Buck-Boost Transformer Calculator
See how the same voltage ratio behaves as the line changes. Keep the output target, permitted input interval and load-current ceiling visible together for each candidate.
Compare two fixed voltage ratios
Check low, nominal and high line conditions against your load band and both candidates’ entered limits.
Line and load data
Line states
Enter RMS line voltage and the associated expected load current for each state.
Candidate conditions
Use a documented input/output pair, its permitted input interval and the applicable load-current ceiling.
Output and operating limits
1 of 2 candidates meets all entered checks
The line spread can fit the target with a fixed ratio
Required floor 1.094527 and ceiling 1.115207 from the voltage endpoints.
Candidate A
One or more state checks fail
- Fixed ratio
- 15/13
- Boost 15.38462%
- Ideal output span
- 231.9231–250.3846 V
- Input span meeting both voltage bands
- 200–209.7333 V
- Largest differential VA in the entered states
- 680.3077 VA
Candidate B
All entered states within limits
- Fixed ratio
- 115/104
- Boost 10.57692%
- Ideal output span
- 222.2596–239.9519 V
- Input span meeting both voltage bands
- 198.9565–218.8522 V
- Largest differential VA in the entered states
- 467.7115 VA
Target 220–242 V · plotted scale 220–250.3846 V.
Filled marks pass all entered checks. Open marks have a failed check.
State ledger and CSV
| State | Ideal output | Target band | Input band | Load current |
|---|---|---|---|---|
| Low line | 231.9231 V | Within | Within | Within |
| Nominal line | 240 V | Within | Within | Within |
| High line | 250.3846 V | Above | Within | Within |
| State | Ideal output | Target band | Input band | Load current |
|---|---|---|---|---|
| Low line | 222.2596 V | Within | Within | Within |
| Nominal line | 230 V | Within | Within | Within |
| High line | 239.9519 V | Within | Within | Within |
How to use this calculator
- Enter the load’s permitted RMS voltage band. Add low, nominal and high input-voltage states with their expected load currents.
- For each candidate, enter a documented reference input/output pair in the intended direction. Enter its applicable input range and load-current ceiling.
- Read which candidates stay within each entered limit. Check whether the measured spread could fit the load band using any single constant ratio.
- Compare the plotted outputs, then open the state ledger to see which check fails. The CSV includes exact rational values.
The Formula
The mathematical logic powering this calculation is:
For the entered reference pair, ratio k = reference output ÷ reference input. Ideal output in a state is k × line voltage. Positive k preserves the order of line extrema. The load-voltage target gives an ideal input interval from target minimum ÷ k to target maximum ÷ k. Intersect it with the authored allowed input interval.
Across all entered line values, the theoretical ratio floor is target minimum ÷ low line. The ceiling is target maximum ÷ high line. If the floor exceeds the ceiling, no single constant ratio satisfies both endpoints. Equality represents one theoretical ratio. This voltage-only test is independent of catalog and current constraints.
Check output range, candidate input range and load current separately. Boundaries are inclusive and comparisons use exact decimal fractions before display rounding. The single-phase differential VA shown for comparison is |ideal output − line voltage| × entered load current. It is an estimated transfer quantity. The entered current ceiling comes from applicable product data.
Enter 1–1,500 V RMS and 0–5,000 A with up to six decimals. Low, nominal and high line values must be in order, and equal readings are permitted. The chart shows ideal ratio arithmetic, including out-of-range points labelled in the ledger. Current checks apply to the three entered states only. The calculation assumes a fixed ratio and frequency. Actual transformer voltage regulation, product derating, protections and installation details require applicable equipment data.Worked Example
If you input:
- Target minimum (V): 220
- Target maximum (V): 242
- Line states: 201 V / 22 A, 208 V / 20 A, and 217 V / 12 A
- Candidate A: 208 → 240 V, 200–220 V input, 24 A load limit
- Candidate B: 208 → 230 V, 198–223 V input, 25 A load limit
Result:
Candidate A reaches about 250.3846 V at high line and exceeds the 242 V target maximum. Candidate B gives about 222.2596–239.9519 V and stays within all three entered checks at every state.
Frequently Asked Questions
Why use more than one line voltage?
A fixed ratio applies the same percentage change across the line range. A boost that reaches the target at low line can exceed the target at high line.
How can I tell whether any fixed ratio could work?
Compare the required ratio floor from the low line with the ceiling from the high line. A floor above the ceiling leaves no fixed ratio that satisfies the entered output band.
Does the calculation infer manufacturer limits from the reference ratio?
Enter the applicable input range and load-current ceiling separately. A voltage ratio alone does not establish either limit.
How are current and differential VA used?
Current is checked against the entered load ceiling in each state. The differential VA is a single-phase comparison based on the modeled voltage change and the corresponding load current.
Can the high-line state have less current than low line?
Yes. Enter each expected load current independently. The line voltages are ordered but their currents can differ in any order.
Does a candidate passing all checks confirm a product choice?
The results show agreement with the entered voltage and current constraints. Product suitability depends on manufacturer and application data beyond these idealized checks.
Similar Calculators
Transformer kVA, Load & Loss Calculator
Compare transformer kVA ratings, currents and profile energy losses. Model energized idle versus switched off, inspect load curves and export exact energy and cost ledgers.
AC Power & Power Factor Calculator
Calculate AC watts, vars, volt-amps and power factor for single-phase or balanced three-phase loads. Combine leading and lagging loads, compare an ideal target PF and export the ledger.
DC Voltage Drop & Cable Loss Calculator
Compare DC cable voltage drop, power losses and load limits with separate conductor lengths, connection resistance, constant-power loads and visual sweeps.
Electrical Load & Phase Balance Planner
Compare three-phase load assignments. Calculate conductor current and fundamental neutral current from a shared set of line-to-neutral loads.