Exhaust Fan CFM & Curve Operating Point Calculator

Compare a pair of fan pressure records with the same measured path. Interpolate between matching airflow stations, keep every supported intersection or coincident range, and see which matches fall inside your comparison band.

Documented pressure curves

Compare exhaust fan and path pressure curves

Edit airflow stations and pressure curves

Use increasing airflow and the same pressure convention for each curve.

Station 1
Station 2
Station 3
Station 4

All of fan A’s matches are inside the airflow band.

Entered airflow band

200 to 220 CFM

Fan A

All matches in band

  • 200 CFM · 70 Pa

Fan B

Matches outside band

  • 150 CFM · 55 Pa

Inspect a measured airflow span

Pressure by airflow

0 to 150 Pa

0 CFM300 CFM
  • Fan A
  • Fan B
  • Shared path
  • Airflow band
  • Selected span
  • Pressure match

0 to 100 CFM

Path pressure 20 Pa to 40 Pa

Fan A

Pressure 120 Pa to 100 Pa

No local match

Fan B

Pressure 130 Pa to 70 Pa

No local match

Review the exact fan curve ledger
Exact measured pressure stations
StationAirflow (CFM)Path (Pa)Fan A (Pa)Fan B (Pa)
1020120130
21004010070
3200707040
43001103020
Exact pressure matches by fan
FanFrom (CFM)To (CFM)Start pressure (Pa)End pressure (Pa)
A2002007070
B1501505555

How to use this calculator

  1. Choose the airflow band you want to compare using your own specification.
  2. Enter common airflow stations in increasing order with documented pressure readings for both fans and the shared path.
  3. Look for each marked pressure match. Some records can agree over an interval or at multiple disconnected flows.
  4. Select a span to inspect endpoint pressure readings and local matches. Export the exact stations and merged matches.

The Formula

The mathematical logic powering this calculation is:

Use two to six increasing airflow stations in cubic feet per minute, with a fan A pressure, fan B pressure and shared path pressure at every station. Enter pressures in pascals with one matched pressure convention and compatible configurations. The two fan records represent alternative tests or products. The common path is the same entered resistance record for both.

Within adjacent stations, interpolate each pressure linearly versus airflow. Subtract path pressure from fan pressure at each endpoint. Opposite signs give one exact intersection. If the differences are d₀ and d₁, its fractional position is d₀/(d₀ − d₁). Use that same fraction to interpolate airflow and path pressure. An endpoint with zero difference is itself a match. Two zero differences make the entire closed span coincident. The worksheet merges matches that touch and keeps isolated matches as points. No match is inferred beyond the entered domain.

Every modeled airflow match qualifies when its full point or interval lies inside the closed entered comparison band. A fan with at least one qualifying airflow and some outside the band is partly inside, even if one coincident range is only partly in the band. A fan with no model intersection has a separate result. Equality on either band endpoint is included.

Airflow and band endpoints accept 0–100,000 CFM. Pressure accepts 0–20,000 Pa. Entries use up to three decimal places, and interpolation and membership comparisons retain exact fractions. Use a matching fan speed and air condition within each record, with comparable pressure definitions between the fan and path. An intersection describes the entered piecewise curves. Actual operating stability, installed performance, equipment limits, airflow requirements and compliance remain outside this model.

Worked Example

If you input:

  • Flow stations: 0, 100, 200, 300 CFM
  • Shared path: 20, 40, 70 and 110 Pa
  • Fan A: 120, 100, 70 and 30 Pa
  • Fan B: 130, 70, 40 and 20 Pa
  • Comparison band: 200–220 CFM

Result:

Fan A matches at 200 CFM and 70 Pa, exactly on the lower comparison bound. Fan B matches at 150 CFM and 55 Pa.

Frequently Asked Questions

Why can the same fan show more than one match?

The difference between fan and path pressure can change sign several times. The worksheet preserves every intersection in the entered domain. Physical stability needs additional evidence.

What if pressure is equal across a whole span?

The two entered lines are coincident there. The worksheet keeps the complete inclusive airflow interval and checks whether it fits the band.

Why do I need matching airflow stations?

The worksheet compares both fans and the path at the same flow coordinates. Choose documented comparable values on common stations before entering them.

Can I combine a static-pressure fan table with a total-pressure path?

Use comparable pressure definitions on both sides of the comparison. Pressure terms with different references or definitions can produce misleading intersections.

What does a match outside the entered airflow band mean?

The pressure curves agree at that modeled flow, which lies outside your chosen comparison range.

Similar Calculators