Mixed Air Temperature & Outdoor Fraction Calculator

Use dry-bulb readings and recorded sensor allowances to find every outdoor-air share consistent with each mixed-air measurement. Inspect the modeled temperature envelope, the entered target band and the effect of low inlet separation.

Recorded air-mixing measurements

Compare outdoor-air share from temperatures

Edit sensor readings and outdoor share limits

Enter all readings and differences in this unit.

Setup A
Setup B

Only Setup A’s inferred range is within the entered share band.

Target share 25% to 40% · Entered separation 18 °F

Setup A

Entire inferred range is inside target

Share range consistent with readings

25% to 35%

Nominal arithmetic share
30%
Minimum inlet separation
40 °F

Setup B

Only part of inferred range is inside target

Share range consistent with readings

16.666667% to 43.333333%

Nominal arithmetic share
30%
Minimum inlet separation
30 °F

This temperature model assumes representative measurements and complete mixing. Confirm airflow using the required field verification method.

Inspect the mixed-air temperature envelope

Modeled mixture and recorded band

36 to 84 °F

0% outdoor100% outdoor
  • Modeled inlet envelope
  • Recorded mixed band
  • Target share band
  • Feasible under model

30% outdoor · Setup A

Predicted mixed range 68 °F

Measured mixed range 66 to 70 °F

Temperature intervals intersect

Inlet separation supports the modeled comparison.

Review the exact air-mixing ledger
Exact sensor and inferred-share ranges
SetupOutdoor °FReturn °FMixed °FMinimum separationFeasible share ratioStatus
A40 to 4080 to 8066 to 70401/4 to 7/20Entire inferred range is inside target
B50 to 5080 to 8067 to 75301/6 to 13/30Only part of inferred range is inside target

How to use this calculator

  1. Choose one temperature unit and enter your target outdoor share band and documented minimum inlet separation.
  2. Enter synchronized outdoor, return and mixed dry-bulb readings and each recorded symmetric sensor allowance for both setups.
  3. Compare the full feasible range and the minimum guaranteed separation.
  4. Inspect a share to see its modeled temperature envelope against the measured band. Review or download the exact measurements and results.

The Formula

The mathematical logic powering this calculation is:

Use one temperature unit throughout. For outside share f between 0 and 1, the dry-bulb model is Tmix = (1 − f) × Treturn + f × Toutdoor. Use synchronized representative readings for two comparable streams before further heating or cooling. The model assumes equal sensible weighting and complete mixing. Temperature layering, unequal stream properties and heat exchange can change a reading. It does not measure a damper position, volume flow or ventilation compliance.
Each entered sensor allowance creates a closed interval centered on its reading. When sensor errors vary independently in their intervals, the minimum modeled mixed temperature at f uses both inlet minima and the maximum uses both inlet maxima. A physical share can explain the measurement when its low prediction is at most the measured high and its high prediction is at least the measured low. Both linear inequalities are solved exactly and intersected with [0, 1]. A result can be an interval, one point or empty.
The nominal share uses (observed mixed − observed return) / (observed outdoor − observed return). It is unavailable for equal inlet readings. Values outside 0–100% remain visible as nominal arithmetic. Guaranteed inlet separation is the distance between the two inlet intervals, zero if they touch or overlap. A target decision requires nonzero guaranteed separation at least as large as your entered minimum. ASHRAE discusses the importance of separation and representative plenum temperatures. Enter a minimum appropriate to your own procedure. The feasible range is still shown for inspection when separation is weak.
The entered target and feasible ranges are closed. Report full inclusion, partial intersection or disjoint ranges only when the separation check passes. Inputs use numeric temperatures −200 to 300, allowances 0–100 in the selected unit, a minimum separation 0–300 and share percentages 0–100. Up to three decimals are supported. Switching the unit changes the input labels; enter all temperatures and temperature differences in that unit. CSV outputs exact share ratios from zero to one where feasible.

Worked Example

If you input:

  • Target: 25–40% outdoor share and at least 18°F inlet separation
  • Setup A: 40°F outdoor, 80°F return and 68 ± 2°F mixed
  • Setup B: 50°F outdoor, 80°F return and 71 ± 4°F mixed

Result:

Both nominal shares are 30%. Setup A’s exact 25–35% feasible range fits the target. Setup B’s range extends from 1/6 to 13/30 and only partly overlaps the target.

Frequently Asked Questions

Why might two setups have the same nominal share and different results?

The nominal formula uses point readings. The full range also uses inlet separation and all entered allowances. A smaller separation or wider measured temperature band can make more percentages consistent with the readings.

What happens when the two inlet readings are equal?

The nominal quotient is undefined. A shared temperature interval can make many or all physical shares consistent. The worksheet identifies the weak separation separately.

How can the readings imply no physical fraction?

If the observed mixed interval has no overlap with any modeled temperature between the two streams, no fraction in 0–100% explains it under the entered assumptions.

Can this substitute for direct airflow measurement?

This worksheet compares temperatures through a simplified mixing model. An actual airflow determination depends on representative conditions and the required verification procedure.