Pump Curve & Operating Point Planner

A pump’s advertised flow is not the flow it will deliver against your system resistance. Enter a base-speed head and efficiency curve, calibrate a passive system curve, and compare up to four pump or speed scenarios. The planner finds supported intersections, distinguishes hydraulic, shaft and electrical power, and checks the runtime needed for your chosen daily volume. Inspect curve samples, compare operating-window shortfalls and export the complete analysis. This can help explore a pool pump run-time question or another water-transfer scenario when you have suitable curve and system data. It does not select a safe pump size, prescribe pool turnover, evaluate NPSH or establish equipment suitability. The two editable examples use fictional curves, not manufacturer ratings.

Pump curves • Flow • Energy

Find the flow. See the energy tradeoff.

Compare pump speeds against your system resistance, then check which scenarios can move your target volume in the available hours.

75% speed has the lowest modeled target energy among scenarios that meet the operating window.

Compare flow, runtime and energy

Authored pump curves and constant system assumptions. Lower energy helps only when the required volume fits the operating window. This does not assess equipment suitability or water quality.

Inputs below remain in SI units.

Lowest eligible target energy
4.086 kWh
75% speed
Operating flow
15 m³/h
At 8.438 m head
Required runtime
8 h
8 h/day available
Target energy cost
USD 1.02
For 120 m³

1. 100% speed

Target fits the window

20 m³/h

Target energy
7.264 kWh
Required runtime
6 h
Electrical input
1.211 kW
Window shortfall
0 m³

2. 75% speed

Lowest eligible target energy

15 m³/h

Target energy
4.086 kWh
Required runtime
8 h
Electrical input
0.511 kW
Window shortfall
0 m³

3. 50% speed

Target exceeds the window

10 m³/h

Target energy
1.816 kWh
Required runtime
12 h
Electrical input
0.151 kW
Window shortfall
40 m³

Target energy assumes the full required runtime, beyond your entered window.

4. 125% speed

Target fits the window

25 m³/h

Target energy
11.35 kWh
Required runtime
4.8 h
Electrical input
2.365 kW
Window shortfall
0 m³

Pump and system intersection

Head versus flow
Head (m) · starts at 0Top: 50.625
Pump curves and passive system headEach numbered, patterned pump curve stays within its supplied flow range. Outlined circles mark supported operating points. The black square is the inspected curve sample. Use the scenario and sample controls and equivalent tables for values.
0 m³/h37.5 m³/h
  • 1. 100% speed · 20 m³/h at 15 m
  • 2. 75% speed · 15 m³/h at 8.438 m
  • 3. 50% speed · 10 m³/h at 3.75 m
  • 4. 125% speed · 25 m³/h at 23.438 m
  • Black dashed line: system head.

The system curve continues above the displayed head range after 36.742 m³/h. Pump ranges and operating results are unchanged.

Runtime needed for your target

Move 120 m³ in 8 h/day. The dashed marker shows your available time.

0 h12 h
100% speed6 h · 7.264 kWh

Fits the entered window.

75% speed8 h · 4.086 kWh

Fits the entered window.

50% speed12 h · 1.816 kWh

Exceeds the window; shortfall 40 m³.

125% speed4.8 h · 11.35 kWh

Fits the entered window.

Longer required runtimes are hypothetical requirements, not an achievable daily schedule. Pumping a chosen volume alone does not establish adequate pool filtration.

Inspect 75% speed

Inspected curve sample: 15 m³/h at 8.4375 m; pump efficiency 75%. This sample is the solved operating point.

Selected operating point and energy account

Operating flow
15 m³/h
Operating head
8.438 m
Pump / motor-drive efficiency
75% / 90%
Hydraulic / shaft power
0.345 / 0.46 kW
Electrical input
0.511 kW
Specific electrical energy
0.034051 kWh/m³
Target runtime
8 h
Target energy / cost
4.086 kWh / USD 1.02
Volume within the window
120 m³
Window energy / cost
4.086 kWh / USD 1.02
Window shortfall
0 m³
Window surplus
0 m³
Complete operating comparison
Supported points and operating-window outcomes
ScenarioFlow (m³/h)Head (m)Input kWTarget hTarget kWhTarget costWindow volume (m³)Window kWhOutcome
100% speed20151.21069867.264185USD 1.821609.68558Fits window
75% speed158.43750.51076384.086104USD 1.021204.086104Fits window
50% speed103.750.151337121.816046USD 0.45801.210698Exceeds window
125% speed2523.43752.3646444.811.350289USD 2.8420018.917149Fits window
Every plotted sample for 75% speed
Selected pump curve data
Flow (m³/h)Head (m)Pump efficiency (%)Point kind
016.8750Entered knot
0.62516.6406255Interpolated sample
1.2516.4062510Interpolated sample
1.87516.17187515Interpolated sample
2.515.937520Interpolated sample
3.12515.70312525Interpolated sample
3.7515.4687530Interpolated sample
4.37515.23437535Interpolated sample
51540Interpolated sample
5.62514.76562545Interpolated sample
6.2514.5312550Interpolated sample
6.87514.29687555Interpolated sample
7.514.062560Entered knot
8.12513.5937561.25Interpolated sample
8.7513.12562.5Interpolated sample
9.37512.6562563.75Interpolated sample
1012.187565Interpolated sample
10.62511.7187566.25Interpolated sample
11.2511.2567.5Interpolated sample
11.87510.7812568.75Interpolated sample
12.510.312570Interpolated sample
13.1259.8437571.25Interpolated sample
13.759.37572.5Interpolated sample
14.3758.9062573.75Interpolated sample
158.437575Operating point
15.6257.9687573.75Interpolated sample
16.257.572.5Interpolated sample
16.8757.0312571.25Interpolated sample
17.56.562570Interpolated sample
18.1256.0937568.75Interpolated sample
18.755.62567.5Interpolated sample
19.3755.1562566.25Interpolated sample
204.687565Interpolated sample
20.6254.2187563.75Interpolated sample
21.253.7562.5Interpolated sample
21.8753.2812561.25Interpolated sample
22.52.812560Entered knot
System curve sample data
Plotted system head data
Flow (m³/h)Head (m)
00
0.4592790.00791
0.9185590.031641
1.3778380.071191
1.8371170.126563
2.2963970.197754
2.7556760.284766
3.2149550.387598
3.6742350.50625
4.1335140.640723
4.5927930.791016
5.0520730.957129
5.5113521.139063
5.9706311.336816
6.4299111.550391
6.889191.779785
7.3484692.025
7.8077492.286035
8.2670282.562891
8.7263072.855566
9.1855873.164063
9.6448663.488379
103.75
10.1041453.828516
10.5634254.184473
11.0227044.55625
11.4819834.943848
11.9412625.347266
12.4005425.766504
12.8598216.201563
13.31916.652441
13.778387.119141
14.2376597.60166
14.6969388.1
158.4375
15.1562188.61416
15.6154979.144141
16.0747769.689941
16.53405610.251563
16.99333510.829004
17.45261411.422266
17.91189412.031348
18.37117312.65625
18.83045213.296973
19.28973213.953516
19.74901114.625879
2015
20.2082915.314063
20.6675716.018066
21.12684916.737891
21.58612817.473535
22.04540818.225
22.50468718.992285
22.96396619.775391
23.42324620.574316
23.88252521.389062
24.34180422.219629
24.80108423.066016
2523.4375
25.26036323.928223
25.71964224.80625
26.17892225.700098
26.63820126.609766
27.0974827.535254
27.5567628.476563
28.01603929.433691
28.47531830.406641
28.93459831.39541
29.39387732.4
29.85315633.42041
30.31243634.456641
30.77171535.508691
31.23099436.576563
31.69027437.660254
32.14955338.759766
32.60883239.875098
33.06811241.00625
33.52739142.153223
33.9866743.316016
34.4459544.494629
34.90522945.689063
35.36450846.899316
35.82378748.125391
36.28306749.367285
36.74234650.625

Your system and operating target

Enter SI quantities. The results display selector converts output only. Static head includes elevation or pressure head; the quadratic loss curve is calibrated by your loss at one reference flow.

Three uppercase letters; label only.

100–2000 kg/m³. Density changes power, not these entered head curves.

0–10000 m; no active control valves.

Positive flow used to calibrate system loss.

Loss only, excluding static head; 0–10000 m.

Your target, not a recommended pool turnover requirement.

0–24 hours. Longer required runtime is shown as unmet.

0–100 per kWh; excludes fixed charges.

Pump curves and speed scenarios

Use the base-speed curve for each scenario. Enter strictly increasing flow and strictly decreasing positive head. Efficiency is interpolated at the corresponding base flow and assumed unchanged with speed. Speed scaling does not establish an equipment rating.

1. 100% speed · 100% speed

1–60 characters.

10–150%; hypothetical scaling only.

1–100%; constant for this scenario.

Base-curve point 1

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 2

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 3

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 4

Positive at positive flow; zero is allowed only at zero flow.

2. 75% speed · 75% speed

1–60 characters.

10–150%; hypothetical scaling only.

1–100%; constant for this scenario.

Base-curve point 1

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 2

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 3

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 4

Positive at positive flow; zero is allowed only at zero flow.

3. 50% speed · 50% speed

1–60 characters.

10–150%; hypothetical scaling only.

1–100%; constant for this scenario.

Base-curve point 1

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 2

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 3

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 4

Positive at positive flow; zero is allowed only at zero flow.

4. 125% speed · 125% speed

1–60 characters.

10–150%; hypothetical scaling only.

1–100%; constant for this scenario.

Base-curve point 1

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 2

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 3

Positive at positive flow; zero is allowed only at zero flow.

Base-curve point 4

Positive at positive flow; zero is allowed only at zero flow.

Up to four scenarios and twelve points per curve. A supported intersection is not a manufacturer-approved operating region. NPSH, suction hazards, equipment minimum flows, viscosity and water quality require separate assessment.

How to use this calculator

  1. Load Low-static-head example or Raised-static-head example to compare a complete fictional four-speed plan. Enter your fluid density and currency label; the label does not convert currencies.
  2. Enter static head, a positive reference flow and loss head at that flow. Keep static lift separate from friction loss. Use your actual passive-system data rather than a pump’s maximum advertised flow.
  3. Set your target daily volume, available hours and electricity price. A pool-volume target is your assumption, not a recommended turnover or filtration requirement.
  4. Expand a pump scenario and enter its base-speed curve in m³/h and metres, with pump efficiency at each point. Keep flows increasing and heads decreasing. Enter speed percent and constant motor-drive efficiency; copy or add scenarios for comparison.
  5. Inspect supported intersections, required runtime, energy and window shortfalls. Use the metric/US results selector, choose a scenario and inspect curve samples or the equivalent tables. A curve sample is not a system duty point unless marked as the operating point.
  6. Download the complete CSV or copy the selectable text. Check manufacturer operating limits, NPSH, equipment minimum flows, suction safety and water-quality requirements separately before making an installation or operating decision.

The Formula

The mathematical logic powering this calculation is:

Use flow Q in m³/h and head H in metres. For speed ratio r = entered speed percent/100, scale the base curve with Q = r × q and H = r² × h(q). Head and pump efficiency are linearly interpolated between the supplied base-flow points. Pump efficiency at the corresponding base flow is assumed unchanged with speed; motor plus drive efficiency is the entered constant. These are explicit approximations, not a measured performance guarantee.
The passive system curve is Hsystem(Q) = static head + loss at reference flow × (Q/reference flow)². Static head includes the entered elevation or pressure head; the loss term excludes it. This calibrated quadratic curve is not a pipe-network solver and does not model active flow-control valves.
A supported operating point is the unique intersection between a strictly decreasing pump curve and the nondecreasing system curve. Locate the intersection within a supplied segment before solving. Write its scaled head line H = intercept − BQ and k = loss/referenceFlow². Then kQ² + BQ − C = 0, where C = intercept − static head. Use the stable positive root Q = 2C/(B + sqrt(B²+4kC)), or Q=C/B when k=0. Exact endpoint checks prevent extrapolation; exact internal knots belong to the preceding segment. Canonical line coefficients make redundant collinear points invariant.
If the pump is below the system at the first positive supplied flow, report below-curve-range. If the first flow is zero and its head is at or below static head, report no positive flow. If the pump remains above the system at the final supplied flow, report above-curve-range. These states have no invented duty, power or runtime. A zero-flow root is not a usable operating point, and power at shutoff is not estimated as zero.
Hydraulic power kW = density × 9.80665 × (Q/3600) × H / 1000. Shaft kW = hydraulic kW / (pump efficiency percent/100). Electrical input kW = shaft kW / (motor-drive efficiency percent/100). Specific electrical energy = electrical kW/Q in kWh/m³.
Target runtime = entered target volume/Q. Target energy = runtime × electrical kW; target energy cost = energy × entered electricity price. Available-window volume = Q × available hours; window energy = electrical kW × available hours. Shortfall = max(0,target−window volume), surplus = max(0,window volume−target). Target energy is a hypothetical longer-run requirement when the target does not fit the window. Zero target needs zero time and energy.
Compare only supported scenarios that meet the available window when identifying lowest modeled target energy. Tie order is target energy, runtime, then scenario identifier. This compares entered assumptions, not reliability, capital cost or equipment safety. No eligible scenario means no winner.
Input numbers are unsigned decimal text with at most six decimal places and twelve significant digits. Density 100–2000 kg/m³; static/loss head 0–10000 m; reference flow 0.000001–100000 m³/h; target 0–100000000 m³; available hours 0–24; electricity price 0–100 per kWh. Use 1–4 scenarios, speed 10–150%, motor-drive efficiency 1–100%, and 2–12 points per curve. Point flow 0–100000 m³/h must strictly increase; positive head 0.000001–10000 m must strictly decrease. Pump efficiency 0–100%, but at positive flow it must be at least 0.000001%. Blank, signed, exponent and fractional tokens are invalid. Bounds are numerical limits, not equipment operating permissions.
The model uses exact decimal endpoint and feasibility checks, exact rational arithmetic and an 80-decimal square-root approximation for non-square roots. Numeric outputs are converted for display/export only after solving; unresolved residuals produce an explicit numerical-resolution state. Chart samples do not determine the solution. All pump samples stay within supplied domains; the system curve may end at the displayed head ceiling, with this clipping disclosed. CSV retains input strings and round-trip numeric outputs, not internal 80-digit fractions.
Inputs stay in SI units. Results can display US gallons/minute, feet and US gallons using 1 US gal = 0.003785411784 m³ and 1 ft = 0.3048 m. Changing display units does not change the physical assumptions. Excludes viscosity correction, cavitation/NPSH, suction hazards, minimum equipment flows, manufacturer operating regions, parallel/series pumps, impeller trimming, active valves, transients, sanitation and compliance.

Worked Example

If you input:

  • System: Static head 0 m; loss 15 m at 20 m³/h; density 1000 kg/m³.
  • Target: 120 m³ within 8 h/day; electricity USD 0.25/kWh.
  • BaseCurve: Flow 0, 10, 20, 30 m³/h; head 30, 25, 15, 5 m; pump efficiency 0, 60, 75, 60%.
  • Scenarios: 100%, 75%, 50% and 125% of base speed; motor-drive efficiency 90% each.

Result:

At 100%, 75%, 50% and 125% speed, the supported flows are 20, 15, 10 and 25 m³/h. Required runtimes are 6, 8, 12 and 4.8 h for 120 m³. The 75% scenario meets the 8 h window exactly: head 8.4375 m, electrical input 0.5107630208 kW, target energy 4.0861041667 kWh and target cost USD 1.02. The 100% scenario needs 7.2641851852 kWh and costs USD 1.82. The 50% scenario uses 1.8160462963 kWh over 12 h but moves only 80 m³ in the available 8 h, leaving 40 m³ short; it is not eligible as the lowest-energy feasible scenario. Raising only static head to 8 m reduces 100% flow to 16.629606739 m³/h and makes it the lowest eligible target-energy scenario; 75% misses the window and 50% cannot overcome the lift. These are illustrative constant-system comparisons, not equipment ratings.

Frequently Asked Questions

Why is a pump’s maximum flow insufficient for sizing?

The actual flow depends on where the pump head curve meets the system head curve. A maximum-flow figure at low head does not establish delivery against elevation or friction. Enter a suitable curve and system assumptions; the intersection alone still does not establish equipment suitability.

Does reducing speed always save enough energy while meeting the target?

A lower speed can reduce electrical input but also reduce delivered flow or fail to overcome static lift. The target may then require too many hours. This planner separates target energy from what fits in the available operating window and excludes unmet scenarios from its lowest-energy comparison.

Why can the curve end without an operating point?

The entered data may not cover the intersection. If the system lies below the pump at the last supplied flow, the solution would be beyond that range; if it lies above the first positive-flow point, the solution would be below the range. The planner reports the missing coverage instead of extending a curve without evidence.

How reliable are speed affinity and efficiency assumptions?

Affinity scaling is an approximation that assumes comparable hydraulic behavior. This planner keeps pump efficiency unchanged at corresponding base-flow points and uses constant motor-drive efficiency. Real viscosity, cavitation, motor losses and operating limits can change the result. Prefer measured curves at the intended speed when available.

Is hydraulic power the electricity the pump consumes?

No. Hydraulic power is imparted to the fluid. Shaft power accounts for pump efficiency, and electrical input additionally accounts for motor and drive efficiency. The energy and cost comparisons use electrical input, not hydraulic power.

Does the target volume establish pool filtration or water safety?

No. It is an entered throughput target. The model does not assess water quality, pool turnover requirements, suction or entrapment hazards, equipment minimum flow, local rules or manufacturer-approved operating regions. Those require separate assessment.

Can I use US units?

Results and plots can display US gallons per minute, feet and US gallons. Entered curve and system inputs remain in SI units, as labeled. Switching the results display does not change the inputs or the solved physical quantities; CSV includes canonical and displayed chart values with units.

What do the chart samples and CSV contain?

The chart includes supplied knots, interpolated samples and the actual solved points. Pump curves stay inside their supplied domains. The system plot can be clipped at the displayed head ceiling, which is disclosed. Tables expose plotted values and CSV includes every assumption, result and sample; plotted sampling does not drive the operating-point solver.

Similar Calculators