Daylight Dimming & Energy Use Calculator

Enter your measured lamp contributions and plug or circuit power for the available modes. See how much energy the modeled schedule uses to maintain an entered workplane illuminance target.

Measured lighting controls

Compare daylight and electric lighting schedules

Both schedules reach the target in every block.

Fixed schedule

280 Wh

Minutes below target
0
Lowest block
500 lx

Adaptive schedule

147.4 Wh

Minutes below target
0
Lowest block
500 lx
Inspect workplane light by time block
  • Daylight
  • Electric light
  • Target 500 lx

Morning · 120 min · peak 800 lx

Fixed schedule

Mode
Full
Total light
600 lx
Block energy
70 Wh
Target check
Meets target

Adaptive schedule

Mode
Mid
Total light
500 lx
Block energy
40 Wh
Target check
Meets target
Measured power and light levels

Mode name, electric-only lux, input watts. Use commas or tabs.

Block name, whole minutes, daylight-only lux. Use commas or tabs.

Review block energy and exact CSV
Exact schedule inputs and light reconciliation
Time blockMinutesDaylightFixed lightFixed energyAdaptive lightAdaptive energy
Morning120300 lx600 lx70 Wh500 lx40 Wh
Noon180500 lx800 lx105 Wh500 lx2.4 Wh
Afternoon180200 lx500 lx105 Wh500 lx105 Wh

How to use this calculator

  1. Enter the workplane threshold in lux and the mode name for the fixed schedule.
  2. Record each measured mode’s electric-only contribution in lux and electrical input power in watts.
  3. Enter a label, duration and daylight-only lux for each time block.
  4. Compare energy and minutes below target, inspect the selected modes and download the exact CSV.

The Formula

The mathematical logic powering this calculation is:

For each time block, add its daylight-only lux to the separately measured electric contribution of a lighting mode. Use the same point and plane for all readings and include support loads such as standby watts in the mode data you enter. Hold each block’s representative daylight and each mode’s input power constant for its duration.
The fixed schedule keeps the named baseline mode. The adaptive schedule selects the least power among measured modes reaching the entered target. Equal draw picks the first matching entered mode. If no level meets the target, use the brightest entered level and keep the shortfall visible. Equal maximum output picks the least power, then row order.
Energy in watt-hours is input watts × minutes ÷ 60, summed across the entered blocks. Duration below target is the sum of minutes in failed blocks. The report covers only the entered schedule, up to 1,440 minutes, and uses modes as measured. Readings at other points, daylight variation inside blocks, sensor delays and transitions require separate measurements.

Worked Example

If you input:

  • Target: 500 lx
  • Durations: 120, 180 and 180 minutes
  • Fixed level: 35 W at 300 lx
  • Adaptive levels: 20 W, 0.8 W and 35 W

Result:

Both schedules reach 500 lx in every block. The fixed schedule uses 280 Wh and the adaptive schedule uses 147.4 Wh. Reducing the last daylight reading from 200 lx to 199.99 lx leaves both schedules below the target in that block.

Frequently Asked Questions

Should I enter the output percentage printed on the dimmer?

Use measured lux and watts for each available mode. A percentage setting alone cannot describe the light contribution or power.

What if sufficient daylight is already available?

Any mode that reaches the target qualifies, including an off or standby mode if you entered one. The adaptive schedule chooses the qualifying mode with the lowest watts.

Can a lower-power schedule still miss the target?

Yes. If no measured mode can supply the necessary light in any block, the report shows the brightest mode and how long the modeled light stays below the target.

What does the chart compare?

It shows daylight and the corresponding electric contribution for each schedule on a shared scale. Block widths follow duration.

Can I estimate this room’s expected whole-day energy?

Include all blocks you want modeled, with representative measurements on the same basis. Run separate schedules for day types whose daylight or occupancy differs.