Heat Exchanger LMTD & Heat Balance Calculator

Compare two steady sensible-heat records from a two-stream exchanger. Enter inlet and outlet temperatures and thermal capacity rates, then reconcile hot-side release and cold-side gain. Compare ideal parallel or counterflow terminal temperature differences and infer UA only when the selected record has a positive driving force and meets your entered balance tolerance.

Terminal heat balance

Compare heat exchanger records and terminal differences

Reconcile paired hot and cold duties, compare the positive terminal log mean, and check whether each record supports an inferred conductance.

Measured sensible heat exchange

Use simultaneous steady single-phase records and documented thermal capacity rates. The preset values are illustrative.

Temperatures and capacity rates

Record A
Record B

Only Record A supports a conditional UA estimate.

Entered mismatch tolerance 5% of the larger absolute duty.

Record A terminal LMTD
37.4444 K
40 K at the hot inlet end, 35 K at the hot outlet end
Hot release / cold pickup
60 kW / 60 kW
Hot minus cold
0 kW
0% relative mismatch. Within entered balance tolerance.
Conditional UA
1.6024 kW/K
Mean duty used for estimate.
Record B terminal LMTD
32.791 K
61 K at the hot inlet end, 15 K at the hot outlet end
Hot release / cold pickup
70 kW / 64.8 kW
Hot minus cold
+5.2 kW
7.4286% relative mismatch. Above entered balance tolerance.
Conditional UA
Heat balance is outside the entered tolerance.

Terminal temperatures by flow arrangement

Straight guides connect the recorded terminals. Both records share a °C scale, and the arrows indicate flow direction.

Terminal temperatures by flow arrangementRecord A uses Counterflow and has terminal differences 40 K and 35 K. Record B uses Parallel flow and has terminal differences 61 K and 15 K.Record ACounterflow245790Hot inlet endHot outlet endRecord BParallel flow245790Hot inlet endHot outlet end
  • Hot stream
  • Cold stream
  • Paired ends
Open terminal and duty ledger
Terminal and heat duty ledger
Recorded or calculated termRecord ARecord B
Hot inlet, outlet90 °C to 60 °C85 °C to 57 °C
Cold inlet, outlet25 °C to 50 °C24 °C to 42 °C
Hot release60 kW70 kW
Cold pickup60 kW64.8 kW
Signed mismatch0 kW+5.2 kW
Hot inlet end difference40 K61 K
Hot outlet end difference35 K15 K
Duty basisMean dutyHot duty
Duty used for UA60 kWUnavailable
UA outcome1.6024 kW/KHeat balance is outside the entered tolerance.
Show copyable CSV

How to use this calculator

  1. Enter the four temperatures and the two thermal capacity rates for each recorded operating condition.
  2. Choose the documented flow arrangement so the corresponding terminals are paired correctly.
  3. Set your comparison tolerance and choose a duty basis if you want to infer UA.
  4. Read signed hot release and cold gain, the mismatch and end differences. Inspect the plotted terminal positions and the ledger.
  5. Download the actual inputs, duty quantities, gating states and computed estimates.

The Formula

The mathematical logic powering this calculation is:

Use recorded temperatures in °C and steady thermal capacity rates in kW/K. For a supplied stream at the test condition, thermal capacity rate is mass flow rate × specific heat, using kg/s and kJ/(kg·K). Hot release = Cₕ × (hot inlet − hot outlet). Cold gain = C𝚌 × (cold outlet − cold inlet). Both are positive in the supported heat-transfer direction. Signed residual = hot release − cold gain. Relative mismatch = |residual| ÷ max(|hot release|, |cold gain|) × 100%. When both measured duties are zero the relative mismatch is undefined. The comparison with your tolerance is inclusive and exact for the entered decimals.

Define the exchanger’s first and second ends in hot-flow order. Parallel flow pairs the two inlets and the two outlets, each with hot minus cold. Counterflow pairs hot inlet with cold outlet and hot outlet with cold inlet. Both terminal differences must be strictly positive for the listed log mean. The logarithmic mean temperature difference is (larger − smaller) ÷ ln(larger ÷ smaller). Equal end differences have their common value.

The estimate UA = selected duty ÷ LMTD requires a chosen hot, cold, or arithmetic mean duty, two positive sensible duties, two positive terminal differences and a heat balance within the entered tolerance. This is one conditional estimate of overall conductance in kW/K, not a fitted surface area or a separate U. Positive temperature-pair arithmetic may still be shown when the duty direction or balance prevents UA.

Enter −150 to 600 °C, capacity rates 0.001–5,000 kW/K, tolerance 0–100%, up to three decimal places. The terminal plot uses schematic straight links through the entered temperatures, with one temperature scale for both records. The model covers ideal single-pass sensible heat exchange. It does not calculate a corrected multi-pass or crossflow mean, material compatibility, phase change, process settings, or equipment safety and capacity.

Worked Example

If you input:

  • Record A: Counterflow, 90→60 °C hot, 25→50 °C cold, capacities 2 and 2.4 kW/K
  • Record B: Parallel, 85→57 °C hot, 24→42 °C cold, capacities 2.5 and 3.6 kW/K
  • Tolerance: 5%

Result:

Record A has 60 kW on each side and terminal differences of 40 and 35 K. LMTD is 37.4444 K and the selected mean duty gives 1.6024 kW/K inferred UA. Record B has 70 kW hot release and 64.8 kW cold gain, a +5.2 kW mismatch or 7.4286% of the larger duty. Its positive terminal LMTD is 32.791 K and the worksheet withholds UA at the entered 5% tolerance.

Frequently Asked Questions

Which terminal temperatures are paired?

Parallel flow pairs inlets at one end and outlets at the other. Counterflow puts the cold outlet at the hot inlet end and the cold inlet at the hot outlet end.

Can cold outlet temperature be above hot outlet temperature?

In counterflow those outlets are at different ends. Compare each hot reading with the cold reading at the same physical end. A nonpositive paired difference prevents the positive log mean in this worksheet.

Why can LMTD appear when UA is unavailable?

The terminal arithmetic depends on temperatures and arrangement. Estimating conductance also needs a chosen duty, two positive measured duties and agreement under your entered tolerance.

What if both terminal differences are equal?

The limit of the logarithmic expression is their common positive difference. The calculator uses that limiting value.

What does a positive signed mismatch mean?

Hot-side heat release exceeds cold-side pickup by that amount under the entered capacity rates. Instrument accuracy, condition variation and actual heat loss are separate possibilities that the worksheet does not infer.

Can I treat each line as an internal temperature prediction?

The graphic connects recorded terminal temperatures with straight guide segments. Internal profiles and performance depend on equipment and conditions.