Ventilation Heat Recovery Energy Savings Calculator
Compare equal outdoor airflow with and without a heat recovery ventilator. Enter representative heating conditions, hours, sensible recovery and fan power across three periods. See heating and fan energy separately, find the break-even fan draw in each period, and compare the electricity savings with an entered target.
Compare heat recovery and fan electricity
Compare the same outdoor airflow under three entered conditions.
Modeled savings exactly meet the target.
Heating and fan electricity by period
Period 1 · 10 °C
100 kWh net savings- Baseline200 kWh heating · 50 kWh fan
- Heat recovery60 kWh heating · 90 kWh fan
Break-even recovery fan draw 190 W
Period 2 · 0 °C
85 kWh net savings- Baseline200 kWh heating · 25 kWh fan
- Heat recovery80 kWh heating · 60 kWh fan
Break-even recovery fan draw 290 W
Period 3 · -10 °C
6 kWh net savings- Baseline120 kWh heating · 10 kWh fan
- Heat recovery90 kWh heating · 34 kWh fan
Break-even recovery fan draw 200 W
Review the exact heat recovery ledger
Inspect exact heating and fan totals
- Hours modeled
- 1700 h
- Baseline electricity
- 605 kWh
- Recovery electricity
- 414 kWh
- Target margin
- 0 USD
How to use this calculator
- Set the same outdoor airflow, indoor temperature and heating COP for both systems.
- Enter the baseline total ventilation fan draw, electricity rate and savings target for the modeled period.
- Enter outdoor temperature, duration, effective sensible recovery and recovery ventilation fan draw in each period. Set unused hours to zero.
- Compare energy bars and each period’s fan crossover. Open the exact ledger or export the full worksheet.
The Formula
The mathematical logic powering this calculation is:
Approximate sensible ventilation heat at 1.2 W/(L/s·K) × equal outdoor airflow × max(indoor temperature minus outdoor temperature, 0). Baseline heating electricity draw equals sensible heat divided by the entered heating COP. With heat recovery, reduce heating draw by the entered fraction of sensible recovery. Add the corresponding total fan power. Multiply each rate in watts by period hours and divide by 1,000 for kWh.
The break-even total recovery fan draw in a period is baseline fan watts plus heating watts avoided, for any positive number of hours at those same conditions. A higher fan draw increases electricity use in that period. Multiply the summed electricity difference by the entered flat rate. The savings target is stated over the same entered periods. Equality meets the target. Calculations and CSV use exact fractions for these authored assumptions.
Three periods cover up to 8,784 combined hours. Unused periods can have zero hours. Use measured or documented effective sensible recovery and electrical power under comparable flow and conditions. If a period represents a reduced-recovery mode, enter its effective values from your scenario. This model covers sensible heating and ventilation fans. Moisture, cooling, auxiliary preheat, equipment sizing and ventilation requirements are outside its scope.Worked Example
If you input:
- Conditions: 50 L/s at 20 °C indoors, COP 3, 50 W baseline fan
- Periods: 1,000 h at 10 °C, 500 h at 0 °C, 200 h at −10 °C. Recovery 70%, 60%, 25%. Fans 90 W, 120 W, 170 W.
- Electricity and target: $0.20/kWh and $38.20
Result:
The three periods save 100, 85 and 6 kWh. Savings total 191 kWh, or $38.20. Raising the target by one cent puts it out of reach under the same conditions.
Frequently Asked Questions
When can a ventilator recover heat and still use more electricity?
When the fan electricity added is greater than the heating electricity avoided. Compare the recovery fan watts to the break-even total fan draw for that period.
Why does heating COP matter?
A higher COP delivers the same heat using less electricity. Each unit of recovered heat then avoids less heating electricity, which lowers the fan-power break-even point.
What happens when outdoor air is warmer than indoors?
This worksheet assigns zero sensible heating in that period and compares fan electricity. A cooling analysis requires its own assumptions.
Can I use published recovery efficiency without an adjustment?
Use a sensible recovery value for the same airflow, temperature and operating mode as your scenario. Heating fan power and sensible heat recovery must use consistent accounting so a fan correction is counted once.
Are the modeled savings a utility bill estimate?
They price the modeled heating and fan kWh difference at an entered flat rate. They do not cover other loads, fixed charges or rate changes.
Similar Calculators
Wall Thermal Bridge & Heat Loss Calculator
Calculate wall heat loss with clear-field, linear junction and point thermal bridge effects. Compare two designs against the same watt limit.
Room Heat Loss & Retrofit Calculator
Explore room heat loss and sensible cooling, compare envelope and ventilation retrofits, and visualize heat flows and outdoor-temperature sensitivity with exact CSV ledgers.
Furnace BTU Calculator for Output & Load Coverage
Compare documented low- and high-stage furnace output against the same heating loads. See unmet BTU, modeled runtime and fuel totals.
Duct Airflow & Velocity Traverse Calculator
Convert signed, area-weighted duct velocity readings to airflow and CFM. Compare two measured passes, reverse flow, and the entered tolerance against a target.