Energy Efficiency Ratio & Cooling Meter Calculator
Pair delivered cooling with electrical input over the same intervals. Combine the measured energies to calculate one Btu per watt-hour ratio. Add optional measurement bounds and see the maximum electrical input for an efficiency target you supply.
Compare measured cooling efficiency
Combine matched time intervals, compare the measured Btu/Wh, and see electric headroom for a target you enter.
Edit meter readings and target
Use matched average readings and nonoverlapping intervals on the same metering boundary. Uncertainty is an optional absolute offset in the same unit as its reading.
Measured efficiency by interval
Dots mark measured ratios. The spans show uncertainty and arrows show unbounded upper estimates. The dashed line marks your target.
8.45945946 to 10.5151515 Btu/Wh. The target lies within the efficiency range.
10.8571429 to 13.2631579 Btu/Wh. All positive-input estimates meet target.
5.3125 to 6.78571429 Btu/Wh. All positive-input estimates are below target.
Measured set total meter and headroom
Meter boundary · Cooling meter and whole-system electric input
- Measured duration
- 1.5 h
- Measured delivered cooling
- 16,500 Btu
- Delivered cooling range
- 15,650 to 17,350 Btu
- Measured electric input
- 1,750 Wh
- Electric input range
- 1,650 to 1,850 Wh
- Measured efficiency
- 9.42857143 Btu/Wh
- Input budget at measured cooling
- 1,650 Wh
- Measured target headroom
- -100 Wh
- Target headroom range
- -285 to +85 Wh
Show selectable CSV
How to use this calculator
- Select cooling, electric power and time units. Describe which equipment and meters the readings cover.
- Enter average delivered cooling and electric input for each matching time interval. Add a row for another distinct interval.
- Enter optional absolute uncertainties for each measured reading. Leave those fields blank for the entered fixed value.
- Set an optional measured-efficiency target. Inspect the range, cooling and electric energy shares, and the input ceiling at the observed cooling.
- Export the exact meter readings, interval totals and target headroom.
The Formula
The mathematical logic powering this calculation is:
For each measured interval, use matched average delivered cooling Q in Btu/h, electrical input P in watts and duration t in hours. Cooling removed = Q × t Btu and electric input = P × t Wh. Combine the intervals as Σ(Q × t) / Σ(P × t). Each interval contributes its measured energy. When every interval has positive input, this equals an electric-energy-weighted average of the interval ratios. The total includes the cooling from any entered zero-input intervals.
Optional uncertainty values are absolute offsets on the entered mean readings. For independent cooling and electrical ranges, the lower possible ratio is lower cooling divided by upper electric input. Upper possible ratio is upper cooling divided by lower positive electric input. If power can approach zero from above and cooling can be positive, the upper ratio has no finite bound. At exactly zero electric input the ratio is undefined, even when cooling is also zero.
For a positive entered target T in Btu/Wh, the nominal permissible electrical rate is Q/T watts. For the full measured set the permissible energy is total cooling/T watt-hours. Headroom is the permissible input minus the entered input, with negative values representing a shortfall. Independent measurement endpoints produce the corresponding low and high headroom. Exact equality meets the entered target.
Use 1–6 intervals, compatible meter boundaries, and nonoverlapping time ranges within the measurement set. Inputs accept up to 1 billion in each chosen unit and 12 fractional digits. Duration and a supplied target must be positive. Cooling and electric input may be zero. One refrigeration ton equals 12,000 Btu/h. Exact results use rational arithmetic, while displayed values and chart positions are rounded.
The calculation uses the entered observations and their supplied uncertainty. Use consistent metering boundaries for cooling and electricity, including applicable fans, pumps or auxiliaries. Label the boundary in the worksheet. EER2, SEER and IEER describe specific rating conditions or protocols. This worksheet reports measured Btu/Wh for the entered operating intervals.Worked Example
If you input:
- Steady morning: 60 min, 12,000 ± 600 Btu/h, 1,000 ± 50 W
- Afternoon pull-down: 30 min, 9,000 ± 500 Btu/h, 1,500 ± 100 W
- Efficiency target: 10 Btu/Wh
Result:
The total is 16,500 Btu of cooling and 1,750 Wh electric input. Measured efficiency is about 9.42857143 Btu/Wh, with a range of about 8.45945946 to 10.5151515 Btu/Wh. At 10 Btu/Wh and the measured cooling, the electric input budget is 1,650 Wh, so the nominal headroom is −100 Wh.
Frequently Asked Questions
How do I calculate energy efficiency ratio from measured power?
Divide average delivered cooling in Btu/h by average electrical input in watts sampled over the same interval. If you combine several intervals, divide their summed cooling energy by their summed electrical energy.
Why does the total differ from the average of the individual ratios?
The combined result weights each input interval by its measured electric energy. Two intervals with equal duration can still contribute different weights if their power draws differ.
What if cooling is measured when the electric meter shows zero?
That interval has no defined Btu/Wh ratio. Its known cooling and zero electrical input remain in the combined energy ledger. Use explicit zeros only for actual zero measurements on your chosen boundary.
Can a measurement range have no finite upper ratio?
Yes. If the electrical range includes arbitrarily small positive input and the cooling range includes positive cooling, their ratio has no finite upper bound. The zero input endpoint itself has no defined ratio.
What does negative target headroom tell me?
It is the gap between the electric input allowed at your authored target and the entered input. For example, −100 Wh means the entered meter input exceeds the calculated budget by 100 Wh at the measured amount of cooling.
Is this result a SEER2 or EER2 rating?
The worksheet reports the ratio for your matched measured intervals. Rated EER2, SEER2 and other metrics use specified testing conditions, boundaries and weighting.
Similar Calculators
Air Conditioner Electricity Cost & Duty Cycle Calculator
Compare two air conditioner schedules using measured watts and time-of-use prices. See daily kWh, billing cost and the compressor duty that fits a cost cap.
Chiller Tonnage & Measured Load Calculator
Find chiller tons and thermal kW from matched flow and temperature readings. Compare timed intervals, entered capacity and flow for a target load.
HVAC Replacement & Operating Cost Planner
Compare HVAC replacement quotes, annual heating and cooling costs, maintenance and dated repairs. Visualize nominal and discounted costs, savings and payback reversals.
SEER Efficiency & Seasonal Cooling Cost Calculator
Compare two cooling options across measured or modeled bins. See seasonal electricity, rate-weighted cost, and the efficiency a selected bin needs to match the other option.