SEER Efficiency & Seasonal Cooling Cost Calculator
Enter one to six cooling bins with delivered load, a tariff, and the applicable efficiency for each option. Compare both on the same loads, see which bins drive electricity and cost, and solve the minimum ratio for a chosen bin while keeping other inputs fixed.
Compare seasonal cooling efficiency and electricity cost
Compare both options on the same delivered cooling, then find what one operating condition would need to change.
Add each bin in sequence. The dashed vertical line marks the bin selected below.
- Option A $960.00
- Option B $800.00
Bin 2 has 20 million Btu of entered cooling at 0.4 USD/kWh.
Minimum A ratio to match or improve on B’s modeled cost
12.5 Btu/Wh
A currently uses 10 Btu/Wh in this bin. Other bins and the selected auxiliary term stay fixed.
Option A in this bin
2,000 kWh · $800.00
Option B in this bin
1,000 kWh · $400.00
Review cooling bins and exact CSV
| Bin | Cooling | A electricity and cost | B electricity and cost |
|---|---|---|---|
| Bin 1 | 40 million Btu | 1,600 kWh · $160.00 | 4,000 kWh · $400.00 |
| Bin 2 | 20 million Btu | 2,000 kWh · $800.00 | 1,000 kWh · $400.00 |
How to use this calculator
- Divide the cooling period into bins with similar operating conditions and electricity prices. Enter the delivered cooling estimate in each.
- Copy the applicable Btu/Wh assumptions for both options. Enter separately metered or estimated auxiliary electricity only if those amounts are outside the supplied ratios.
- Compare energy and cost by bin. Select a bin to see the ratio Option A would need there to match B's total.
- Review the cost and efficiency ledger, then download exact values if using the model in another worksheet.
The Formula
The mathematical logic powering this calculation is:
For each bin, both options serve the same entered million Btu of delivered cooling. Dividing Btu by Btu/Wh gives watt-hours. Converting watt-hours to kWh makes the factor 1,000 for each million Btu. Bin electricity in kWh equals delivered million Btu × 1,000 divided by its entered Btu/Wh ratio, plus any separately estimated auxiliary electricity. Include auxiliary kWh only when the ratio you enter excludes those loads.
Multiply each bin’s electricity by its own marginal cost per kWh, then sum all bin costs and electricity. The modeled seasonal Btu/Wh ratio equals total delivered cooling times 1,000 divided by total electricity. It is a ratio of totals using your scenario. Official SEER and SEER2 use specified rating procedures. This worksheet does not convert between those ratings or certify equipment performance.
When inspecting one bin, keep Option A's other bins and the selected bin's auxiliary electricity fixed. Subtract that retained share from Option B's total electricity or cost. A positive amount left in the target provides the denominator for the required ratio. Divide the selected bin's cooling numerator by it, multiplying by that bin's price for the cost case. If cooling at that tariff contributes zero to the metric, either every positive ratio meets the target or none does, according to the retained total. A positive contribution with zero or negative headroom has no finite qualifying ratio.
Enter one to six bins, up to 100,000 million Btu in each, source ratios 0.001–100 Btu/Wh, separate auxiliary electricity through 10,000,000 kWh and prices through $1,000/kWh. Inputs support up to three decimal places. Costs model only the entered energy charges, without fixed fees, demand charges or equipment costs. Values are compared before any presentation rounding.Worked Example
If you input:
- Cooler bin: 40 million Btu, $0.10/kWh, A 25 and B 10 Btu/Wh
- Pricier bin: 20 million Btu, $0.40/kWh, A 10 and B 20 Btu/Wh
- Auxiliaries: 0 separately entered kWh for each option
Result:
Option A uses 3,600 kWh for $960 and B uses 5,000 kWh for $800. Increasing A’s ratio to 12.5 Btu/Wh in the second bin ties the modeled cost.
Frequently Asked Questions
Why can the lower electricity option cost more?
An option can use more electricity in your higher-priced bins even if it uses fewer kWh across the full period.
Is the modeled ratio the same as a SEER2 label?
The modeled ratio comes from your bins and auxiliary terms. A labeled SEER2 result uses the applicable equipment test procedure and conditions.
Why does the seasonal ratio differ from the average entered ratios?
Dividing total load by total electricity weights the conditions through their cooling and usage. A simple arithmetic average ignores those amounts.
Why might there be no break-even ratio in a bin?
The fixed portions of A may already consume the entire electricity or cost target, leaving no room for the selected bin's positive energy contribution.
Can I add costs other than energy charges?
This worksheet treats each price as a cost per kWh and models no fixed, installation, financing or demand charges.
Similar Calculators
Energy Efficiency Ratio & Cooling Meter Calculator
Calculate measured cooling efficiency in Btu/Wh across matched meter intervals. Compare uncertainty, electricity use and headroom to your own EER target.
HVAC Replacement & Operating Cost Planner
Compare HVAC replacement quotes, annual heating and cooling costs, maintenance and dated repairs. Visualize nominal and discounted costs, savings and payback reversals.
Electricity Bill & Rate Comparison Calculator
Compare electricity bills with flat, time-of-use or tiered rates. Enter usage and fees, then find how much peak electricity you would need to shift to break even.