Valve Cv Calculator & Catalog Travel Window
Preview two catalog Cv tables with an independently supplied pressure drop range across the valve. See the modeled flow envelope, inspect possible and whole-band travel ranges, and audit the exact curve interpolation.
Compare valve Cv and catalog travel
Use catalog Cv rows and an independently supplied valve pressure drop range to see where the modeled flow meets your target.
Both tables have a whole-band travel range.
Possible Cv 7.5 to 16.6667 · whole-band Cv 10 to 12.5.
Valve A
Possible travel 37.5% to 83.333%.
Whole-band travel 50% to 62.5%.
60% travel
Cv 12 · 36 to 48 US gpm.
Valve B
Possible travel 20.834% to 86.111%.
Whole-band travel 50% to 79.166%.
60% travel
Cv 10 · 30 to 40 US gpm.
Travel ranges round inward to 0.001 percentage-point input precision.
Inspect modeled flow by catalog travel
- Modeled flow band
- Entered flow target
- Preview travel
Edit flow and pressure inputs
Use the documented differential across the valve for a suitable nonchoked clean-liquid case.
Edit catalog Cv tables
Enter 2–11 rows per valve. Put travel percent first and Cv second, separated by a comma, tab or space. Use one pair per line.
Review exact thresholds and table rows
Whole-band Cv: 10 to 25/2.
Valve A
Possible travel 75/2 to 250/3.
Whole-band travel 50 to 125/2.
- 0% travel · Cv 0
- 25% travel · Cv 5
- 50% travel · Cv 10
- 75% travel · Cv 15
- 100% travel · Cv 20
Valve B
Possible travel 125/6 to 775/9.
Whole-band travel 50 to 475/6.
- 0% travel · Cv 0
- 25% travel · Cv 9
- 50% travel · Cv 10
- 75% travel · Cv 10
- 100% travel · Cv 25
Show Cv travel CSV text
How to use this calculator
- Enter your documented valve-only pressure drop range, liquid specific gravity and target flow band.
- Copy the travel and Cv pairs from each catalog table. Keep the product's travel basis for both entries.
- Move the preview control to inspect interpolated Cv and modeled flow at one travel.
- Read the possible and whole-band travel windows. Use the exact ledger when a rounded bound is close to a measured value.
- Export the supplied table values and exact results.
The Formula
The mathematical logic powering this calculation is:
The worksheet uses Q = Cv × √(ΔP ÷ SG) for modeled nonchoked, single-phase clean liquid flow. Q is U.S. gallons per minute, ΔP is the pressure drop directly across the valve in psi, and SG is liquid specific gravity. Supply the documented ΔP and SG for a case where that simplified relationship is applicable. Manufacturer factors for choking, viscosity, flashing, attached fittings and installed system behavior are separate inputs to a full engineering analysis.
At each catalog travel, the low and high pressure drops produce a flow band. For a target flow band [Qlo, Qhi], some pressure in the entered band can produce a matching modeled flow when Cv is between Qlo × √(SG ÷ ΔPhi) and Qhi × √(SG ÷ ΔPlo). The whole pressure band produces modeled flows within the target when Cv is between Qlo × √(SG ÷ ΔPlo) and Qhi × √(SG ÷ ΔPhi). An inverted interval gives no whole-band Cv result.
Within each catalog table, interpolate linearly between adjacent entered rows. Travel must increase, and Cv may rise or remain flat. Use the first and last matching values for inclusive bounds, which retain all of a matching plateau. The upper and lower Cv comparisons use exact squared bounds. Each inverse endpoint is retained as a rational or radical expression. The displayed travel window rounds inward to entered 0.001 percentage-point precision. Extrapolation outside the first and last row is outside the worksheet.
Paste 2–11 rows per option with travel percent first and Cv second. Use a comma, tab or space between numbers, with one row per line and no headers. Travel can span any documented subset of 0–100%. The catalog curves are inherent input data. The comparison models prescribed conditions and gives no prediction of installed pressure feedback, product suitability or a safe setting. The worked examples use illustrative tables.Worked Example
If you input:
- Specific gravity: 1
- Valve differential: 9 to 16 psi
- Target: 30 to 50 US gpm
- Valve A Cv: 0, 5, 10, 15, 20 at 0, 25, 50, 75, 100% travel
- Valve B Cv: 0, 9, 10, 10, 25 at the same travel points
Result:
The whole-band Cv window is 10 to 12.5. It maps to 50–62.5% for Valve A and 50–79.166% at the accepted precision for Valve B. At 60% travel, A models 36–48 US gpm and B models 30–40 US gpm.
Frequently Asked Questions
What is the valve flow coefficient Cv?
Cv is a reference measure of how much water a particular opening passes at one psi of pressure drop under the test convention. The worksheet uses catalog Cv at each entered travel.
Where does the entered pressure drop come from?
Use a measured or documented differential directly across the valve for the condition of interest. Total supply pressure and pipe-only pressure losses describe different quantities.
Why can the whole-band travel window disappear?
The lower pressure may need a bigger Cv to reach the minimum flow than the higher pressure permits at the maximum flow. No constant Cv can satisfy both limits in that case.
How does a plateau affect inverse interpolation?
If a plateau exactly equals either bound, the earliest or latest matching travel is retained at that side of the interval. The full matching constant segment stays included.
Can this compare compressible gas or steam?
The model covers the simplified clean-liquid relationship entered here. Gas, steam, cavitation, flashing and operating constraints need the appropriate manufacturer method.
Why is a preview reading unavailable after a table edit?
The preview travel must be within the first and last table rows. Move into the documented range or enter additional supported rows.
Similar Calculators
Pump Curve & Operating Point Planner
Compare pump curves and speeds against system head. Visualize operating flow, runtime, electrical energy and whether your target volume fits the available hours.
Pipe Pressure Drop Calculator
Compare pipe pressure loss across inside diameters. Calculate Darcy friction, fitting losses, velocity and Reynolds number with explicit transition limits.
Measured Pump Head Calculator & Tap Audit
Calculate pump head from recorded suction and discharge pressures, pipe sizes, elevations and flow. Compare measured head and entered loss corrections.
Pump Flow per Hour Calculator
Pump Flow per Hour for the exact fields in this tool, with clear inputs and an immediate result for planning or comparison.
Hydraulic Cylinder Force & Cycle Calculator
Compare push and pull force for two cylinders. Account for opposing chamber pressure, separate flow caps and the entered load in each direction.