Chiller Tonnage & Measured Load Calculator
Enter measured flow and entering and leaving liquid temperatures for one chilled-water loop. Compare peak and duration-weighted cooling, track signed thermal energy, and estimate the flow associated with an entered target at each measured temperature drop. Use reference water properties or enter a documented liquid density and specific heat.
Compare measured cooling and rated load
Record coincident flow and temperatures. Compare peak and duration-weighted cooling and solve the flow needed at an observed temperature drop.
Edit measurements and limits
Water reference uses 1,000 kg/m³ and 4.186 kJ/(kg·K). You can enter documented liquid properties instead.
Rating, target and flow limits are optional. Match flow and temperature readings from the same loop and interval. Enter decimals or exact fractions.
Peak interval
Part-load interval
Idle interval
Measured load across recorded time
Interval width represents recorded duration. Signed load below zero shows warming across the measured loop.
- 418.6 kW
Peak interval
20 min · Measured cooling
- 251.16 kW
Part-load interval
40 min · Measured cooling
- 0 kW
Idle interval
30 min · No observed flow
Flow to meet the target
Peak interval
Measured interval
- Entering / leaving
- 12 °C / 7 °C
- Temperature drop
- 5 °C
- Observed flow
- 1,200 L/min
- Measured flow check
- Within entered flow limits
- Signed thermal load
- 418.6 kW
- Positive cooling energy
- 139.533333 kWh
- Rating minus cooling
- 31.4 kW
At this interval’s temperature drop
1,290.014333 L/min
Above entered flow ceiling
- Entered load target
- 450 kW
- Flow floor
- 200 L/min
- Flow ceiling
- 1,250 L/min
The inverse holds this interval’s temperature drop and liquid properties fixed. The rated comparison uses your reference capacity at its documented conditions.
Show every interval and assumption
- Rated load entered
- 450 kW
- Recorded duration
- 1.5 h
- Liquid density
- 1,000 kg/m³
- Specific heat
- 4.186 kJ/(kg·K)
- Signed thermal energy
- 306.973333 kWh
Peak interval
- Measured flow
- 1,200 L/min
- Flow check
- Within entered flow limits
- Signed load
- 418.6 kW
- Positive cooling
- 418.6 kW
- Signed thermal energy
- 139.533333 kWh
- Rating minus cooling
- 31.4 kW
- Flow for target
- 1,290.014333 L/min
- Target flow check
- Above entered flow ceiling
Part-load interval
- Measured flow
- 900 L/min
- Flow check
- Within entered flow limits
- Signed load
- 251.16 kW
- Positive cooling
- 251.16 kW
- Signed thermal energy
- 167.44 kWh
- Rating minus cooling
- 198.84 kW
- Flow for target
- 1,612.517917 L/min
- Target flow check
- Above entered flow ceiling
Idle interval
- Measured flow
- 0 L/min
- Flow check
- Below entered flow floor
- Signed load
- 0 kW
- Positive cooling
- 0 kW
- Signed thermal energy
- 0 kWh
- Rating minus cooling
- 450 kW
- Flow for target
- Unavailable
- Target flow check
- Needs flowing liquid and a positive temperature drop
Show selectable CSV
How to use this calculator
- Open Edit measurements and limits. Choose metric or U.S. customary readings and reference water or entered liquid properties.
- Enter coincident flow, entering temperature, leaving temperature and interval duration for the same circuit.
- Optionally enter a documented reference rating, a thermal load target and measured-flow bounds.
- Use the duration-width timeline, then inspect the inverse flow and arithmetic rating difference for each interval.
- Download the exact interval and assumption ledger as CSV.
The Formula
The mathematical logic powering this calculation is:
Record coincident readings on the same liquid circuit and use a duration during which each set reasonably represents conditions. Entering temperature is the return at the chiller and leaving temperature is the supply. Signed temperature drop = entering minus leaving. Mass flow in kg/s = volumetric flow in L/min × density in kg/m³ ÷ 60,000. Signed thermal kW = mass flow × specific heat in kJ/(kg·K) × signed drop in kelvins. At zero observed flow the calculated transfer is zero. A negative result identifies an observed warming direction under the supplied readings.
Positive cooling per interval = max(0, signed load). Multiply each load by its duration in hours for thermal energy. The duration-weighted average divides summed positive cooling energy by total entered hours, including entered idle intervals. The timeline concatenates intervals in entry order and shows only entered duration. Peak cooling is the largest positive estimate, or zero if no interval has a positive load. Net signed energy retains negative transfer. Thermal kW and kWh describe heat transfer from the liquid circuit.
Water mode uses fixed reference density 1,000 kg/m³ and specific heat 4.186 kJ/(kg·K). For glycol or another documented single-phase liquid, enter the applicable density and specific heat for the measured composition and conditions. One property pair applies throughout the worksheet. The familiar U.S. water approximation uses 500 × US gpm × temperature drop in °F ÷ 12,000 for tons. This worksheet computes from mass flow and specific heat in SI, so the result can differ slightly from that shortcut. A U.S. liquid gallon is 3.785411784 L. A refrigeration ton is 12,000 Btu_IT/h, about 3.516853 thermal kW.
For a positive target, a usable interval has positive measured flow and a positive measured drop. Flow in L/min for a target in thermal kW = target × 60,000 ÷ (density × specific heat × observed drop). This computes a fixed-drop comparison. Real temperature drop can change with flow. An entered zero target yields zero required flow. A target left blank stays unavailable. The entered flow limits are inclusive and independently check observed and inverse flow. A rating entered for its own documented conditions gives a signed difference = rated load minus positive measured load. A negative difference marks a measured load above that reference rating. The entered rating and flow limits remain independent comparisons.
Use 1–12 intervals, each over zero and up to 1,440 minutes. Flow accepts 0–1,000,000 L/min equivalent, temperatures −100 to 150 °C equivalent, rated and target load 0–1 billion thermal kW equivalent, density 100–3,000 kg/m³ and specific heat 0.1–10 kJ/(kg·K). These are worksheet entry bounds. Numbers accept up to six decimal places or exact fractions. Rounded display values preserve exact boundary comparisons. The CSV records exact quantities, with a leading apostrophe on signed values or fractions when needed to retain literal text.
This worksheet describes thermal transfer on one measured loop. The heat exchanger LMTD worksheet covers dual-stream balance and heat-transfer coefficient estimates. The chiller rating comparison assumes a user-supplied reference capacity and documents recorded load and the entered limits. Equipment performance at changed conditions depends on its own operating data.Worked Example
If you input:
- Peak interval: 20 min at 1,200 L/min, entering 12 °C and leaving 7 °C
- Part-load interval: 40 min at 900 L/min, entering 11 °C and leaving 7 °C
- Idle interval: 30 min at zero observed flow
- Reference and target: 450 kW rating and target, with 1,250 L/min flow ceiling
Result:
Measured peak is 418.6 kW and recorded positive cooling is 306.973333 kWh over 90 minutes. The entered rating is 31.4 kW above the peak. A 450 kW target at the peak interval’s measured temperature drop corresponds to 1,290.014333 L/min, above the entered flow ceiling.
Frequently Asked Questions
How is chiller tonnage calculated from flow and temperature?
Multiply measured liquid mass flow by specific heat and the entering-to-leaving temperature drop. Divide thermal kW by approximately 3.516853 to get refrigeration tons.
Can I calculate tons for a glycol loop?
Yes. Enter documented density in kg/m³ and specific heat in kJ/(kg·K) for your measured condition and liquid composition. Liquid properties stay in those units when you switch flow and temperature units.
Does the average include idle and reverse intervals?
Yes. They contribute their entered duration with zero positive cooling. The separate signed energy retains any heat gain identified by negative load.
How can the target flow exceed my flow limit while peak cooling is below the entered rating?
The inverse uses an observed temperature drop and your entered flow bounds. The separate rating difference uses an entered capacity reference for its documented conditions. The two comparisons answer different questions.
Do I need a chiller rating?
A rating is optional. Enter it to see the difference from measured load. Peak, average and thermal energy remain available from the measurement intervals.
Similar Calculators
Heat Exchanger LMTD & Heat Balance Calculator
Compare two exchanger records using signed sensible-heat duties, parallel or counterflow terminal differences and conditional UA at an entered tolerance.
Measured Pump Head Calculator & Tap Audit
Calculate pump head from recorded suction and discharge pressures, pipe sizes, elevations and flow. Compare measured head and entered loss corrections.
Hydronic Radiator Output & Water Temperature Planner
Compare hot-water radiator output by room. Check changing supply and return temperatures, room shortfalls and modeled minimum supply.
Timed Cold Room Pull-Down Calculator
Compare two refrigeration capacities across two timed sensible heat loads. Find heat remaining at the deadline and the minimum modeled cooling capacity.