Heat Sink Thermal Resistance & Junction Temperature Calculator
Compare two cooling setups for one electronic component with a dominant case-to-heat-sink path. Use resistance data matched to the real airflow and mounting, or estimate effective sink resistance from steady measurements. Trace the temperature rises from nearby air to the sink, case and junction. See how much resistance the case and interface leave for the sink, and where each setup reaches your chosen junction temperature.
Compare heat sinks and junction temperatures
Compare two cooling paths, check the power each can dissipate at your target, and see which part of the setup drives the temperature rise.
Device and operating conditions
Use the heat the device dissipates and the local air near the heat sink. This estimate assumes a dominant, steady heat path through the package case and sink.
Heat sink and interface inputs
Compare ratings or measurements that reflect the mounting and airflow of each setup.
Setup B is 121 °C hotter at the entered power.
Junction target 120 °C.
- Power at target
- 79.1667 W
- Sink resistance budget
- 8.6 °C/W maximum at the entered power
- Power at target
- 7.1429 W
- Sink resistance budget
- 8.2 °C/W maximum at the entered power
Junction temperature by dissipated power
Each line holds resistance and local air temperature constant. Squares mark entered watts, and circles mark the target crossings within this range.
- Setup A
- Setup B
- Junction target
Temperature rise across the cooling path
Identify which stage uses the most temperature headroom at your entered power.
Setup A12 °C rise
- Sink to air
- 3 °C
- Case to sink
- 1 °C
- Junction to case
- 8 °C
Setup B133 °C rise
- Sink to air
- 120 °C
- Case to sink
- 5 °C
- Junction to case
- 8 °C
Open thermal path ledger
| Quantity | Setup A | Setup B |
|---|---|---|
| Sink resistance basis | Specified | Specified |
| Sink to air | 0.3 °C/W | 12 °C/W |
| Case to sink | 0.1 °C/W | 0.5 °C/W |
| Junction to case | 0.8 °C/W | 0.8 °C/W |
| Total resistance | 1.2 °C/W | 13.3 °C/W |
| Sink base | 28 °C | 145 °C |
| Device case | 29 °C | 150 °C |
| Device junction | 37 °C | 158 °C |
| Power at target | 79.1667 W | 7.1429 W |
Show copyable CSV
How to use this calculator
- Enter local air temperature at the sink, the heat dissipated by the device and a chosen junction target.
- Enter the junction-to-case resistance for the package surface used and the two case-to-sink interface resistances.
- For each setup, enter the sink-to-air resistance under matching cooling conditions or use settled sink-base, air and power measurements.
- Compare junction temperatures and remaining target allowances. Change the plot maximum to inspect the expected operating power range.
- Open the calculation ledger or export the inputs, temperature stages and modeled crossing values.
The Formula
The mathematical logic powering this calculation is:
For a dominant steady heat path through the mounted sink, total thermal resistance = junction-to-case + case-to-sink + sink-to-air. Each temperature rise is dissipated power × that segment’s resistance. Add them to the local inlet air temperature to estimate junction temperature. The same watts flow through the three series segments in this model.
Enter heat sink resistance explicitly from matching conditions, or infer the effective value from (measured sink-base temperature − nearby air temperature) ÷ measured dissipation. Use the selected package case surface, mounted interface, sink orientation and nearby inlet air. The chart holds each effective resistance constant over the author’s chosen power range.
At or below the chosen target, available temperature rise = target − inlet air temperature. Maximum modeled dissipated power = available rise ÷ total resistance. At positive entered power, maximum allowed sink resistance = available rise ÷ entered power − junction-to-case − case-to-sink. The worksheet distinguishes air already above target, zero entered watts and a nonpositive sink allowance.
Accept up to three decimal places. Nearby air and calibration temperatures are −100 to 250 °C, target −100 to 300 °C, dissipated power 0–1,000 W, and measured power and plot maximum 0.001–1,000 W. Junction-to-case resistance 0.001–100 °C/W, case-to-sink 0–100 °C/W, specified sink 0.001–500 °C/W. Measurements must imply positive sink resistance of at most 500 °C/W. Compare using exact input ratios. Figures are rounded for reading. This worksheet supports fixed steady-state resistance with a dominant case path. Other heat paths, airflow changes, transients, multiple heat sources and safe operating area need separate evaluation.Worked Example
If you input:
- Ambient: 25 °C
- Dissipation: 10 W
- Junction-to-case: 0.8 °C/W
- Setup A interface and sink: 0.1 and 0.3 °C/W
- Setup B interface and sink: 0.5 and 12 °C/W
- Entered comparison target: 120 °C
Result:
The published TI/Burr-Brown TO-3 examples give 37 °C junction for Setup A and 158 °C for Setup B at 10 W. Setup A has 83 °C headroom under the separately entered 120 °C target. Setup B is 38 °C above and reaches the target at about 7.1429 W under the worksheet’s fixed-resistance assumptions.
Frequently Asked Questions
What is the difference between dissipated power and electrical input power?
Dissipated power is the heat the selected device releases at the operating point. Some equipment sends part of its input power to the load. Use a relevant device loss estimate or calibrated dissipation measurement.
Where should I obtain the three thermal resistances?
Use the device’s junction-to-case figure for the mounted thermal path, a measured or specified interface resistance for the mounting arrangement, and the sink rating for matching airflow and orientation. Each quantity represents a different section of the same path.
Can I substitute a datasheet junction-to-ambient value?
Junction-to-ambient data typically represent an entire tested assembly, including board and airflow. The series model requires the separate junction-to-case, case-to-sink and sink-to-air values.
Why use nearby air temperature?
Inlet air near the sink can be warmer than room air because of enclosure recirculation or other components. Use representative inlet conditions for the assembly.
How do I interpret a zero or negative sink budget?
At the current power, the junction-to-case and interface resistances already consume the entire allowance. A positive sink resistance can only add temperature rise, so review the other resistances, local air or dissipated power.
When is measured heat sink resistance useful?
It estimates an effective resistance at the settled test conditions. A material, mounting, airflow or power change can alter that resistance. Confirm transferred heat is adequately represented by the dissipated power entered.
Does staying below the worksheet target confirm safe operation?
The worksheet compares a chosen target within its model. Use the device’s operating conditions, limits, safe operating area and measured worst-case performance to assess the actual assembly.
Similar Calculators
Thermal Conductivity Calculator & Wall Heat Flow Planner
Find thermal conductivity from measured slab heat flow. Compare two wood-framed wall assemblies by U-factor, effective R-value, heat flow and layer temperatures.
Thermal Expansion & Clearance Calculator
Calculate linear thermal expansion for an opening and insert. Plot clearance over temperature and find where a limit or zero gap occurs.
Server Power Cost Calculator
Compare server fleets with active, idle and standby schedules, PUE, time-of-use rates and coincident demand. Visualize hourly power, monthly costs and upgrade payback.
Transformer kVA, Load & Loss Calculator
Compare transformer kVA ratings, currents and profile energy losses. Model energized idle versus switched off, inspect load curves and export exact energy and cost ledgers.
Transient Thermal Impedance Calculator
Use Foster thermal coefficients to predict junction temperature on the first pulse, after a finite pulse count and at the repeating-cycle limit.
Thermal Contact Resistance & Conductivity Fit Calculator
Fit steady thermal resistance versus measured thickness. Estimate apparent conductivity and combined contact resistance, then check held-out runs.