Motor Amperage Calculator & Electrical Duty Profile
Compare two entered AC motor profiles using one fixed RMS voltage. Mix measured line current with shaft-output stages when you know the operating efficiency and true power factor. Inspect the time above a chosen current reference along with the duration-weighted RMS and electrical input energy.
Compare motor line current by stage
Use shaft output and efficiency or recorded line current to watch how two schedules differ in peak draw and electrical energy.
Shaft uses the entered operating efficiency to estimate electrical input power. Reading uses recorded RMS line amps. Use the operating power factor for each stage.
Profile A
30 min above reference of 60 entered min.
Profile B
0 min above reference of 60 entered min.
Line current and energy by stage
Compare both recorded timelines from minute zero. Each profile stops at its entered end time.
- Profile A
- Profile B
- 10 A reference
Review stage readings and exact worksheet CSV
| Stage | Ends at | Line current | Input power | Stage input energy | Reference |
|---|---|---|---|---|---|
| Profile A · 1 | 30 min | 11.547005 A | 6 kW | 3 kWh | Above |
| Profile A · 2 | 60 min | 8 A | 2.771281 kW | 1.385641 kWh | Within |
| Profile B · 1 | 60 min | 10 A | 4.988306 kW | 4.988306 kWh | Within |
How to use this calculator
- Choose the phase mode and enter the fixed supply RMS voltage. Use line-to-line voltage with three phases.
- Enter the current reference from your comparison worksheet.
- Create both stage timelines using recorded line amps or positive shaft output and operating efficiency. Enter duration and true PF for each stage.
- Compare peak stage current, profile RMS, cumulative energy and time above the entered reference.
- Switch the timeline view and export the exact current squares, inputs and energy terms from the stage ledger.
The Formula
The mathematical logic powering this calculation is:
For a stage with shaft output Pₛ in kW and operating efficiency η as a fraction, input power Pᵢ = Pₛ/η. The entered true power factor PF is real input power divided by apparent power. Line RMS amps are 1,000 Pᵢ/(k V PF). Use k = 1 and voltage across the supply for single phase, or k = √3 and line-to-line RMS voltage for balanced three phase. In a recorded stage, use the entered line RMS amps I and calculate input real power k V I PF/1,000 kW.
A stage contributes real input energy equal to its modeled kW times duration in hours. Add these contributions cumulatively across each profile. Peak is the largest stage RMS reading. Profile RMS is the square root of sum of I² times minutes divided by total minutes. The reference applies to each stage individually. Sum the time for stages whose unrounded I² is strictly above the reference squared. Exact equality stays within the reference. Recorded and computed current squares use rational arithmetic. Balanced three-phase measured energy retains a √3 term for exact export. Line amps and the plotted energy are rendered numerically.
Use 1–4 constant stages per profile with durations of 0.001–1,440 minutes, one fixed RMS voltage from 1–1,000 V and an entered current reference from 0–10,000 A. Shaft mode accepts 0.001–1,000 kW, 1–100% efficiency and PF 0.001–1. Reading mode accepts 0–10,000 A and PF 0–1. Zero amps contribute zero energy, including when the entered PF is zero. Use up to six plain decimal places. Use operating-point inputs instead of assuming a fixed nameplate efficiency or power factor across loads.
This steady-stage model applies to single-phase or balanced, sinusoidal three-phase AC. It compares entered conditions and does not infer startup current, waveform peaks, harmonics, unbalance, thermal limits, regenerative work, service suitability, conductor sizing, or protection settings. The time and current reference are user-authored comparison inputs. Electrical measurements and equipment decisions require the relevant qualified review.Worked Example
If you input:
- Supply: Balanced three phase, 400 V line-to-line RMS, 10 A entered reference.
- Profile A: 30 min at 5.4 kW shaft output, 90% efficiency, PF 0.75. Then 30 min at 8 A, PF 0.5.
- Profile B: 60 min at 10 A and PF 0.72.
Result:
A peaks at 11.547005 A and needs about 4.385641 kWh, with 30 minutes above 10 A. Its duration-weighted RMS is 9.933110 A. B stays at 10 A all 60 minutes and needs about 4.988306 kWh.
Frequently Asked Questions
Does 5.4 kW mean shaft or electrical power in Shaft mode?
Enter the mechanical output measured or specified at that point. The worksheet divides it by operating efficiency to get electrical input power.
Why use line-to-line voltage in the three-phase mode?
The √3 multiplier pairs line-to-line RMS voltage with one balanced line RMS current. A line-to-neutral reading needs the matching voltage basis first.
Why can two profiles have the same RMS but different peaks?
RMS combines squared current across elapsed time. One profile can spend less time at a high current and more at zero while retaining the same duration-weighted result.
What should I enter for a running stage with zero shaft output?
Use Reading mode with documented line amps and operating power factor. An energized unloaded stage can still draw current and input power.
Will this tell me whether my breaker, wire or motor is suitable?
The reference line compares the current of each entered stage. Equipment and protective settings depend on the applicable ratings, loading, operating conditions and qualified assessment.
Do the profiles include startup or one more cycle beyond the end?
Each trace stops at the end of the stages you enter. Each value describes the RMS current during an entered steady stage. Starting transients require separate data.
Similar Calculators
Motor Torque & Duty Cycle Calculator
Compare motor peak and RMS torque, reflected inertia, speed, and signed shaft work for the same load motion across two drive options.
AC Power & Power Factor Calculator
Calculate AC watts, vars, volt-amps and power factor for single-phase or balanced three-phase loads. Combine leading and lagging loads, compare an ideal target PF and export the ledger.
Electrical Load & Phase Balance Planner
Compare three-phase load assignments. Calculate conductor current and fundamental neutral current from a shared set of line-to-neutral loads.
Motor RPM from Hz Calculator
Motor RPM from Hz for the exact fields in this tool, with clear inputs and an immediate result for planning or comparison.
