Room Lumens & Maintained Illuminance Calculator
Pick your workplane area and maintained illuminance target. Use a measured existing average or model your existing fixtures with documented luminaire output, room utilization and a retained-light assumption. Compare two ways to add light, identify the minimum whole count and see what your entered position and power limits allow.
Compare maintained lumens and added fixtures
Use documented fixture output and room utilization, then compare whole counts against your own maintained target and limits.
Edit workplane, baseline and fixture options
Baseline fixture groups
Existing luminaires
Use documented utilization for the workplane and your retained-light assumption. Leave unknown wattage blank.
Edit Option A fixture
Edit Option B fixture
Maintained light at each fixture count
Dashed marker · 300 lux maintained target
Fixture quantity and constraint ledger
Both options start from the same baseline. Each projection adds the selected fixture type to that baseline.
Option A
Meets the entered target and limits
- Added fixtures required
- 4
- Entered position cap
- 4
- Power-limited count
- 5
- Maintained lumens per fixture
- 1,120 lm
- Initial average at required count
- 413.333333 lux
- Maintained average at required count
- 330.666667 lux
- Total watts at required count
- 196 W
- Known count ceiling
- 4
- Maintained average at ceiling
- 330.666667 lux
Option B
Exceeds the entered power cap
- Added fixtures required
- 4
- Entered position cap
- 6
- Power-limited count
- 3
- Maintained lumens per fixture
- 1,104 lm
- Initial average at required count
- 410 lux
- Maintained average at required count
- 328 lux
- Total watts at required count
- 244 W
- Known count ceiling
- 3
- Maintained average at ceiling
- 282 lux
Show baseline quantities
Known baseline watts · 84 W
Entered power cap · 225 W
Initial workplane lumens · 4,320 lm
Maintained workplane lumens · 3,456 lm
Show selectable CSV
How to use this calculator
- Edit workplane, baseline and fixture options. Enter the area and a maintained average target.
- Enter baseline fixture groups, or switch to a measured average. Record watts separately from optical quantities.
- Enter luminaire output, documented room utilization and a retained-light assumption for each added fixture option.
- Compare the minimum required counts with any entered position and watt limits. Inspect the projection at known count ceilings.
- Review the exact fixture worksheet in CSV.
The Formula
The mathematical logic powering this calculation is:
The workplane is the surface whose average illuminance you want to estimate. Use its measured area and a user-entered average maintained target. Lux is lumens per square metre. Foot-candles are lumens per square foot. The worksheet uses exactly 0.09290304 m² per ft².
For fixture mode, enter initial emitted lumens per complete luminaire and its documented room utilization factor for the chosen workplane and room. The factor is a proportion of luminaire lumens arriving at the workplane under the modeled conditions. Use luminaire lumens rather than bare lamp lumens. Initial workplane lumens per luminaire = emitted lumens × room utilization percentage ÷ 100. Maintained workplane lumens = initial workplane lumens × retained-light percentage ÷ 100. The retained-light percentage is your assumption for the planning condition, taking care to avoid double-counting existing allowances. Multiply by group count, then sum all groups. Total rated system watts are known when each active group's wattage is entered. A zero-count group contributes zero.
In measured mode use an observed average at the same workplane and operating condition. Equivalent workplane lumens for the comparison = measured average × area. This mode uses the observed baseline as its maintained reference. Initial fixture delivery remains unavailable without a fixture model. Enter measured baseline watts separately if known. Keep outdoor light, switched fixtures and other conditions consistent with the intended comparison.
Maintained average illuminance = total maintained workplane lumens ÷ area. Required added maintained lumens = max(0, target average × area − baseline workplane lumens). When the baseline already meets your target, zero extra fixtures suffice. Otherwise the minimum added count is ceil(required added lumens ÷ maintained workplane lumens per new fixture). A zero denominator means that candidate does not contribute maintained light. Each option adds a single selected candidate fixture type to the same baseline.
An entered position limit applies to added fixtures. For a positive known wattage and known remaining power, the power count ceiling is floor((entered watt cap − known baseline watts) ÷ candidate watts). A zero-watt candidate does not impose a finite additional-watt count ceiling if the baseline watts already fit. A baseline over the cap cannot meet the power condition even with zero additions. If the power cap has been entered but actual watt data is missing, preserve the optical count and report an incomplete power comparison. A known count ceiling combines active count constraints with the worksheet maximum. A projection at that ceiling remains arithmetic, including when baseline power already exceeds the cap.
Use up to six existing fixture groups and counts or position limits from 0 to 1,000,000. Area must be positive through 1,000,000 m² equivalent. Targets and measured averages accept 0–1,000,000 lux equivalent. Initial fixture lumens, rated fixture watts and retained percentages must be nonnegative and within the entered worksheet bounds. Rated luminaire output and power have a maximum of 1,000,000 in their units, and percentages have a maximum of 100. Enter up to six decimal places or exact fractions. Unit switching preserves the same quantities. Counts and decisions use exact rational values, while displayed decimals round to six places.
This is an average-lumen comparison using entered data. Layout, uniformity, glare, emergency lighting and wiring require their applicable evaluations. Use documented room-specific optical factors and a target tied to your workplane.Worked Example
If you input:
- Workplane: 24 m² with an entered target of 300 lux
- Baseline: Six 1,200 lm luminaires, 60% utilization, 80% retained light, 14 W each
- Candidate cap: 225 W for the complete comparison
- Additions: A 2,000 lm, 70% utilization, 80% retained, 28 W. B 2,300 lm, 60%, 80%, 40 W.
Result:
Baseline maintained average is 144 lux. Option A needs four additions and reaches 330.666667 lux at 196 W. Option B also needs four additions, but its power cap allows three. Three B fixtures provide 282 lux under the entered optical factors.
Frequently Asked Questions
How many lumens do I need for my room?
Workplane lumens for the entered maintained target equal target average times workplane area. Fixture-rated lumens depend on documented utilization and your entered retained-light allowance.
Why do both options need the same count but pass differently?
The light calculation finds each minimum whole count first. Independent power and position constraints then determine whether that count fits.
Can I use a measured baseline with unknown power?
Yes. The optical comparison remains available. An entered power cap needs enough recorded baseline and candidate watt data to confirm its condition.
What does the maintained percentage include?
Use the light retained for the planning condition under your documented assumptions. It can include documented depreciation or maintenance effects, provided the factors do not count a loss twice.
Does average lux describe the darkest spot or glare?
It describes the average under the entered factors. Point levels, uniformity, glare and placement require the appropriate photometric analysis.
Similar Calculators
Recessed Lighting Layout Calculator
Compare recessed-light center grids, spacing and wall offsets. Inspect coordinates and entered keep-out conflicts on a scaled room plan.
Electricity Cost Calculator
Estimate appliance electricity cost from wattage, daily use, electricity rate, and billing fees.
Window Film Light Transmission & Quote Planner
Compare architectural window film light transmission on matching glazing, whole-roll cut plans and entered installation prices.
High-Bay Lighting & Workplane Illuminance Calculator
Compare two high-bay fixture layouts using four candela readings. Inspect horizontal illuminance at nine workplane samples and compare minimum-to-mean ratios.
Foot-Candle Workplane Survey & Lumens Calculator
Compare two workplane meter surveys across unequal regions. Calculate weighted foot-candles, estimated incident lumens and qualifying area.
Daylight Dimming & Energy Use Calculator
Compare a fixed lighting mode with a daylight-responsive schedule using measured lux and watts. Find the light level and energy use for each time block.