ≈ 60.9359829581 % | ≈ 16.550842427 g/kg dry air | ≈ 72.7686777721 kJ/kg dry air | single phase |
| ≈ 64 % | ≈ 30.3910026564 °C | ≈ 60.9573816454 % | ≈ 16.6830107298 g/kg dry air | ≈ 73.2406034752 kJ/kg dry air | single phase |
| ≈ 65 % | ≈ 30.520092344 °C | ≈ 60.9756126095 % | ≈ 16.8151790327 g/kg dry air | ≈ 73.7125291782 kJ/kg dry air | single phase |
| ≈ 66 % | ≈ 30.649120858 °C | ≈ 60.990731588 % | ≈ 16.9473473356 g/kg dry air | ≈ 74.1844548813 kJ/kg dry air | single phase |
| ≈ 67 % | ≈ 30.7780882418 °C | ≈ 61.0027934657 % | ≈ 17.0795156384 g/kg dry air | ≈ 74.6563805844 kJ/kg dry air | single phase |
| ≈ 68 % | ≈ 30.9069945388 °C | ≈ 61.0118522872 % | ≈ 17.2116839413 g/kg dry air | ≈ 75.1283062875 kJ/kg dry air | single phase |
| ≈ 69 % | ≈ 31.0358397925 °C | ≈ 61.0179612701 % | ≈ 17.3438522442 g/kg dry air | ≈ 75.6002319905 kJ/kg dry air | single phase |
| ≈ 70 % | ≈ 31.1646240462 °C | ≈ 61.0211728171 % | ≈ 17.4760205471 g/kg dry air | ≈ 76.0721576936 kJ/kg dry air | single phase |
| ≈ 71 % | ≈ 31.2933473432 °C | ≈ 61.0215385288 % | ≈ 17.6081888499 g/kg dry air | ≈ 76.5440833967 kJ/kg dry air | single phase |
| ≈ 72 % | ≈ 31.4220097267 °C | ≈ 61.0191092158 % | ≈ 17.7403571528 g/kg dry air | ≈ 77.0160090998 kJ/kg dry air | single phase |
| ≈ 73 % | ≈ 31.55061124 °C | ≈ 61.0139349106 % | ≈ 17.8725254557 g/kg dry air | ≈ 77.4879348028 kJ/kg dry air | single phase |
| ≈ 74 % | ≈ 31.6791519263 °C | ≈ 61.0060648796 % | ≈ 18.0046937586 g/kg dry air | ≈ 77.9598605059 kJ/kg dry air | single phase |
| ≈ 75 % | ≈ 31.8076318288 °C | ≈ 60.9955476347 % | ≈ 18.1368620614 g/kg dry air | ≈ 78.431786209 kJ/kg dry air | single phase |
| ≈ 76 % | ≈ 31.9360509904 °C | ≈ 60.9824309446 % | ≈ 18.2690303643 g/kg dry air | ≈ 78.9037119121 kJ/kg dry air | single phase |
| ≈ 77 % | ≈ 32.0644094544 °C | ≈ 60.9667618463 % | ≈ 18.4011986672 g/kg dry air | ≈ 79.3756376151 kJ/kg dry air | single phase |
| ≈ 78 % | ≈ 32.1927072636 °C | ≈ 60.948586656 % | ≈ 18.53336697 g/kg dry air | ≈ 79.8475633182 kJ/kg dry air | single phase |
| ≈ 79 % | ≈ 32.3209444612 °C | ≈ 60.9279509802 % | ≈ 18.6655352729 g/kg dry air | ≈ 80.3194890213 kJ/kg dry air | single phase |
| ≈ 80 % | ≈ 32.44912109 °C | ≈ 60.9048997265 % | ≈ 18.7977035758 g/kg dry air | ≈ 80.7914147244 kJ/kg dry air | single phase |
| ≈ 81 % | ≈ 32.577237193 °C | ≈ 60.8794771139 % | ≈ 18.9298718787 g/kg dry air | ≈ 81.2633404274 kJ/kg dry air | single phase |
| ≈ 82 % | ≈ 32.7052928129 °C | ≈ 60.8517266835 % | ≈ 19.0620401815 g/kg dry air | ≈ 81.7352661305 kJ/kg dry air | single phase |
| ≈ 83 % | ≈ 32.8332879927 °C | ≈ 60.8216913088 % | ≈ 19.1942084844 g/kg dry air | ≈ 82.2071918336 kJ/kg dry air | single phase |
| ≈ 84 % | ≈ 32.9612227751 °C | ≈ 60.7894132054 % | ≈ 19.3263767873 g/kg dry air | ≈ 82.6791175367 kJ/kg dry air | single phase |
| ≈ 85 % | ≈ 33.0890972028 °C | ≈ 60.7549339415 % | ≈ 19.4585450902 g/kg dry air | ≈ 83.1510432397 kJ/kg dry air | single phase |
| ≈ 86 % | ≈ 33.2169113186 °C | ≈ 60.7182944473 % | ≈ 19.590713393 g/kg dry air | ≈ 83.6229689428 kJ/kg dry air | single phase |
| ≈ 87 % | ≈ 33.344665165 °C | ≈ 60.6795350247 % | ≈ 19.7228816959 g/kg dry air | ≈ 84.0948946459 kJ/kg dry air | single phase |
| ≈ 88 % | ≈ 33.4723587848 °C | ≈ 60.638695357 % | ≈ 19.8550499988 g/kg dry air | ≈ 84.566820349 kJ/kg dry air | single phase |
| ≈ 89 % | ≈ 33.5999922205 °C | ≈ 60.595814518 % | ≈ 19.9872183016 g/kg dry air | ≈ 85.038746052 kJ/kg dry air | single phase |
| ≈ 90 % | ≈ 33.7275655147 °C | ≈ 60.5509309813 % | ≈ 20.1193866045 g/kg dry air | ≈ 85.5106717551 kJ/kg dry air | single phase |
| ≈ 91 % | ≈ 33.8550787097 °C | ≈ 60.5040826294 % | ≈ 20.2515549074 g/kg dry air | ≈ 85.9825974582 kJ/kg dry air | single phase |
| ≈ 92 % | ≈ 33.9825318482 °C | ≈ 60.4553067624 % | ≈ 20.3837232103 g/kg dry air | ≈ 86.4545231613 kJ/kg dry air | single phase |
| ≈ 93 % | ≈ 34.1099249725 °C | ≈ 60.4046401072 % | ≈ 20.5158915131 g/kg dry air | ≈ 86.9264488644 kJ/kg dry air | single phase |
| ≈ 94 % | ≈ 34.2372581249 °C | ≈ 60.3521188256 % | ≈ 20.648059816 g/kg dry air | ≈ 87.3983745674 kJ/kg dry air | single phase |
| ≈ 95 % | ≈ 34.3645313479 °C | ≈ 60.2977785233 % | ≈ 20.7802281189 g/kg dry air | ≈ 87.8703002705 kJ/kg dry air | single phase |
| ≈ 96 % | ≈ 34.4917446838 °C | ≈ 60.241654258 % | ≈ 20.9123964218 g/kg dry air | ≈ 88.3422259736 kJ/kg dry air | single phase |
| ≈ 97 % | ≈ 34.6188981747 °C | ≈ 60.1837805475 % | ≈ 21.0445647246 g/kg dry air | ≈ 88.8141516767 kJ/kg dry air | single phase |
| ≈ 98 % | ≈ 34.7459918629 °C | ≈ 60.1241913785 % | ≈ 21.1767330275 g/kg dry air | ≈ 89.2860773797 kJ/kg dry air | single phase |
| ≈ 99 % | ≈ 34.8730257907 °C | ≈ 60.0629202136 % | ≈ 21.3089013304 g/kg dry air | ≈ 89.7580030828 kJ/kg dry air | single phase |
| ≈ 100 % | ≈ 35 °C | ≈ 60 % | ≈ 21.4410696333 g/kg dry air | ≈ 90.2299287859 kJ/kg dry air | single phase |
Integer shares plus your current share are sampled independently. The table does not certify unsampled shares.
Save and reuse your comparison
Complete report CSV
Complete input and import
Includes both humidity drafts, units, labels and mixing settings. Saved unit changes preserve the entered quantities.
Import replaces the comparison atomically. Choosing a file only stages it. Malformed data leaves the current comparison unchanged.
What these properties mean
This workspace uses the named ASHRAE 2017 perfect-gas approximations with an ice/liquid saturation convention. It accepts −20 to 60°C and 60 to 110 kPa. Calculated precision is not measurement accuracy. Mixing uses dry-air mass, a shared pressure and no heat exchange. It does not size equipment or calculate a final fog equilibrium.
Method references: ASHRAE 2017 psychrometrics · triple-point convention.
Assumptions and limits
- ASHRAE Fundamentals 2017 SI perfect-gas approximations; not the newer 2025 saturation formulation.
- Both unit systems retain the common 0°C dry-air/liquid-water enthalpy datum.
- Humidity ratio, enthalpy, specific volume and mixing share use a dry-air mass basis.
- RH is referenced to ice at dry bulb <=0.01°C and liquid water above; bulb phase ambiguities are explicit.
- No equipment suitability, condensate amount, measured psychrometer calibration or comfort conclusion is inferred.
How to use this calculator
- Choose Units and enter the common absolute Pressure for State A and State B. The supported pressure range is 60–110 kPa. Pressure is entered directly; the tool does not assume an altitude or fetch weather conditions.
- Enter each Dry-bulb temperature and choose Humidity input: Relative humidity or Humidity ratio. Temperature must be −20 to 60°C. Humidity ratio is water mass per dry-air mass, displayed as g/kg in SI or grains/lb in IP. Changing mode converts the current valid state while preserving its source draft.
- Read each state's humidity ratio, enthalpy, specific volume and available dew/frost or thermodynamic wet/ice-bulb result. A state with an invalid active field keeps its valid peer visible. Correct associated errors before interpreting a comparison or downloading a complete report.
- Enable Mix these states and enter State B dry-air mass share. Zero percent selects State A and 100 percent selects State B. This is a dry-air mass proportion, not a volume proportion; a condensation-required result is not a solved final gas equilibrium.
- Inspect the selected state and RH curves on the temperature/humidity-ratio chart. The mixing path is calculated from conserved humidity ratio and enthalpy before projection. Fit and full views change the drawing domain, not the calculated inlet states. Use the ledger for precise values and explicit method statuses.
- Choose Input format and apply a complete psychrometric input to replace the plan atomically, or save the complete input for reuse. Download the complete report or select its identical CSV fallback. Dry-air, phase-ambiguous and condensation-required statuses are reportable; active validation or numerical-limit errors must be corrected first.
The Formula
The mathematical logic powering this calculation is:
The model pins the perfect-gas relations in ASHRAE Fundamentals 2017, chapter 1. With T in °C, P and pᵥ in Pa, W in kg water/kg dry air, h in kJ/kg dry air and v in m³/kg dry air: W = 0.621945 pᵥ/(P − pᵥ), RH = 100 pᵥ/pₛₐₜ(T), h = 1.006T + W(2501 + 1.86T), and v = 287.042(T + 273.15)(1 + 1.607858W)/P. Published rounded constants are preserved.
The saturation correlation uses an ice reference at T ≤ 0.01°C and liquid water above it. Dew/frost inversion respects the tiny coefficient gap; thermodynamic wet/ice-bulb candidates are solved separately across freezing. No minimum moisture floor or fabricated unique phase result is introduced.
For State B dry-air mass fraction f: Wₘ = (1 − f)Wₐ + fWᵦ, hₘ = (1 − f)hₐ + fhᵦ and Tₘ = (hₘ − 2501Wₘ)/(1.006 + 1.86Wₘ). A supersaturated or numerically near-saturation mixture retains conserved quantities and provisional coordinates; this model does not solve the resulting condensed-phase equilibrium. The plotted locus samples mixing shares rather than proving every intermediate share.
Comparison changes are State B minus State A. The fixed-Wₐ sensible term (1.006 + 1.86Wₐ)(Tᵦ − Tₐ) is an algebraic comparison, not equipment duty. Both unit systems keep the same 0°C enthalpy reference. All physical properties are approximate, despite exact unit-conversion factors.Worked Example
If you input:
- Units: SI
- Pressure: 101.325 kPa
- State A: 22°C dry bulb, 50% relative humidity
- State B: 35°C dry bulb, 60% relative humidity
- Mix these states: Enabled
- State B dry-air mass share: 25%
Result:
State A has approximately 8.224239 g/kg dry air of water and enthalpy 43.037358 kJ/kg dry air; State B has approximately 21.441070 g/kg and 90.229929 kJ/kg. With 25% of the dry-air mass from State B, the single-phase mixture is approximately 25.308321°C, 57.126017% RH, 11.528447 g/kg and 54.835501 kJ/kg. These are approximate model properties, not measurement accuracy or a cooling-equipment rating.
Frequently Asked Questions
How does relative humidity differ from humidity ratio?
Relative humidity compares vapor partial pressure with the model's saturation reference at the same dry-bulb temperature. Humidity ratio instead measures water mass per unit of dry-air mass. It is not absolute humidity, moist-air water mass fraction or a volume percentage. The two input modes describe the same physical state only after a valid pressure-dependent conversion. Each displayed field carries its basis and unit.
What pressure and temperature range does this calculator support?
Enter absolute pressure from 60 to 110 kPa and dry-bulb temperatures from −20 to 60°C, or their converted IP values. These are this workspace's admission limits, not universal limits of moist air. Both states share the same pressure. No altitude, local weather, pressure loss or equipment operating condition is inferred. The pinned perfect-gas approximation does not claim the accuracy of a real-gas property package.
What do dew point, frost point and thermodynamic wet bulb mean here?
A finite saturation inverse is labeled frost point on the ice-reference branch and dew point on the liquid branch. Dry air has no finite dew/frost point; an extremely dry state may fall below the correlation range. Thermodynamic wet/ice-bulb calculations retain both branch candidates when freezing makes the result ambiguous. They are not a calibration or correction for an actual wetted thermometer, whose reading depends on heat and mass transfer.
What happens if the mixed air would condense?
The tool first conserves humidity ratio and enthalpy for the requested dry-air mass share. If the resulting provisional state exceeds saturation, it reports condensation required and retains those conserved values without inventing a final equilibrium temperature or condensate amount. A declared numerical band identifies near-saturation ambiguity. These explicit outcomes remain reportable. Do not interpret an enthalpy difference alone as total cooling duty or an equipment recommendation.
Why is the mixing path not necessarily straight on this chart?
This workspace uses a rectangular dry-bulb-temperature versus humidity-ratio plot. Mixing is linear in humidity ratio and enthalpy, then converted to temperature for drawing. A straight line on an oblique enthalpy chart does not imply a straight line in these coordinates. The displayed locus samples integer shares plus the selected share, so its marked outcomes do not certify every unsampled intermediate proportion.
Do SI and IP units use the same enthalpy reference?
Yes. Both displays retain the same 0°C dry-air/liquid-water reference, with enthalpy expressed as kJ/kg dry air or Btu(IT)/lb dry air. This can differ from another IP chart's customary datum. Temperature conversion includes its offset; temperature changes do not. Specific volume is volume per dry-air mass, not the reciprocal of total moist-air density. Exact conversion anchors preserve quantities through repeated unit changes without implying exact physical properties.
How are invalid drafts, very small values and unsupported states handled?
Blank required values are not zero. An invalid state keeps a valid peer, while shared pressure/unit errors prevent the complete calculation. Inactive humidity drafts and disabled mixing drafts remain editable and are ignored by the solver, but a unit change validates nonblank dimensional drafts before converting all of them atomically. Numeric atoms allow 18 significant digits and exponents from −100 to 100; positive authored RH and canonical humidity ratio must be at least 1e−50. Smaller valid derived quantities remain nonzero. A failed numerical inversion is reported explicitly and blocks the complete report; recognized dry, phase and condensation statuses do not.
Similar Calculators
Temperature Converter
Convert temperatures between Celsius, Fahrenheit, and Kelvin instantly.
Unit Converter
Convert between units of length, weight, volume, and area — all in one tool.
Ratio Calculator
Simplify ratios, find equivalent ratios, and solve for a missing value in a proportion.
Room Heat Loss & Retrofit Calculator
Explore room heat loss and sensible cooling, compare envelope and ventilation retrofits, and visualize heat flows and outdoor-temperature sensitivity with exact CSV ledgers.