Duct Airflow & Velocity Traverse Calculator

Use your own measured normal velocities at a clear rectangular duct plane. Compare area-weighted airflow, differences between passes, and target flow across the entered error bounds.

Duct measurement worksheet

Compare two measured duct traverses

Only Pass A stays inside the entered flow band.

Pass A

2.7 m³/s net

5,720.97600888 cfm at the measurement plane

Full interval in band · 2.6 to 2.8 m³/s

Forward
2.7 m³/s
Reverse magnitude
0 m³/s
Area-weighted mean
5.4 m/s
Unweighted mean
5 m/s

Unweighted minus area-weighted flow · -0.2 m³/s

Pass B

1.78 m³/s net

3,771.60640585 cfm at the measurement plane

Interval outside target · 1.68 to 1.88 m³/s

Forward
1.98 m³/s
Reverse magnitude
0.2 m³/s
Area-weighted mean
3.56 m/s
Unweighted mean
3.16666667 m/s

Unweighted minus area-weighted flow · -0.19666667 m³/s

Difference and mean velocity

Face area 0.5 m² · target mean velocity 5.2 to 5.6 m/s

Pass B minus A · -0.92 m³/s · interval -1.12 to -0.72 m³/s

Edit clear areas and velocity readings

Enter signed normal velocity. Keep one direction convention and the same measured plane for both passes.

Clear rectangle and target
Pass A
Pass B

Net flow ranges and target

The gold region marks the target. Each track shows its net flow and the bounds from the entered velocity error.

Airflow in cubic meters per secondPass A 2.6 to 2.8 m³/s, Pass B 1.68 to 1.88 m³/s. Target 2.6 to 2.8 m³/s.AB0 m³/s2.8 m³/s

Velocity across the duct face

Areas follow the entered row and column proportions. Values are signed m/s. Amber and a dashed outline indicate reverse flow.

Measured signed velocity by duct cellPass A. R1C1 4 m/s. R1C2 5 m/s. R1C3 8 m/s. R2C1 3 m/s. R2C2 4 m/s. R2C3 6 m/s.458346

Reverse-flow area · 0% at measured values. With entered velocity error, 0% to 0%.

Review exact cell measurements and CSV
Pass A cell readings and signed contributions
CellArea (m²)Velocity (m/s)Flow (m³/s)
R1C10.0440.16
R1C20.0650.3
R1C30.180.8
R2C10.0630.18
R2C20.0940.36
R2C30.1560.9

Use the worksheet for a documented six-cell estimate. Probe placement, flow distortion, sampling uncertainty and standardized test procedures require separate review.

How to use this calculator

  1. Enter the measured inside widths of the three columns and heights of the two rows. Use the clear dimensions at the plane.
  2. Enter each pass's representative normal velocity for every cell. Use positive and negative signs consistently.
  3. Enter the absolute velocity error per cell and the desired net flow range.
  4. Compare both pass ranges, the signed face map and the change from A to B.
  5. Open or download the exact ledger to trace cell area, velocity, contribution and total.

The Formula

The mathematical logic powering this calculation is:

Divide the clear rectangular measurement plane into two rows and three columns represented by your readings. For each cell, multiply its entered width and height in millimeters and divide by 1,000,000 to get square meters. Its measured contribution is area × signed normal velocity in cubic meters per second. Add positive contributions for forward flow. Sum the magnitudes of negative contributions for reverse flow. Net volumetric flow is forward minus reverse at the local measurement conditions.

The area-weighted mean is net flow divided by the full clear area. An unweighted mean of the six velocities is shown for comparison, along with the implied flow difference. It gives the same weighted result for equal areas. Divide the target flow limits by the same clear area to get the required mean velocity. Values in cfm use the international foot of exactly 0.3048 m.

Enter a common absolute velocity error u. For measured cell velocity v the worksheet models [v − u, v + u]. Weight both bounds by that cell's area and sum. The target check classifies the resulting closed net-flow interval as inside, overlapping or outside. Touching counts as an intersection. An interval is inside only when both of its endpoints meet the target.

Reported reverse area adds the areas whose measured signed velocity is negative. The always-reverse lower bound uses cells whose upper velocity stays below zero. The possibly-reverse upper bound uses cells whose lower velocity falls below zero. For the difference B minus A, subtract A's upper bound from B's lower, and A's lower from B's upper. This is a conservative entered-error envelope, separate from statistical inference about repeatability.

Dimensions are positive through 100,000 mm per row or column; velocities are −500 to +500 m/s and each target is −100,000,000 to +100,000,000 m³/s. Absolute velocity error is 0–500 m/s. Inputs accept up to eight fractional places. Arithmetic uses exact rational values, including CFM conversion and boundary checks.

This is a six-cell integration worksheet for supplied representative normal velocities, not a prescribed probe layout or test standard. Its bounded inputs do not estimate flow distortion, density corrections, probe alignment, location bias, pulsation or spatial sampling uncertainty. Use measured clear internal areas and compare readings from the same plane and direction convention.

Worked Example

If you input:

  • Clear face: Column widths 200, 300 and 500 mm. Row heights 200 and 300 mm.
  • Pass A velocities: 4, 5, 8, 3, 4 and 6 m/s, in row order.
  • Pass B velocities: 3, 3, −2, 3, 5 and 7 m/s, in row order.
  • Comparison: 2.6–2.8 m³/s target and ±0.2 m/s velocity error.

Result:

The clear face is 0.5 m². Pass A gives 2.7 m³/s with an interval of 2.6–2.8. Pass B gives 1.78 m³/s with a 0.2 m³/s reverse contribution. Only Pass A stays fully inside the entered target.

Frequently Asked Questions

When can I average readings without area weighting?

The same area for every reading makes the arithmetic mean equivalent. With unequal areas, weight velocity by the area represented.

Why can forward and reverse be nonzero when net flow is zero?

Separate areas can carry equal volumes in opposite directions. Net flow subtracts the reverse magnitude from forward flow.

Do I enter speed or signed velocity?

Enter the component normal to the plane with its direction. A scalar speed alone cannot distinguish reverse flow.

Is calculated CFM corrected to standard air?

The worksheet converts units at the measurement plane. A standard-air calculation needs density and reference conditions.

Does the entered error account for a disturbed flow profile?

It gives the supplied pointwise velocity bounds. Spatial sampling, probe alignment and upstream obstructions need separate analysis.

What if the range for the change includes zero?

The stated velocity bounds admit changes of either sign or no change, depending on where zero lies in the interval.