Chiller Tonnage & Measured Load Calculator

Enter measured flow and entering and leaving liquid temperatures for one chilled-water loop. Compare peak and duration-weighted cooling, track signed thermal energy, and estimate the flow associated with an entered target at each measured temperature drop. Use reference water properties or enter a documented liquid density and specific heat.

Chilled-water measurements

Compare measured cooling and rated load

Record coincident flow and temperatures. Compare peak and duration-weighted cooling and solve the flow needed at an observed temperature drop.

Peak measured cooling
418.6 kW
Largest positive interval
Average cooling
204.648889 kW
Weighted by recorded duration
Thermal energy
306.973333 kWh
Positive cooling over recorded time
Rating minus peak
31.4 kW
Compared with entered rated load
Edit measurements and limits

Water reference uses 1,000 kg/m³ and 4.186 kJ/(kg·K). You can enter documented liquid properties instead.

Rating, target and flow limits are optional. Match flow and temperature readings from the same loop and interval. Enter decimals or exact fractions.

Peak interval
Part-load interval
Idle interval

Measured load across recorded time

Interval width represents recorded duration. Signed load below zero shows warming across the measured loop.

Cooling Reverse Rated 450 kW
  1. Peak interval

    20 min · Measured cooling

    418.6 kW
  2. Part-load interval

    40 min · Measured cooling

    251.16 kW
  3. Idle interval

    30 min · No observed flow

    0 kW

Flow to meet the target

Peak interval

Measured interval

Entering / leaving
12 °C / 7 °C
Temperature drop
5 °C
Observed flow
1,200 L/min
Measured flow check
Within entered flow limits
Signed thermal load
418.6 kW
Positive cooling energy
139.533333 kWh
Rating minus cooling
31.4 kW

At this interval’s temperature drop

1,290.014333 L/min

Above entered flow ceiling

Entered load target
450 kW
Flow floor
200 L/min
Flow ceiling
1,250 L/min

The inverse holds this interval’s temperature drop and liquid properties fixed. The rated comparison uses your reference capacity at its documented conditions.

Show every interval and assumption
Rated load entered
450 kW
Recorded duration
1.5 h
Liquid density
1,000 kg/m³
Specific heat
4.186 kJ/(kg·K)
Signed thermal energy
306.973333 kWh
  • Peak interval

    Measured flow
    1,200 L/min
    Flow check
    Within entered flow limits
    Signed load
    418.6 kW
    Positive cooling
    418.6 kW
    Signed thermal energy
    139.533333 kWh
    Rating minus cooling
    31.4 kW
    Flow for target
    1,290.014333 L/min
    Target flow check
    Above entered flow ceiling
  • Part-load interval

    Measured flow
    900 L/min
    Flow check
    Within entered flow limits
    Signed load
    251.16 kW
    Positive cooling
    251.16 kW
    Signed thermal energy
    167.44 kWh
    Rating minus cooling
    198.84 kW
    Flow for target
    1,612.517917 L/min
    Target flow check
    Above entered flow ceiling
  • Idle interval

    Measured flow
    0 L/min
    Flow check
    Below entered flow floor
    Signed load
    0 kW
    Positive cooling
    0 kW
    Signed thermal energy
    0 kWh
    Rating minus cooling
    450 kW
    Flow for target
    Unavailable
    Target flow check
    Needs flowing liquid and a positive temperature drop
Download chiller load CSV
Show selectable CSV

How to use this calculator

  1. Open Edit measurements and limits. Choose metric or U.S. customary readings and reference water or entered liquid properties.
  2. Enter coincident flow, entering temperature, leaving temperature and interval duration for the same circuit.
  3. Optionally enter a documented reference rating, a thermal load target and measured-flow bounds.
  4. Use the duration-width timeline, then inspect the inverse flow and arithmetic rating difference for each interval.
  5. Download the exact interval and assumption ledger as CSV.

The Formula

The mathematical logic powering this calculation is:

Record coincident readings on the same liquid circuit and use a duration during which each set reasonably represents conditions. Entering temperature is the return at the chiller and leaving temperature is the supply. Signed temperature drop = entering minus leaving. Mass flow in kg/s = volumetric flow in L/min × density in kg/m³ ÷ 60,000. Signed thermal kW = mass flow × specific heat in kJ/(kg·K) × signed drop in kelvins. At zero observed flow the calculated transfer is zero. A negative result identifies an observed warming direction under the supplied readings.

Positive cooling per interval = max(0, signed load). Multiply each load by its duration in hours for thermal energy. The duration-weighted average divides summed positive cooling energy by total entered hours, including entered idle intervals. The timeline concatenates intervals in entry order and shows only entered duration. Peak cooling is the largest positive estimate, or zero if no interval has a positive load. Net signed energy retains negative transfer. Thermal kW and kWh describe heat transfer from the liquid circuit.

Water mode uses fixed reference density 1,000 kg/m³ and specific heat 4.186 kJ/(kg·K). For glycol or another documented single-phase liquid, enter the applicable density and specific heat for the measured composition and conditions. One property pair applies throughout the worksheet. The familiar U.S. water approximation uses 500 × US gpm × temperature drop in °F ÷ 12,000 for tons. This worksheet computes from mass flow and specific heat in SI, so the result can differ slightly from that shortcut. A U.S. liquid gallon is 3.785411784 L. A refrigeration ton is 12,000 Btu_IT/h, about 3.516853 thermal kW.

For a positive target, a usable interval has positive measured flow and a positive measured drop. Flow in L/min for a target in thermal kW = target × 60,000 ÷ (density × specific heat × observed drop). This computes a fixed-drop comparison. Real temperature drop can change with flow. An entered zero target yields zero required flow. A target left blank stays unavailable. The entered flow limits are inclusive and independently check observed and inverse flow. A rating entered for its own documented conditions gives a signed difference = rated load minus positive measured load. A negative difference marks a measured load above that reference rating. The entered rating and flow limits remain independent comparisons.

Use 1–12 intervals, each over zero and up to 1,440 minutes. Flow accepts 0–1,000,000 L/min equivalent, temperatures −100 to 150 °C equivalent, rated and target load 0–1 billion thermal kW equivalent, density 100–3,000 kg/m³ and specific heat 0.1–10 kJ/(kg·K). These are worksheet entry bounds. Numbers accept up to six decimal places or exact fractions. Rounded display values preserve exact boundary comparisons. The CSV records exact quantities, with a leading apostrophe on signed values or fractions when needed to retain literal text.

This worksheet describes thermal transfer on one measured loop. The heat exchanger LMTD worksheet covers dual-stream balance and heat-transfer coefficient estimates. The chiller rating comparison assumes a user-supplied reference capacity and documents recorded load and the entered limits. Equipment performance at changed conditions depends on its own operating data.

Worked Example

If you input:

  • Peak interval: 20 min at 1,200 L/min, entering 12 °C and leaving 7 °C
  • Part-load interval: 40 min at 900 L/min, entering 11 °C and leaving 7 °C
  • Idle interval: 30 min at zero observed flow
  • Reference and target: 450 kW rating and target, with 1,250 L/min flow ceiling

Result:

Measured peak is 418.6 kW and recorded positive cooling is 306.973333 kWh over 90 minutes. The entered rating is 31.4 kW above the peak. A 450 kW target at the peak interval’s measured temperature drop corresponds to 1,290.014333 L/min, above the entered flow ceiling.

Frequently Asked Questions

How is chiller tonnage calculated from flow and temperature?

Multiply measured liquid mass flow by specific heat and the entering-to-leaving temperature drop. Divide thermal kW by approximately 3.516853 to get refrigeration tons.

Can I calculate tons for a glycol loop?

Yes. Enter documented density in kg/m³ and specific heat in kJ/(kg·K) for your measured condition and liquid composition. Liquid properties stay in those units when you switch flow and temperature units.

Does the average include idle and reverse intervals?

Yes. They contribute their entered duration with zero positive cooling. The separate signed energy retains any heat gain identified by negative load.

How can the target flow exceed my flow limit while peak cooling is below the entered rating?

The inverse uses an observed temperature drop and your entered flow bounds. The separate rating difference uses an entered capacity reference for its documented conditions. The two comparisons answer different questions.

Do I need a chiller rating?

A rating is optional. Enter it to see the difference from measured load. Peak, average and thermal energy remain available from the measurement intervals.

Similar Calculators