AC Power & Power Factor Calculator
Connect current, power factor and real power with a signed power triangle. Enter one or more compatible sinusoidal loads as current plus power factor, or as active plus signed reactive power. The workspace adds active and reactive components before deriving the combined VA and supply current, so opposing reactive loads are represented correctly. Compare an ideal target power factor without turning the result into equipment-selection advice.
Combine loads on one AC supply
Compare real, reactive and apparent power, then see an ideal power-factor adjustment without confusing VA with watts.
Try an example
One common supply
All rows share this voltage, phase configuration and frequency. Each row represents a load across the single-phase supply. Use sinusoidal steady-state RMS values.
Your loads
Changing a row’s mode preserves its other entries. Only the currently selected quantities are used.
Ideal target comparison
The comparison reduces net |Q| only. A lower target never worsens a load that already meets it.
This is an ideal power comparison, not capacitor selection or installation advice.
Display only; input quantities and SI export values stay unchanged.
Combined apparent power
1,200 VA
10 A at 120 V · PF 0.8 lagging
Derived from the vector sum of active and reactive power across 1 load.
Active power P
960 W
Real power consumed
Signed reactive power Q
720 var
Positive: lagging
Before and after the ideal adjustment
Ideal compensation reduces the magnitude of net reactive power while keeping active power and the leading/lagging direction unchanged (unity has zero reactive power).
Signed reactive power to add
-404.463259 var
Ideal capacitive contribution
After: supply current
8.421053 A
1.578947 A reduction
After: power factor
0.95 lagging
Active power stays 960 W
Combined apparent power 1,200 VA. Current 10 amperes. Power factor 0.8, lagging.
The signed power triangle
Signed Q (var): + lagging / − leading
Both axes use the same scale. The diagonal is S = √(P² + Q²). Leading Q points down; lagging Q points up. A very small component may appear flat at this scale; its nonzero value remains in the table.
Each load and the combined supply
The individual VA magnitudes add to 1,200 VA; the combined load is 1,200 VA. Different reactive directions can cancel. The target row adds only ideal reactive power; it does not change the original loads.
| Load | P (W) | Q (var) | S (VA) | Current (A) | PF magnitude | Direction |
|---|---|---|---|---|---|---|
| Load 1 | 960 | 720 | 1,200 | 10 | 0.8 | lagging |
| Combined | 960 | 720 | 1,200 | 10 | 0.8 | lagging |
| After ideal adjustment | 960 | 315.536741 | 1,010.526316 | 8.421053 | 0.95 | lagging |
Method, conventions and supported limits
For a sinusoidal single-phase load, S = VI. For each balanced three-phase load, S = √3 Vline-to-lineIline. P = S × PF and Q = ±S√(1 − PF²). The combined supply uses P = ΣP, Q = ΣQ, S = √(P² + Q²), PF = P/S and I = S/V (or S/(√3V)). PF is a magnitude; reactive direction is stated separately.
For a higher target PF, Qtarget keeps the existing sign and has magnitude P√(1 − PFtarget²)/PFtarget. The signed adjustment is Qtarget − Q. Active power remains unchanged. Zero active power cannot produce a defined positive target PF by reactive cancellation alone.
Accepted inputs: 1–12 compatible loads; voltage 0.001–1,000,000 V; current 0–1,000,000 A; entered P 0–1,000,000,000 W and Q −1,000,000,000 to +1,000,000,000 var. These quantities accept at most six decimal places. PF accepts 0–1 with up to twelve decimal places; a target must be greater than zero. Derived totals may exceed individual input bounds. Calculations retain model precision; displayed values are rounded and very small nonzero values use scientific notation.
This model excludes harmonics, unbalanced or mixed supplies, active generation, inrush, distribution losses and transient behavior. It does not select capacitors, cables, protection or other equipment. Actual distorted-waveform power factor is not fully described by this sinusoidal triangle.
Primary methods: Schneider Electric: reactive power and single-/three-phase equations; why individual VA ratings do not generally add; power quantities and differing PF sign conventions.
How to use this calculator
- Choose single phase or balanced three phase and enter RMS voltage. For three phase, use line-to-line voltage; every row then represents a balanced load with total three-phase P and Q.
- For each load, choose the quantities you know. Enter RMS current and PF from 0 to 1 with leading or lagging direction, or enter nonnegative active power in watts and signed reactive power in vars.
- Add up to 12 compatible loads on the same supply. Positive Q is lagging; negative Q is leading. Do not combine different supplies or enter active generation as a negative load.
- Read combined active, reactive and apparent power, current and PF. Inspect the signed triangle and ledger to see how reactive components cancel rather than adding individual VA ratings.
- Optionally enter a target PF above zero and up to 1. The comparison reduces net reactive magnitude only; a target already met makes no change, and a zero-active-power case has no defined positive target result.
- Switch result display between base and kilo units without changing inputs. Download or copy full-precision SI CSV data, and verify model assumptions before using the comparison in a wider engineering analysis.
The Formula
The mathematical logic powering this calculation is:
Single phase: S = V(rms) × I(rms). Balanced three phase: S = √3 × V(line-to-line,rms) × I(line,rms).
Per load: P = S × PF; Q = ±S√(1 − PF²), positive for lagging and negative for leading.
Combined load: P = ΣPᵢ; Q = ΣQᵢ; S = √(P² + Q²); PF = P/S. PF is undefined when S = 0.
Current = S/V for single phase, or S/(√3V) for balanced three phase.
For a higher target PF with P > 0: |Qtarget| = P√(1 − targetPF²)/targetPF, keeping the original Q sign; signed ideal adjustment = Qtarget − Q.
Power-factor magnitude is shown separately from reactive direction. All inputs share one sinusoidal supply.Worked Example
If you input:
- Supply configuration: Single phase
- RMS supply voltage (line-to-line for three phase): 120
- Compare a target power factor: Yes
- Target power factor: 0.95
- Load 1: known quantities: current-pf
- Load 1: RMS current: 10
- Load 1: power factor: 0.8
- Load 1: reactive direction: lagging
Result:
A single-phase 120 V, 10 A load at 0.8 lagging PF has 1,200 VA apparent power, 960 W active power and +720 var reactive power. An ideal target PF of 0.95 keeps active power at 960 W, lowers reactive power to about +315.536741 var and requires a −404.463259 var adjustment. The resulting apparent power is about 1,010.526316 VA and supply current is 8.421053 A, a reduction of 1.578947 A.
Frequently Asked Questions
Why are volt-amps and watts different in AC circuits?
For this sinusoidal model, VA is apparent power S = VI, while watts are active power P = S × PF. At unity PF they are equal. At 0.8 PF, 1,200 VA corresponds to 960 W. The remaining reactive component is measured in vars; it is not found by subtracting watts from VA because P and Q are perpendicular components of the power triangle.
Which voltage and current should I enter for three-phase power?
Enter RMS line-to-line voltage and RMS line current. Each row must be a balanced three-phase load, with P and Q representing totals over all three phases. The model uses S = √3VI. It does not accept phase-to-neutral voltage in that field, individual unbalanced phase loads or loads connected to unrelated supplies.
What do positive and negative reactive power mean here?
For the supported consuming loads, positive Q denotes lagging current and negative Q denotes leading current. Power factor is displayed as a nonnegative magnitude with its direction stated separately. Meter conventions for signed PF vary, so a negative PF reading should not be entered directly; translate it using that meter's documented sign convention.
Why does the combined VA differ from the sum of the load VA values?
Active powers add, and signed reactive powers add. The combined VA is the magnitude of that resulting vector. For example, two 120 V, 10 A loads at 0.8 PF, one leading and one lagging, have a combined 1,920 W and zero net vars. The combined load is therefore 1,920 VA, while the individual VA magnitudes sum to 2,400 VA. Scalar VA addition agrees only when the power vectors have the same direction.
What does the target power-factor comparison calculate?
It keeps active power fixed and reduces the magnitude of net reactive power to achieve the entered PF, while retaining the original leading or lagging direction until unity is reached. A negative ideal adjustment is capacitive and a positive one inductive. If the combined load already meets the target, nothing changes. This is not a capacitor-size, resonance, switching or installation calculation.
Why can power factor or the target result be undefined?
When combined apparent power is zero, P/S has no defined value. This can occur with no load or with equal opposing purely reactive loads. A nonzero purely reactive load has PF = 0. Cancelling its Q leaves zero apparent power rather than a defined positive PF, so the target comparison is unavailable when active power is zero; its original load results remain valid.
Does this apply to harmonics, unbalanced loads or equipment sizing?
No. The triangle assumes ideal sinusoidal steady-state quantities on one common supply. Harmonics can make true PF differ from displacement PF; unbalance requires phase-specific analysis. Inrush, losses, transients and active generation are excluded. The linked Schneider Electric methods explain the sinusoidal relationships; the workspace does not select cables, protection, capacitors or other equipment.
What units, input precision and numerical limits are supported?
Use 1–12 loads. Voltage accepts 0.001–1,000,000 V; current 0–1,000,000 A; entered active power 0–1,000,000,000 W; entered reactive power ±1,000,000,000 var. Those inputs accept up to six decimal places. PF accepts 0–1 with up to twelve decimal places; a target must be positive. Derived values can exceed input-field bounds. The result-unit switch changes presentation only. CSV uses SI units at model precision; small nonzero results use scientific notation instead of being displayed as exact zero.
Similar Calculators
Transformer kVA, Load & Loss Calculator
Compare transformer kVA ratings, currents and profile energy losses. Model energized idle versus switched off, inspect load curves and export exact energy and cost ledgers.
Power Calculator
Calculate electrical power in watts from voltage and current, or find current from power and voltage.
Ohm's Law Calculator
Calculate voltage, current, or resistance using Ohm's Law — enter any two values to find the third.
DC Voltage Drop & Cable Loss Calculator
Compare DC cable voltage drop, power losses and load limits with separate conductor lengths, connection resistance, constant-power loads and visual sweeps.
Passive Filter Bode Plot & Load Planner
Plot gain and phase for two loaded RC or series RLC filters. Compare cutoff shifts, half-power frequencies and source-referenced gain at your test frequency.
Electrical Load & Phase Balance Planner
Compare three-phase load assignments. Calculate conductor current and fundamental neutral current from a shared set of line-to-neutral loads.