Electrical Load & Phase Balance Planner

Enter simultaneous line-to-neutral loads on a balanced wye voltage source. Compare their existing and alternative phase assignments with paired current bars, phasors and a load ledger. See whether a change affects peak phase current, neutral current or both.

Three-phase wye · RMS

Compare phase loading and neutral current

Ideal, steady sinusoidal four-wire source. The entered reference compares phase currents.

Existing allocation

Above entered reference

Peak phase current

18 A

Fundamental neutral

10.3923 A

Headroom to phase reference
-3 A
Phase current spread
12 A

Alternative allocation

Below entered reference

Peak phase current

12 A

Fundamental neutral

0 A

Headroom to phase reference
3 A
Phase current spread
0 A

Alternative has 6 A less peak phase current. Alternative has 10.3923 A less fundamental neutral current.

Shared active power 4,320 W and net reactive power 0 var.

Alternative has 6 A less peak phase current. Alternative has 10.3923 A less fundamental neutral current.

Current by conductor

Both allocations share one RMS amp scale, 0–18 A. The vertical line marks the 15 A entered reference for phase conductors.

  • Existing allocation
  • Alternative allocation

Phase A

Existing18 A
Alternative12 A

Phase B

Existing12 A
Alternative12 A

Phase C

Existing6 A
Alternative12 A

Neutral

Existing10.3923 A
Alternative0 A

Edit shared loads and assignments

Compare two assignments of these same simultaneous line-to-neutral loads on paper.

Load assignments

Shared load assignments for both allocations
LoadExistingAlt.

720 W · 0 var

AA

720 W · 0 var

AA

720 W · 0 var

AC

720 W · 0 var

BB

720 W · 0 var

BB

720 W · 0 var

CC

Current phasors

The right-hand axis is phase A voltage at 0°. Both plots place 18 A at the outer circle. The neutral arrow balances the three phase arrows. Zero current has no arrow.

  • Phase A
  • Phase B
  • Phase C
  • Neutral
Existing allocation
Existing allocation current vectors referenced to phase A voltage
Neutral angle
150°
Fundamental neutral
10.3923 A
Alternative allocation
Alternative allocation current vectors referenced to phase A voltage
Neutral angle
Unavailable
Fundamental neutral
0 A

Conductor ledger and export

Show current components and phase PF
Existing allocation current components
LineReal (A)Imag. (A)Angle
A1800°
B-6-10.3923-120°
C-35.1962120°
N-95.1962150°
Phase A PF
1 unity
Phase B PF
1 unity
Phase C PF
1 unity
Alternative allocation current components
LineReal (A)Imag. (A)Angle
A1200°
B-6-10.3923-120°
C-610.3923120°
N00Unavailable
Phase A PF
1 unity
Phase B PF
1 unity
Phase C PF
1 unity
Download phase balance comparison CSV
Show selectable CSV text

How to use this calculator

  1. Enter the common line-to-neutral RMS voltage. Set the phase-current reference you want to compare against.
  2. Add the loads expected to operate simultaneously. Enter current, power factor and direction, or active watts and signed reactive vars.
  3. Enter the existing and alternative phase for each of those same loads. A row with the same phase in both columns stays in place.
  4. Compare the phase-current bars and neutral current. Read the phasor and signed power ledger to see which current components add or cancel.
  5. Download the loads, assignments, phase and neutral currents as a CSV.

The Formula

The mathematical logic powering this calculation is:

The worksheet uses fixed, equal RMS voltages V from line to neutral on a three-phase, four-wire wye source at one common frequency. Phase A voltage defines angle 0°. Phase B and phase C are −120° and +120°, respectively. Loads draw sinusoidal line-to-neutral current at the same modeled instant.

Enter RMS current I and displacement power factor PF, or enter active power P in watts and signed reactive power Q in vars. Current-and-PF rows use P = VI × PF and |Q| = VI × √(1 − PF²). Lagging Q is positive and leading Q is negative. Each load belongs to exactly one phase in each allocation. Add the active and reactive power of the loads on that phase. Relative to the phase's own voltage the current phasor is (P − jQ)/V. Rotate that current by its phase voltage angle to express it in the shared frame. Every current arrow is referenced from supply to load. Kirchhoff's law gives the neutral current phasor IN = −(IA + IB + IC). The reported magnitude is the fundamental RMS current. The angle uses phase A voltage as its reference. Zero current has no angle or power factor.

Report peak and spread from the three phase magnitudes. Phase headroom equals the entered phase-current reference minus peak. Equality is resolved at full numerical precision with a floating endpoint tolerance below the 0.000001 A input step. The phase reference has no effect on the calculation of neutral current. Total watts and net vars stay the same when the same loads are reassigned. Phase displacement PF is P/√(P² + Q²) with direction shown separately. The worksheet reports P and net Q totals and individual phase PF.

Enter 1–12 loads, a common voltage of 1–1,000 V, and a phase reference of 0–1,000,000 A. Current inputs are 0–1,000 A, PF magnitude 0–1, active power 0–1,000,000 W, and reactive power −1,000,000 to +1,000,000 var. Numbers accept up to six decimals. The comparison covers ideal fixed supply voltage and fundamental steady load only. Service sizing, breaker selection, equipment ratings, conductor sizing, harmonics, thermal loading, voltage drop, phase-to-phase loads, starting currents, load diversity and physical changes or electrical work are outside its scope.

Worked Example

If you input:

  • Supply and reference: 120 V line-to-neutral and 15 A phase-current reference.
  • Shared loads: Six simultaneous 6 A loads, each at unity displacement power factor.
  • Existing allocation: Three loads on A, two on B and one on C.
  • Alternative allocation: Move one worksheet load from A to C, leaving two on each phase.

Result:

The existing phase currents are 18, 12 and 6 A. Peak current is 3 A above the entered reference and neutral current is 10.3923 A. The alternative gives 12 A on each phase, 3 A of phase headroom and zero modeled neutral current. Both allocations use 4,320 W and zero net vars.

Frequently Asked Questions

Why can equal phase amps still leave neutral current?

The current on each phase can have a different phase shift relative to its voltage. The neutral responds to the sum of the current vectors, including their angles. Magnitude alone cannot determine that sum.

Why does net reactive power remain unchanged while neutral current changes?

Total reactive power adds each load’s signed vars. Neutral current combines each load’s current in the supply frame. Reassigning a load rotates its current vector but keeps its active and reactive power the same under the assumed equal phase voltages.

Which voltage do I enter?

Use the common RMS voltage measured or documented from each phase to neutral in a three-phase four-wire wye system. The worksheet assumes three equal voltage magnitudes, phase angles separated by 120° and a connected neutral.

How do I enter leading and lagging loads?

In current-and-PF mode choose the documented displacement power factor magnitude and direction. In watts-and-vars mode enter lagging reactive power as positive vars and leading reactive power as negative vars. PF of zero permits a purely reactive load.

How should I read the entered current reference?

The reference compares with the largest modeled phase-current magnitude. At equality the headroom is zero. The reference is user-entered and carries no service, circuit or equipment rating.

Does the calculation include harmonic neutral current?

The displayed value covers the sinusoidal fundamental. Nonlinear loads can produce additional neutral current through harmonics. The ideal comparison also assumes unchanged voltage and load behavior across both allocations.

Does this recommend how to move real circuits?

The workspace is for comparing entered assignments on paper. Electrical design and changes require a qualified review of actual equipment, system constraints and applicable requirements.

Similar Calculators