HVAC Duct Pressure & Airflow Planner
Trace where available pressure is consumed through a rigid ventilation duct path. Compare up to four alternatives, each with up to eight round or rectangular sections, using local fitting coefficients and an entered equipment loss at the same airflow. Inspect actual cross-section diagrams, cumulative pressure-loss curves, friction and fitting breakdowns, and estimated operating energy from your combined efficiency and schedule. Switch between CFM, L/s and m³/h, inches and millimetres, or feet and metres without rounding the underlying quantities. This is a low-speed serial-path planning model, not a branching network, fan operating-point solver, flexible-duct model, acoustic prediction or installation certification. Unknown or out-of-domain results remain visible as unassessed rather than becoming zero losses.
See where the pressure goes.
Compare round and rectangular duct paths at the same airflow. Inspect section losses, available pressure and entered-efficiency energy estimates.
Rigid, low-speed ventilation paths only. Each path is serial with the same prescribed airflow through every section. This is not a branching network, fan operating-point solver, flexible-duct model or compliance assessment.
1. Set the design point
Changing airflow does not automatically update fitting or equipment performance data.
Use matching path boundaries and TOTAL pressure, not an unexamined external-static-pressure rating.
An entered preference, not a noise or safety threshold.
Air properties and operating-energy assumptions
Properties are explicit, constant assumptions. Energy is steady-state at this design point, not seasonal performance. Pressure is in Pa; efficiency includes the fan, drive and motor.
2. Compare serial duct paths
Include filters/coils/terminals as applicable. This is an entered loss, not a curve.
Referenced to this section’s actual mean velocity; transitions are not added automatically.
Referenced to this section’s actual mean velocity; transitions are not added automatically.
2 of 2 paths are within the entered pressure and velocity preferences under this model.
3. Follow cumulative pressure loss
Loss increases from path start through each section, with equipment added last. Horizontal positions show normalized step order, not physical distance. The dashed grey line is the entered total-pressure budget; unknown cumulative loss stops that series.
Vertical range: 0 to ≈ 200 Pa.
- 1. Baseline path: ≈ 199.452 Pa · Within entered pressure and velocity preferences
- 2. Larger ducts: ≈ 131.9 Pa · Within entered pressure and velocity preferences
4. Inspect each path
1. Baseline path
Within entered pressure and velocity preferences
Assessed within the stated model
Required loss
≈ 199.452 Pa
Pressure headroom
≈ 0.547935 Pa
Electrical input
≈ 166.21 W
Annual energy cost
≈ 99.726 USD/year
Diameter: ≈ 300 mm
≈ 7.07355 m/s · Within preference
≈ 400 mm × ≈ 200 mm
≈ 6.25 m/s · Within preference
Cross-sections share one scale across all paths; dimensions above are canonical millimetres. These are internal dimensions after any liner.
| Section | Velocity m/s | Friction Pa | Fittings Pa | Total Pa | Method / limit |
|---|---|---|---|---|---|
| Round supply | ≈ 7.07355 | ≈ 18.5938 | ≈ 45.1817 | ≈ 63.7756 | Turbulent flow |
| Rectangular section | ≈ 6.25 | ≈ 13.6453 | ≈ 47.0312 | ≈ 60.6765 | Turbulent flow |
| Step | Added loss Pa | Cumulative Pa |
|---|---|---|
| Path start | 0 | 0 |
| Round supply | ≈ 63.7756 | ≈ 63.7756 |
| Rectangular section | ≈ 60.6765 | ≈ 124.452 |
| Equipment loss | ≈ 75 | ≈ 199.452 |
Geometry, friction diagnostics and energy details
| Section | Area m² | Hydraulic diameter m | Reynolds | Darcy factor | Solver residual |
|---|---|---|---|---|---|
| Round supply | ≈ 0.0706858 | ≈ 0.3 | ≈ 141,158 | ≈ 0.018519 | ≈ -8.63842E-12 |
| Rectangular section | ≈ 0.08 | ≈ 0.266667 | ≈ 110,866 | ≈ 0.0193421 | ≈ 4.05009E-13 |
Air power ≈ 99.726 W · estimated annual energy ≈ 498.63 kWh. Display values are approximate, not measured performance. CSV retains full model values and solver diagnostics.
2. Larger ducts
Within entered pressure and velocity preferences
Assessed within the stated model
Required loss
≈ 131.9 Pa
Pressure headroom
≈ 68.0997 Pa
Electrical input
≈ 109.917 W
Annual energy cost
≈ 65.9501 USD/year
Diameter: ≈ 350 mm
≈ 5.1969 m/s · Within preference
≈ 500 mm × ≈ 250 mm
≈ 4 m/s · Within preference
Cross-sections share one scale across all paths; dimensions above are canonical millimetres. These are internal dimensions after any liner.
| Section | Velocity m/s | Friction Pa | Fittings Pa | Total Pa | Method / limit |
|---|---|---|---|---|---|
| Round supply | ≈ 5.1969 | ≈ 8.69181 | ≈ 24.388 | ≈ 33.0798 | Turbulent flow |
| Rectangular section | ≈ 4 | ≈ 4.55649 | ≈ 19.264 | ≈ 23.8205 | Turbulent flow |
| Step | Added loss Pa | Cumulative Pa |
|---|---|---|
| Path start | 0 | 0 |
| Round supply | ≈ 33.0798 | ≈ 33.0798 |
| Rectangular section | ≈ 23.8205 | ≈ 56.9003 |
| Equipment loss | ≈ 75 | ≈ 131.9 |
Geometry, friction diagnostics and energy details
| Section | Area m² | Hydraulic diameter m | Reynolds | Darcy factor | Solver residual |
|---|---|---|---|---|---|
| Round supply | ≈ 0.0962113 | ≈ 0.35 | ≈ 120,993 | ≈ 0.0187109 | ≈ -6.01474E-12 |
| Rectangular section | ≈ 0.125 | ≈ 0.333333 | ≈ 88,692.4 | ≈ 0.0197107 | ≈ -5.48894E-12 |
Air power ≈ 65.9501 W · estimated annual energy ≈ 329.751 kWh. Display values are approximate, not measured performance. CSV retains full model values and solver diagnostics.
Keep your comparison
CSV includes display drafts and units, canonical inputs, every pressure step and model limitations. Entries stay in this page session.
The model leaves transition friction and rectangular laminar friction unassessed. Its domain excludes velocity above 30 m/s, rectangular aspect ratio above 4 and relative roughness above 0.05; paths above 5,000 Pa calculated loss have no assessed budget or energy estimate. These are model limits, not universal safety thresholds. Method: ASHRAE duct design, Darcy/Colebrook and local fitting losses. Verify the actual system, product data and pressure boundaries before using results.
How to use this calculator
- Choose the 500 L/s comparison or Higher airflow example. Set airflow and its units, inside-dimension units and section-length units. Exact fractions may appear after conversion to preserve physical quantities.
- Enter the available TOTAL-pressure budget on the same path boundaries and a velocity preference. Review density, dynamic viscosity, combined efficiency, annual operating hours and electricity price under the air-property section.
- Name each path and enter equipment loss at the specified airflow. Add sections in path order, choosing round or rectangular clear internal dimensions, straight length, absolute roughness in mm and locally referenced fitting coefficient sum K.
- Duplicate a path to compare different dimensions or coefficients. Add/remove sections as needed. Include transitions, terminals and other applicable losses explicitly; the planner does not choose fitting coefficients or solve a fan curve.
- Inspect cumulative loss, cross-sections and component tables. Investigate unassessed flow regimes, domain limits, exceeded preferences or near-boundary results. The cumulative chart shows normalized step order, not physical distance.
- Download duct CSV or use Selectable CSV to retain display units, canonical inputs, full model values and solver diagnostics. Correct invalid drafts before export; data stays in the current page session.
The Formula
The mathematical logic powering this calculation is:
Use the prescribed volumetric flow Q in m³/s in every section. Round area A = πd²/4 and hydraulic diameter Dh = d. Rectangular area A = ab and Dh = 2ab/(a+b). Dimensions are clear internal dimensions in metres. Mean velocity V = Q/A, Reynolds number Re = ρVDh/μ and velocity pressure Pv = ρV²/2.
Round laminar flow below Re 2300 uses Darcy factor f = 64/Re. Rectangular laminar friction is not replaced by the circular formula. A deliberately unassessed transition region extends through Re 4000 with a relative 1e−10 boundary margin. Above that region, solve the Colebrook equation 1/√f = −2 log10[(ε/Dh)/3.7 + 2.51/(Re√f)]. The bounded solver requires both a small residual and a narrow bracket; failure is not reported as a solved factor.
Section friction loss = f(L/Dh)Pv. Fitting loss = K Pv using that section’s actual mean velocity. The required path loss is the sum of all section friction and fitting losses plus entered equipment loss. This is dissipative total-pressure loss, not static-pressure change across differing section areas. Fitting coefficients and equipment losses must be appropriate to the current flow and geometry; transitions and terminal losses are not added automatically. At zero length the friction contribution is zero where the model domain permits, even if the friction factor is unavailable. Unknown required terms leave the path cumulative loss unknown.
Pressure headroom = entered available total-pressure budget − calculated loss. A numerical band of 1e−8 × max(1, budget, loss) around equality is boundary-uncertain, not a confirmed pass. The entered velocity preference uses the same comparison policy. Air power = Q × total loss in watts; estimated electrical input = air power / combined efficiency. Annual energy = input watts × operating hours / 1000; annual cost = kWh × entered USD/kWh. These are steady-state estimates, not measured or seasonal fan performance.
Model domain: rigid constant-density ventilation paths, velocity no greater than 30m/s, rectangular aspect ratio no greater than 4 and relative roughness no greater than 0.05. Calculated total loss above 5000Pa has no assessed budget or energy result. These are declared model limits, not universal physical safety thresholds. Inputs support 1–4 paths, 1–8 sections each, airflow 1–20000L/s, active dimensions 50–2000mm, lengths 0–1000m, roughness 0–10mm and K 0–100. Density is 0.5–2kg/m³; viscosity 0.01–0.03mPa·s. Numerical results are approximate physics. Exact unit identities include 1ft = 0.3048m, 1in = 25.4mm, 1CFM = 0.4719474432L/s and 1m³/h = 5/18L/s.Worked Example
If you input:
- Airflow / air properties: 500L/s; density 1.204kg/m³; viscosity 0.0181mPa·s
- Baseline sections: 300mm round, 10m, K1.5; 400×200mm rectangular, 8m, K2
- Larger alternative: 350mm round and 500×250mm rectangular; lengths and K unchanged
- Roughness / equipment loss: 0.09mm / 75Pa per path
- Pressure budget / velocity preference: 200Pa total pressure / 8m/s
- Energy assumptions: 60% combined efficiency; 3000h/year; 0.20USD/kWh
Result:
At the entered design point, the baseline requires approximately 199.452Pa and the larger-duct alternative 131.900Pa. Their pressure headroom is approximately 0.548Pa and 68.100Pa. Estimated annual electricity cost is approximately $99.73 and $65.95 at the entered efficiency, hours and price. Both are within the entered pressure and velocity preferences under this model. The small baseline headroom is not a design-margin recommendation. No fan curve, branching flow distribution or seasonal operating profile is inferred.
Frequently Asked Questions
Does this automatically choose the correct duct size?
No. It compares the dimensions you enter at a prescribed airflow. Inspect pressure, velocity, model limits, available space and actual system requirements. The tool does not infer room loads, solve branching flows or perform an ACCA Manual D design.
Can I enter external static pressure as the fan budget?
Only if you have reconciled its measurement boundaries and pressure definition with the modeled path. This comparison uses an available total-pressure budget and dissipative path losses. Static pressure and total pressure are not interchangeable labels, especially when velocities and cross-sections differ.
Why are some friction losses unavailable?
The planner leaves the transition region unassessed and does not apply the circular laminar formula to a rectangular duct. Domain limits or solver failure also prevent an assessed loss. Known local fitting contributions remain visible. An unavailable required friction term is not silently replaced by zero.
What should I enter for local K and equipment loss?
Use coefficients referenced to the actual section velocity and equipment losses applicable at the entered flow. Re-evaluate them when geometry or flow changes. This tool supplies no fitting database and does not automatically account for transitions, terminals, fan-system effects or filter loading.
Are flexible ducts or compressed-air lines supported?
No. The assumptions concern rigid, low-speed ventilation with constant entered air properties. Flexible-duct compression and bends, changing density, compressibility, buoyancy, leakage and thermal effects require other models.
Why does the unit conversion display fractions?
Some exact conversions cannot be represented by a short decimal. The fraction preserves the underlying quantity through unit changes. Blank drafts remain blank; malformed retained dimensions must be corrected before conversion so their meaning cannot change silently.
Are the annual energy numbers measured savings?
No. They estimate steady-state pressure times flow divided by your entered combined efficiency, multiplied by operating hours and electricity price. Real fan efficiency, control behavior, duty cycle and operating point can change. Unassessed paths do not receive an energy estimate.
Similar Calculators
Pipe Pressure Drop Calculator
Compare pipe pressure loss across inside diameters. Calculate Darcy friction, fitting losses, velocity and Reynolds number with explicit transition limits.
Electricity Cost Calculator
Estimate appliance electricity cost from wattage, daily use, electricity rate, and billing fees.
AC Power & Power Factor Calculator
Calculate AC watts, vars, volt-amps and power factor for single-phase or balanced three-phase loads. Combine leading and lagging loads, compare an ideal target PF and export the ledger.
Room Heat Loss & Retrofit Calculator
Explore room heat loss and sensible cooling, compare envelope and ventilation retrofits, and visualize heat flows and outdoor-temperature sensitivity with exact CSV ledgers.
Compressed Air Demand & Receiver Planner
Compare compressor CFM and receiver storage against timed demand. Visualize pressure reserve, recharge and unserved air, with exact stage ledgers and CSV export.