Mixed Air Temperature & Outdoor Fraction Calculator
Use dry-bulb readings and recorded sensor allowances to find every outdoor-air share consistent with each mixed-air measurement. Inspect the modeled temperature envelope, the entered target band and the effect of low inlet separation.
Compare outdoor-air share from temperatures
Use outdoor, return and mixed temperatures to find which outdoor-air shares fit your readings.
Edit sensor readings and outdoor share limits
Enter all readings and differences in this unit.
Only Setup A’s inferred range is within the entered share band.
Target share 25% to 40% · Entered separation 18 °F
Setup A
Entire inferred range is inside targetShare range consistent with readings
25% to 35%
- Nominal arithmetic share
- 30%
- Minimum inlet separation
- 40 °F
Setup B
Only part of inferred range is inside targetShare range consistent with readings
16.666667% to 43.333333%
- Nominal arithmetic share
- 30%
- Minimum inlet separation
- 30 °F
This temperature model assumes representative measurements and complete mixing. Confirm airflow using the required field verification method.
Inspect the mixed-air temperature envelope
Modeled mixture and recorded band
36 to 84 °F
- Modeled inlet envelope
- Recorded mixed band
- Target share band
- Feasible under model
30% outdoor · Setup A
Predicted mixed range 68 °F
Measured mixed range 66 to 70 °F
Temperature intervals intersect
Inlet separation supports the modeled comparison.
Review the exact air-mixing ledger
| Setup | Outdoor °F | Return °F | Mixed °F | Minimum separation | Feasible share ratio | Status |
|---|---|---|---|---|---|---|
| A | 40 to 40 | 80 to 80 | 66 to 70 | 40 | 1/4 to 7/20 | Entire inferred range is inside target |
| B | 50 to 50 | 80 to 80 | 67 to 75 | 30 | 1/6 to 13/30 | Only part of inferred range is inside target |
How to use this calculator
- Choose one temperature unit and enter your target outdoor share band and documented minimum inlet separation.
- Enter synchronized outdoor, return and mixed dry-bulb readings and each recorded symmetric sensor allowance for both setups.
- Compare the full feasible range and the minimum guaranteed separation.
- Inspect a share to see its modeled temperature envelope against the measured band. Review or download the exact measurements and results.
The Formula
The mathematical logic powering this calculation is:
Use one temperature unit throughout. For outside share f between 0 and 1, the dry-bulb model is Tmix = (1 − f) × Treturn + f × Toutdoor. Use synchronized representative readings for two comparable streams before further heating or cooling. The model assumes equal sensible weighting and complete mixing. Temperature layering, unequal stream properties and heat exchange can change a reading. It does not measure a damper position, volume flow or ventilation compliance.
Each entered sensor allowance creates a closed interval centered on its reading. When sensor errors vary independently in their intervals, the minimum modeled mixed temperature at f uses both inlet minima and the maximum uses both inlet maxima. A physical share can explain the measurement when its low prediction is at most the measured high and its high prediction is at least the measured low. Both linear inequalities are solved exactly and intersected with [0, 1]. A result can be an interval, one point or empty.
The nominal share uses (observed mixed − observed return) / (observed outdoor − observed return). It is unavailable for equal inlet readings. Values outside 0–100% remain visible as nominal arithmetic. Guaranteed inlet separation is the distance between the two inlet intervals, zero if they touch or overlap. A target decision requires nonzero guaranteed separation at least as large as your entered minimum. ASHRAE discusses the importance of separation and representative plenum temperatures. Enter a minimum appropriate to your own procedure. The feasible range is still shown for inspection when separation is weak.
The entered target and feasible ranges are closed. Report full inclusion, partial intersection or disjoint ranges only when the separation check passes. Inputs use numeric temperatures −200 to 300, allowances 0–100 in the selected unit, a minimum separation 0–300 and share percentages 0–100. Up to three decimals are supported. Switching the unit changes the input labels; enter all temperatures and temperature differences in that unit. CSV outputs exact share ratios from zero to one where feasible.Worked Example
If you input:
- Target: 25–40% outdoor share and at least 18°F inlet separation
- Setup A: 40°F outdoor, 80°F return and 68 ± 2°F mixed
- Setup B: 50°F outdoor, 80°F return and 71 ± 4°F mixed
Result:
Both nominal shares are 30%. Setup A’s exact 25–35% feasible range fits the target. Setup B’s range extends from 1/6 to 13/30 and only partly overlaps the target.
Frequently Asked Questions
Why might two setups have the same nominal share and different results?
The nominal formula uses point readings. The full range also uses inlet separation and all entered allowances. A smaller separation or wider measured temperature band can make more percentages consistent with the readings.
What happens when the two inlet readings are equal?
The nominal quotient is undefined. A shared temperature interval can make many or all physical shares consistent. The worksheet identifies the weak separation separately.
How can the readings imply no physical fraction?
If the observed mixed interval has no overlap with any modeled temperature between the two streams, no fraction in 0–100% explains it under the entered assumptions.
Can this substitute for direct airflow measurement?
This worksheet compares temperatures through a simplified mixing model. An actual airflow determination depends on representative conditions and the required verification procedure.
Similar Calculators
Psychrometric Calculator
Compare moist-air properties and dry-air mixing on a pressure-specific temperature and humidity chart, with explicit saturation and phase limits.
HVAC Duct Pressure & Airflow Planner
Compare round and rectangular duct paths at a prescribed airflow. Visualize pressure losses, check entered pressure and velocity preferences, and export energy estimates.
Room Heat Loss & Retrofit Calculator
Explore room heat loss and sensible cooling, compare envelope and ventilation retrofits, and visualize heat flows and outdoor-temperature sensitivity with exact CSV ledgers.