Electrical Box Fill Calculator
See which allowances make up the required volume in one undivided dwelling box. Group conductors and yokes by gauge, enter ordinary equipment grounding conductors, and check two marked box volumes against the same contents. The worksheet applies selected 2023 NEC box-fill rules within the scope shown at the top.
Compare required and marked box volume
Review conductor, yoke, clamp and ground allowances for one undivided dwelling box. Compare two marked volumes using the same contents.
This compares volume allowances for the selected configuration. The applicable code edition, box listing and installation conditions need separate review.
Marked box volumes
Use the marked usable volume in cubic inches. Both boxes are evaluated with the same contents.
Counts by wire gauge
Use one row per AWG. Each count describes a physical conductor, loop or yoke.
How to classify each count
- Single count
- Outside conductors ending or spliced here, plus unspliced pass-throughs, counted once. Use a separate count for qualifying loops.
- Double-count loops
- Count each qualifying continuous loop once here. The model doubles its allowance. This applies to a loop or coil at least twice the required free conductor length.
- Single-gang yokes
- Group yokes by the largest conductor connected to a device on that yoke. Each yoke counts twice. A duplex receptacle on one yoke is one yoke.
- Entering grounds
- Count equipment grounding conductors entering from outside the box. The calculation pools entering grounds across all gauges.
Ordinary internal cable clamps
Include any larger conductor contained inside the box. An external clamping mechanism adds no clamp allowance.
Required volume 22.5625 cubic inches.
Required versus marked volume
Bars share a cubic-inch scale. Read the exact differences below.
0.0625 in³ short of required volume
2.4375 in³ above required volume
Volume allowance breakdown
- Conductors and loops
- 13 in³
- Single-gang yokes
- 4.5 in³
- Internal clamps
- 2.25 in³
- Entering equipment grounds
- 2.8125 in³
Internal clamps use one allowance at 12 AWG, the largest conductor you identified inside the box.
5 entering grounds use 1.25 allowances at 12 AWG. The first four share one allowance and each additional ground adds a quarter.
Allowance ledger by gauge
| AWG | Per allowance (in³) | Conductor fill (in³) | Yoke fill (in³) |
|---|---|---|---|
| 14 | 2 | 4 | 0 |
| 12 | 2.25 | 9 | 4.5 |
View CSV text
How to use this calculator
- Choose the box configuration. This estimate covers one undivided dwelling box and conventional single-gang yokes. Other configurations display the part of the scope that requires a separate calculation.
- Enter the marked volume in cubic inches. Enable Compare a second box to check another marked size using the same contents.
- Add one row per AWG. Enter the single-count conductors, qualifying double-count loops, single-gang yokes at their largest connected gauge, and entering equipment grounds.
- If the box has ordinary internal cable clamps, select the largest conductor actually present. Include larger conductors contained within the box when identifying that gauge.
- Read Required versus marked volume, then open Allowance ledger by gauge or download the CSV to review the exact figures.
The Formula
The mathematical logic powering this calculation is:
Required volume is the sum of the conductor, device-yoke, internal clamp and equipment-ground allowances. Under the supported 2023 NEC §314.16 rules, multiply each counted conductor by its gauge allowance from Table 314.16(B)(1). A qualifying continuous loop or coil uses two allowances. Each conventional single-gang yoke uses two allowances at the largest gauge connected to a device on that yoke. Ordinary internal cable clamps, if present, add one allowance at the largest conductor present. Pool the entering equipment grounding conductors across gauges. Use one allowance for one to four grounds, plus a quarter for each after four, all at the largest entering ground gauge. Marked volume minus required volume gives the signed difference. Compare the exact cubic-inch values.Method sources
- NFPA 70, 2023 edition · National Electrical Code
- NFPA code development · Base 2023 §314.16(B)(5) text, Public Input 1580
- NFPA code development · First Revision 7734 and entering equipment grounds
- New York Department of State · 2023-based residential extract, table E3905.12.2.1 and conductor, clamp and yoke allowances
Worked Example
If you input:
- Box A marked volume (in³): 22.5
- Box B marked volume (in³): 25
- Gauge group 1: 14 AWG: 2 single-count conductors and 3 entering grounds
- Gauge group 2: 12 AWG: 4 single-count conductors, 1 single-gang yoke and 2 entering grounds
- Ordinary internal cable clamps: Present. Largest conductor is 12 AWG.
Result:
The conductors use 13 in³, the yoke uses 4.5 in³ and internal clamps use 2.25 in³. The five entering grounds use 1.25 allowances at 12 AWG, or 2.8125 in³. The total is 22.5625 in³. Box A is 0.0625 in³ short and Box B is 2.4375 in³ above the required volume.
Frequently Asked Questions
Which conductors receive a single allowance?
Count each conductor that comes from outside and terminates or splices in the box once. Count an uninterrupted pass-through once. A qualifying long continuous loop or coil has two allowances, so enter it in the double-count field. A conductor that stays entirely inside the box adds no ordinary conductor allowance.
How do I count devices on one yoke?
Count conventional single-gang yokes or straps. A duplex receptacle on one yoke is one yoke. Group each yoke under the largest conductor connected to a supported device. Its allowance is twice the table volume for that gauge. A device wider than one gang requires a separate calculation.
Do mixed equipment ground sizes each have a separate allowance?
The supported 2023 NEC method pools the ordinary equipment grounding conductors that enter the box. Up to four share one allowance at the largest entering ground gauge. Each additional entering grounding conductor adds a quarter allowance at that same gauge. Isolated grounding arrangements and exceptions require separate review.
What if the largest conductor inside the box is a pigtail?
An entirely internal conductor adds no ordinary conductor allowance. It can still determine the ordinary internal-clamp allowance because that rule uses the largest conductor present. Select its wire gauge in the clamp section if it is the largest.
Where do I find the marked volume for this comparison?
Enter the manufacturer’s cubic-inch marking for each candidate box in the regular undivided configuration. The worksheet uses that entered volume and accepts up to 100 in³. Accessories that change usable volume, divided enclosures and unmarked box sizing need a separate review.
What does equal marked and required volume mean?
The two values are equal under the entered scope and 2023 NEC allowance model. A difference below zero means the marked cubic inches are below the calculated allowance. Review local adoption, hardware listing, physical installation and other code provisions independently.
Similar Calculators
Conduit Fill Calculator
Compare current and planned cable fill across conduit sizes. Inspect mixed cable areas, explicit fill targets and additional-cable capacity with a reusable plan.
DC Voltage Drop & Cable Loss Calculator
Compare DC cable voltage drop, power losses and load limits with separate conductor lengths, connection resistance, constant-power loads and visual sweeps.
AC Power & Power Factor Calculator
Calculate AC watts, vars, volt-amps and power factor for single-phase or balanced three-phase loads. Combine leading and lagging loads, compare an ideal target PF and export the ledger.