Hydronic Radiator Output & Water Temperature Planner

See whether two hot-water radiator plans cover entered room heat loads at their selected supply and return temperatures. Compare documented panel ratings and exponents. Then identify the room that sets the minimum modeled supply at the same water drop and compare it with an entered cap.

Hydronic heat

Compare radiator output at your water temperatures

Find which rooms fall short and how hot the modeled supply must be at the entered water drop.

Room coverage and supply cap

Combined entered heat load 1,870 W.

Plan A

1 of 3 rooms meet load

Total modeled output
1,901.7 W
Sum of room shortfalls
50.2 W
Minimum modeled supply
56.1036 °C
Controlling room
Living room

Modeled requirement above cap · 55 °C cap at 10 K water drop.

Plan B

3 of 3 rooms meet load

Total modeled output
2,602.9 W
Sum of room shortfalls
0 W
Minimum modeled supply
49.753 °C
Controlling room
Living room

Modeled requirement within cap · 55 °C cap at 10 K water drop.

Plan B meets every entered room load at its selected water temperatures.

Radiator output by room

Compare both plans with each room’s own load. Bars share one scale from 0 to 1,173.4 W.

Plan APlan BEntered room load
Living room

Entered load 900 W.

Living room output. Plan A 856.8 W. Plan B 1,173.4 W. Room load 900 W.
Plan A
856.8 W · 43.2 W short
Plan B
1,173.4 W · 273.4 W spare
Bedroom

Entered load 620 W.

Bedroom output. Plan A 701.9 W. Plan B 960.3 W. Room load 620 W.
Plan A
701.9 W · 81.9 W spare
Plan B
960.3 W · 340.3 W spare
Study

Entered load 350 W.

Study output. Plan A 342.9 W. Plan B 469.2 W. Room load 350 W.
Plan A
342.9 W · 7.1 W short
Plan B
469.2 W · 119.2 W spare
Edit water temperatures and room radiators

Use measured or authored water temperatures. Select catalog ratings at 75/65/20 °C and use each model’s own exponent. Enter per-unit ratings with the number of matching units in each room.

Plan A water temperatures

Plan B water temperatures

The preset compares Purmo Compact C22 with C33 panels at the same entered room loads. Room temperatures and loads are editable example assumptions.

Room 1

Plan A panel ratings
Plan B panel ratings

Room 2

Plan A panel ratings
Plan B panel ratings

Room 3

Plan A panel ratings
Plan B panel ratings

Panel calculations and export

Plan A

Supply 55 °C · return 45 °C · water drop 10 K

Living room
Room air 20 °C · logarithmic excess 29.7201 K
1 × 1,709 W at rating conditions · exponent 1.3358
Modeled minimum supply 56.1036 °C
Bedroom
Room air 22 °C · logarithmic excess 27.6998 K
1 × 1,538 W at rating conditions · exponent 1.3358
Modeled minimum supply 52.5722 °C
Study
Room air 20 °C · logarithmic excess 29.7201 K
1 × 684 W at rating conditions · exponent 1.3358
Modeled minimum supply 55.4528 °C

Plan B

Supply 55 °C · return 45 °C · water drop 10 K

Living room
Room air 20 °C · logarithmic excess 29.7201 K
1 × 2,356 W at rating conditions · exponent 1.3486
Modeled minimum supply 49.753 °C
Bedroom
Room air 22 °C · logarithmic excess 27.6998 K
1 × 2,120 W at rating conditions · exponent 1.3486
Modeled minimum supply 47.4403 °C
Study
Room air 20 °C · logarithmic excess 29.7201 K
1 × 942 W at rating conditions · exponent 1.3486
Modeled minimum supply 49.2629 °C
Download radiator comparison CSV
View selectable CSV

How to use this calculator

  1. Enter each room’s design air temperature and independently determined heat load in watts.
  2. Enter each plan’s supply, return and supply cap in degrees Celsius.
  3. Enter each room’s per-unit rating at 75/65/20 °C, model-specific exponent, and number of equal units for each plan.
  4. Compare the per-room bars with their load marks and inspect the rooms that set the minimum modeled supply.
  5. Use W or Btu/h to read results and export the canonical watt and Celsius calculations.

The Formula

The mathematical logic powering this calculation is:

Use a per-unit manufacturer heat-output rating at 75/65/20 °C and the manufacturer’s exponent for the same radiator configuration. The nameplate or supplier may report a rating at another temperature. Match the reference before entering it. The preset references Purmo Compact C22 or C33 panels at 600 mm high, across 1000, 900 and 400 mm lengths. The room temperatures and heat loads in the preset are illustrative.

For supply S, return R and room air T, the logarithmic temperature difference is L = (S − R) ÷ ln((S − T) ÷ (R − T)). Require S ≥ R > T. When supply equals return, the logarithmic mean has the limit S − T. The 75/65/20 reference has L₀ ≈ 49.83288654564 K. Per-room modeled output = count × per-unit rating × (L ÷ L₀)^n. Use the logarithmic model only with matching catalog information. Manufacturer methods that specify a different temperature basis or correction table require their own adjustment.

The required logarithmic temperature difference Lreq for a room is L₀ × (room load ÷ total rated room output)^(1/n). Hold the selected water drop D = S − R fixed. At D > 0, solving the logarithmic relation gives required supply = T + D + D ÷ (exp(D ÷ Lreq) − 1). At D = 0, required supply = T + Lreq. The maximum across the entered rooms controls the plan. Compare that modeled minimum with the entered cap. Minimums above the supported 100 °C range are reported as beyond the range. This cap is a worksheet assumption. It does not set an allowable operating temperature.

A room meets its load when modeled output reaches the entered heat requirement, to within a relative numerical tolerance of 10^−12 for floating-point equality. Sum only individual shortages for the plan’s shortage figure. Surplus from one room does not fill another room’s modeled shortage. Enter one to six rooms, each with 1–20 equal units per plan, 5–40 °C room air, 5–100 °C water temperatures and cap, 0.1–50,000 W ratings and loads, and an exponent in [0.5,3.0]. Decimal measurements support up to four places. The Btu/h display uses 1 Btu (International Table) = 1,055.05585262 J. Inputs and exported data remain in watts and Celsius.

The worksheet compares steady output at entered water and room temperatures. It does not estimate building heat loss, circulation, pressure drop, energy use, heating cost, equipment compatibility, or safe and approved system settings.

Worked Example

If you input:

  • Shared loads: 900 W at 20 °C in the living room, 620 W at 22 °C in the bedroom, and 350 W at 20 °C in the study.
  • Both operating points: 55 °C supply, 45 °C return and a 55 °C authored supply cap.
  • Plan A: Purmo C22 ratings 1,709 / 1,538 / 684 W at 75/65/20 °C, exponent 1.3358.
  • Plan B: Purmo C33 ratings 2,356 / 2,120 / 942 W at 75/65/20 °C, exponent 1.3486.

Result:

A models 1,901.7 W against 1,870 W of total load, but two rooms fall short by 50.2 W combined. B models 2,602.9 W, meeting all three loads. At the authored 10 K water drop, modeled minimum supply is 56.1036 °C for A and 49.753 °C for B.

Frequently Asked Questions

Why can combined output exceed the total heat load while some rooms are short?

Each panel serves its own room in this worksheet. A room with extra output cannot make up another room’s missing output, so individual shortages are summed separately.

Is logarithmic excess the same as the usual mean water temperature minus room temperature?

They differ when supply and return differ. This worksheet uses the manufacturer’s logarithmic method and recalculates the rating reference on the same basis.

Where do I get the catalog exponent?

Use the manufacturer’s technical output data for the exact model and type. The reference rating and exponent should describe the same radiator.

How should I use the minimum modeled supply?

It estimates the supply that delivers each entered load when the selected supply-to-return drop stays fixed. The entered cap is a comparison target. Actual drop and circulation may change when the system operates.

Do I multiply the catalog rating by the number of panels before entering it?

Enter the per-unit rating. The separate count applies to matching radiators serving that room with the same modeled water and air temperatures.

Similar Calculators