DC Voltage Drop & Cable Loss Calculator
Compare up to four entered cable alternatives on the same DC circuit. See terminal voltage, conductor and connection losses, and whether each alternative meets your own voltage criteria. Enter outgoing and return lengths separately, include source and connection resistance, and switch between fixed current and delivered DC power. Explore how load changes voltage and heat loss, inspect the complete table, and export every input and sweep point. Exact unit conversions preserve physical quantities. It compares voltage performance from authored resistance data; it does not infer a safe wire gauge, ampacity, protection scheme or dynamically stable equipment behavior.
Voltage drop, cable losses & load limits
Compare entered cable resistance data, see both conductors, and explore current or constant-power loads.
Voltage performance only. A result that meets your criteria does not establish ampacity, insulation, protection, installation safety or dynamic stability. Enter resistance at the intended operating conditions; this model does not infer a safe wire gauge.
1. Source & complete conductor path
Ideal DC source before source resistance; 0.1–1000 V.
Both lengths convert exactly, or neither changes.
Actual outgoing conductor length, 0–10,000 m. Fractions are accepted.
Actual return conductor length, 0–10,000 m. No extra factor of two.
Fixed source series resistance, 0–10,000 mΩ. Confirm zero for an ideal source.
Total external connections / devices, excluding source and conductor resistance. 0–10,000 mΩ.
2. Load & your voltage criteria
Power mode accounts for current rising as terminal voltage falls. Inactive inputs are retained.
Requested steady current, 0–10,000 A.
Your maximum drop relative to the source, 0–100%. Not a code threshold.
Your separate minimum terminal voltage, 0–1000 V. Above-source values are valid but impossible.
Explicit plot extent, 0–10,000 A. The requested load is not clamped.
3. Compare cable alternatives
Use one-conductor resistance per stated length from your cable data. The same resistance per length applies to each separately entered conductor. Labels do not determine ratings. Ω/km and mΩ/m have the same numeric scale.
3 alternatives evaluated at the requested load. 2 meet entered voltage criteria.
At your requested 20 A
Cable A
Operating point
23.36 V at the load
- Current
- 20 A
- Voltage drop
- 0.64 V (2.66667%)
- Source power
- 480 W
- Delivered power
- 467.2 W
- Resistive loss
- 12.8 W
- Delivery efficiency
- 97.33333%
Meets entered voltage criteria
Drop criterion: met. Minimum voltage: met.
Voltage-limited model ceilings
Current: 22.5 A.
Delivered power: 523.8 W.
Unconstrained constant-power fold: 4,500 W.
Cable B
Operating point
23.6 V at the load
- Current
- 20 A
- Voltage drop
- 0.4 V (1.66667%)
- Source power
- 480 W
- Delivered power
- 472 W
- Resistive loss
- 8 W
- Delivery efficiency
- 98.33333%
Meets entered voltage criteria
Drop criterion: met. Minimum voltage: met.
Voltage-limited model ceilings
Current: 36 A.
Delivered power: 838.08 W.
Unconstrained constant-power fold: 7,200 W.
Cable C
Operating point
22.96 V at the load
- Current
- 20 A
- Voltage drop
- 1.04 V (4.33333%)
- Source power
- 480 W
- Delivered power
- 459.2 W
- Resistive loss
- 20.8 W
- Delivery efficiency
- 95.66667%
Does not meet entered voltage criteria
Drop criterion: not met. Minimum voltage: not met.
Voltage-limited model ceilings
Current: 13.84615 A.
Delivered power: 322.33846 W.
Unconstrained constant-power fold: 2,769.23077 W.
Resistance budget for your requested load
Voltage floor: 23.28 V. Binding criteria: maximum drop.
Total series budget: 0.036 Ω. After entered source and connection resistance: 0.034 Ω for both conductors.
Maximum one-conductor resistance per length: 3.4 Ω/km (1.03632 Ω/1000 ft). Compare actual cable data; no wire gauge or ampacity is inferred.
How Cable A responds to load
High-voltage branch only in constant-power mode. Crosses mark requests with no attained operating result; the curve stops at unavailable points. Diamonds mark the fold.
Blue: attained terminal voltage. Dashed purple: entered voltage floor. Red ×: unavailable. Purple ◆: power fold. Voltage axis starts at 0 V.
Selected demand: 20 A
Operating point
23.36 V at the load
- Current
- 20 A
- Voltage drop
- 0.64 V (2.66667%)
- Source power
- 480 W
- Delivered power
- 467.2 W
- Resistive loss
- 12.8 W
- Delivery efficiency
- 97.33333%
Meets entered voltage criteria
Drop criterion: met. Minimum voltage: met.
| Demand (A) | State | Load V | Current A | Drop V | Loss W | Voltage criteria |
|---|---|---|---|---|---|---|
| 0 | Operating point | 24 | 0 | 0 | 0 | Met |
| 0.5 | Operating point | 23.984 | 0.5 | 0.016 | 0.008 | Met |
| 1 | Operating point | 23.968 | 1 | 0.032 | 0.032 | Met |
| 1.5 | Operating point | 23.952 | 1.5 | 0.048 | 0.072 | Met |
| 2 | Operating point | 23.936 | 2 | 0.064 | 0.128 | Met |
| 2.5 | Operating point | 23.92 | 2.5 | 0.08 | 0.2 | Met |
| 3 | Operating point | 23.904 | 3 | 0.096 | 0.288 | Met |
| 3.5 | Operating point | 23.888 | 3.5 | 0.112 | 0.392 | Met |
| 4 | Operating point | 23.872 | 4 | 0.128 | 0.512 | Met |
| 4.5 | Operating point | 23.856 | 4.5 | 0.144 | 0.648 | Met |
Where the voltage and power go
The source, both conductors, and all entered connections form one series path. The breakdown follows the selected sweep point below.
Positive conductor
0.015 Ω
0.3 V drop
6 W loss
Return conductor
0.015 Ω
0.3 V drop
6 W loss
Source resistance
0 Ω
0 V drop
0 W loss
Connections / devices
0.002 Ω
0.04 V drop
0.8 W loss
Total series resistance: 0.032 Ω. Blue bars show shares of voltage drop; purple bars show shares of resistive loss.
Constant-power roots and model assumptions
For total series resistance R, source Vs and delivered power P: V² − VsV + RP = 0. The high-voltage / lower-current root is shown in the comparison and sweep. A second mathematical root does not establish stable equipment behavior.
Cable A requested-load diagnostic: No separate lower-voltage root applies to this request.
Cable B requested-load diagnostic: No separate lower-voltage root applies to this request.
Cable C requested-load diagnostic: No separate lower-voltage root applies to this request.
Resistance is fixed at the entered conditions. AC reactance, transient response, temperature rise, protection and battery state of charge are outside this model.
Victron Wiring Unlimited: DC circuit theory. Use the cable supplier’s operating-condition resistance data; bulk material resistivity alone is not a cable rating.
Keep the comparison
Selectable CSV fallback
Complete authored inputs, results and all sweep points are generated when this section opens.
The download and fallback contain identical CSV. Every cell is quoted and text-prefixed; exact rational source values are preserved.
How to use this calculator
- Enter the DC source voltage before source resistance. Enter positive and return conductor lengths separately; changing metres and feet converts both exactly.
- Enter fixed source resistance and the total resistance of external connections/devices. Confirm zero when intentionally omitted; do not include the conductors twice.
- Choose constant current or delivered DC power. Enter your own maximum drop percentage, minimum load voltage and plotting extent. The two voltage criteria remain independent.
- Add one to four labeled cable alternatives using one-conductor resistance data at the intended operating condition. Resistance-unit changes preserve the same physical quantity.
- Compare the requested-load cards and voltage-based resistance budget. Select a cable and sweep point to inspect its terminal voltage and component drop/loss breakdown, including unavailable requests.
- Read the paginated sweep table or download the complete CSV. Open Selectable CSV fallback to copy the identical export. Check actual equipment and cable suitability separately.
The Formula
The mathematical logic powering this calculation is:
For one-conductor resistance per metre r and separately entered positive and return lengths Lp and Ln, total series resistance R = rLp + rLn + Rs + Rc. Rs is entered source resistance; Rc is the total additional external connection/device resistance. Do not double either entered conductor length.
For a constant-current request I, terminal voltage V = Vs − IR, component drop = I × component resistance, and component heat loss = I² × component resistance. A positive terminal voltage gives an attained operating point. At zero voltage the request is a boundary; negative calculated terminal voltage means insufficient source voltage in this passive-load model. Those cases retain voltage diagnostics without claiming delivered power or attained losses.
For delivered constant power P, V² − VsV + RP = 0. Classify D = Vs² − 4RP exactly. D < 0 has no real steady-state operating point. D = 0 is the fold boundary at V = Vs/2. With D > 0, the primary high-voltage root is (Vs + √D)/2 and current is 2P/(Vs + √D). A separate lower-voltage root is a mathematical diagnostic, not a claim of dynamic stability. With zero resistance use V = Vs; at zero requested power use I = 0 and V = Vs. Numerical root outputs must satisfy circuit and power residual checks.
The two independent voltage criteria are drop percentage ≤ entered maximum and terminal voltage ≥ entered minimum. Their combined floor F = max(Vs × (1 − maximum drop/100), minimum voltage). If F > Vs, no load passes. For R > 0 and F ≤ Vs, the current ceiling is (Vs − F)/R; when F = 0 its zero-voltage endpoint is excluded. High-branch power is limited at current min((Vs − F)/R, Vs/(2R)); evaluate P = I(Vs − IR) there. Zero resistance has no finite voltage-limited ceiling in this ideal model. These ceilings are not ampacity or recommended continuous loads.
At positive requested current, total resistance budget = (Vs − F)/I. At positive requested power it is F(Vs − F)/P when F ≥ Vs/2, otherwise Vs²/(4P). Subtract Rs + Rc to obtain the conductor-loop budget. A negative remainder means cable replacement alone cannot meet the criteria. Divide a nonnegative remainder by Lp + Ln for the maximum one-conductor resistance per metre; zero combined length makes this quantity inapplicable. A zero-load request imposes no finite resistance budget when the voltage floor is possible.
Each candidate sweep evaluates 101 uniformly spaced demands plus exact requested and applicable criterion/fold/zero-voltage boundary points inside the entered extent, deduplicated and sorted. Unavailable points break the curve. Canonical inputs, resistance sums and boundary decisions use exact fractions. One foot equals 381/1250 metre; Ω/km and mΩ/m have the same scale. CSV retains exact rational values and numerical operating precision.Worked Example
If you input:
- Source: 24 V DC; 0 mΩ source resistance
- Conductors: 5 m positive + 5 m return; 2 mΩ total external connections
- Load: 20 A constant current
- Criteria: 3% maximum drop and 23 V minimum at load
- Alternatives: Cable A: 3 Ω/km; B: 1.8 Ω/km; C: 5 Ω/km
- Sweep: 0–50 A
Result:
Cable A has 0.032 Ω total resistance: 0.64 V drop, 23.36 V at the load and 12.8 W resistive loss. Cable B has 0.020 Ω total, 0.4 V drop, 23.6 V at the load and 8 W loss. Both meet the entered criteria. Cable C has 0.052 Ω total, 1.04 V drop, 22.96 V at the load and 20.8 W loss; it fails both criteria. The stricter voltage floor is 23.28 V. The requested total resistance budget is 0.036 Ω; after the connections, 0.034 Ω remains across 10 m of conductor, equivalent to 3.4 Ω/km. These are illustrative resistance values, not cable ratings.
Frequently Asked Questions
Do I enter one-way length or the complete circuit length?
Enter the outgoing positive conductor and return conductor separately. The calculator adds their resistance without another factor of two. For a 120-foot outward run and 120-foot return, enter 120 feet in each field. Unequal conductor lengths are supported.
Can this calculate a safe 12V wire size or minimum AWG?
It calculates voltage performance and a resistance-per-length budget for the entered circuit. It does not select AWG, certify ampacity, or determine insulation and protection requirements. Compare actual cable resistance data and separately verify the other requirements for the application.
Why does a constant-power load draw more current as voltage falls?
Delivered DC power is terminal voltage multiplied by current. Holding power fixed while voltage falls requires more current, which adds resistive drop. The quadratic model accounts for this feedback and reports requests above its mathematical power limit as unavailable.
Does the second power root describe a stable operating point?
No stability claim is made for either root. The primary display uses the higher-voltage, lower-current solution. The lower-voltage solution is shown only as a mathematical diagnostic. Actual load controls, startup behavior and dynamics are outside this steady-state model.
Is a 3% or 5% voltage-drop limit always required?
The limits here are authored criteria, not a universal standard or equipment rating. Enter the requirements appropriate to the equipment and application. The minimum terminal-voltage criterion may be stricter than the percentage criterion, and both are checked independently.
Why does changing Ω/km to mΩ/m leave the number unchanged?
One ohm per kilometre equals one milliohm per metre. The two labels have the same physical scale. Ω per 1000 feet has a different scale; conversion uses the exact foot-to-metre relationship and preserves both conductor resistances.
What does a negative remaining conductor resistance budget mean?
The entered source and connection resistances alone exceed the total resistance allowed by the requested load and voltage criteria. A lower-resistance cable alone cannot fix that result. The negative remainder is retained as a diagnostic rather than clipped to zero.
Does the loss result include temperature rise or inverter efficiency?
No. I²R is resistive power loss at the fixed entered resistance. The model does not solve thermal equilibrium or temperature-dependent resistance. Power mode means delivered DC terminal power; it does not automatically convert AC load power or include inverter efficiency.
Similar Calculators
Ohm's Law Calculator
Calculate voltage, current, or resistance using Ohm's Law — enter any two values to find the third.
Power Calculator
Calculate electrical power in watts from voltage and current, or find current from power and voltage.
Battery Runtime Calculator & Duty Cycle Planner
Compare steady and repeating load profiles. Estimate battery runtime from amp-hours, inverter loads, reserve charge and an optional discharge-rate correction.