Tankless Water Heater Demand & Sizing Planner
A tankless heater must meet simultaneous hot-water demand at the required temperature rise, not just a daily water volume. Build an explicit fixture schedule, distinguish mixed fixture flow from heater flow, and compare up to three candidates across up to three seasonal inlet cases. The workspace shows a duration-scaled demand chart, minimum-activation and maximum-flow diagnostics, ideal capacity curves, complete interval and fixture ledgers, and exact CSV export. Compare overlapping fixtures with staggered use without changing their total water consumption. Enter compatible rated input power, steady heat-conversion efficiency and flow limits for your candidates; no standard equipment size is selected automatically. This is a constant-property, steady-response planning model, not manufacturer performance data, an installation design, a safe-temperature recommendation, an annual savings forecast or an estimate of installation prices.
See when hot-water demand overlaps.
Compare fixture schedules, seasonal inlet temperatures and heater limits. Explore the same demand in litres or US gallons, Celsius or Fahrenheit.
Current demand calculated. Inspect all inlet cases and candidate limits below.
Operating window and units
This is an explicit operating window, not an annual forecast. Start times are included, end times excluded. Temperature inputs are mathematical assumptions, not safe-temperature recommendations. Required numbers accept six decimals or exact fractions.
Seasonal inlet cases
Compare up to three measured or assumed inlet temperatures separately. Setpoint must exceed every inlet; fixture targets must be at or above every inlet.
Fixture schedule
Enter total mixed fixture flow, including both hot and cold water. Up to 24 fixture intervals can overlap. Each interval stays within the authored window; a target equal to an inlet needs no heat for that case.
Heater candidates
Compare up to three entered candidates. Input power × steady conversion efficiency gives useful output. Use compatible product data; efficiency is not a substitute for a seasonal UEF rating. Minimum and maximum flow apply to the heater stream, not total mixed fixture flow. Tariffs must be USD per input kWh of the relevant energy source.
Demand timeline — Winter inlet
Rectangle widths follow actual interval durations. Blue is required useful heat; the dashed line is selected-candidate output. Hatched intervals fail at least one entered limit, including activation or flow even when power is adequate. See the diagnostic ledger for every reason.
| Start min | End min | Fixtures | Mixed flow | Heater flow | Bypass flow | Required heat | Interval heat | Selected candidate |
|---|---|---|---|---|---|---|---|---|
| 0 | 5 | Shower | 8 L/min | 6 L/min | 2 L/min | ≈ 16.744 kW | ≈ 1.39533 kWh | Within entered limits |
| 5 | 10 | Kitchen · Shower | 12 L/min | ≈ 9.5 L/min | ≈ 2.5 L/min | ≈ 26.5113 kW | ≈ 2.20928 kWh | Within entered limits |
| 10 | 15 | Kitchen | 4 L/min | ≈ 3.5 L/min | ≈ 0.5 L/min | ≈ 9.76733 kW | ≈ 0.813944 kWh | Within entered limits |
| 15 | 30 | Idle | 0 L/min | 0 L/min | 0 L/min | 0 kW | 0 kWh | No heating requested |
Compare every inlet and candidate
| Inlet case | Inlet temperature | Heater rise | Peak mixed flow | Peak heater flow | Peak heat | Mixed volume | Heated volume | Thermal energy | Heating minutes |
|---|---|---|---|---|---|---|---|---|---|
| Winter inlet | 10 °C | 40 Δ °C | 12 L/min | ≈ 9.5 L/min | ≈ 26.5113 kW | 120 L | 95 L | ≈ 4.41856 kWh | 15 |
| Summer inlet | 20 °C | 30 Δ °C | 12 L/min | ≈ 8.66667 L/min | ≈ 18.1393 kW | 120 L | ≈ 86.6667 L | ≈ 3.02322 kWh | 15 |
| Inlet / candidate | Useful power | Ideal available heater flow | Unmet min | Activation min | Flow exceeded min | Power exceeded min | Peak power ratio | Peak flow ratio | Modeled input energy | Energy cost |
|---|---|---|---|---|---|---|---|---|---|---|
| Winter inlet / 30 kW input at 95% | ≈ 28.5 kW | 10 L/min | 0 | 0 | 0 | 0 | ≈ 0.930222 × | ≈ 0.95 × | ≈ 4.65111 kWh | ≈ $0.93 |
| Winter inlet / 18 kW input at 100% | 18 kW | ≈ 6.45007 L/min | 5 | 0 | 0 | 5 | ≈ 1.47285 × | ≈ 0.95 × | Unavailable: unmet demand | Unavailable: unmet demand |
| Summer inlet / 30 kW input at 95% | ≈ 28.5 kW | 10 L/min | 0 | 0 | 0 | 0 | ≈ 0.636468 × | ≈ 0.866667 × | ≈ 3.18234 kWh | ≈ $0.64 |
| Summer inlet / 18 kW input at 100% | 18 kW | ≈ 8.6001 L/min | 5 | 0 | 0 | 5 | ≈ 1.00774 × | ≈ 0.866667 × | Unavailable: unmet demand | Unavailable: unmet demand |
Unmet minutes count the union of failing intervals, so do not add the three diagnostic durations. Equality meets a numerical limit. Energy and cost are shown only when the entire demand can be served under these assumptions. No standby, startup, cycling, pipe loss or installation cost is included.
Ideal flow capacity versus temperature rise
30 kW input at 95%: constant useful output with the entered maximum-flow cap. The selected rise is 40 Δ °C. This is an ideal curve, not a manufacturer performance curve. A capacity below minimum activation leaves no operating flow range in this model.
Filled markers reach the minimum activation flow; hollow markers do not. The larger marker and vertical line identify the selected rise. Minimum activation: ≈ 0.5 L/min.
| Temperature rise | Uncapped thermal limit | Capped available flow | Activation range possible | Selected rise |
|---|---|---|---|---|
| 1 Δ °C | ≈ 408.505 L/min | 10 L/min | Yes | |
| 5 Δ °C | ≈ 81.7009 L/min | 10 L/min | Yes | |
| 10 Δ °C | ≈ 40.8505 L/min | 10 L/min | Yes | |
| 15 Δ °C | ≈ 27.2336 L/min | 10 L/min | Yes | |
| 20 Δ °C | ≈ 20.4252 L/min | 10 L/min | Yes | |
| 25 Δ °C | ≈ 16.3402 L/min | 10 L/min | Yes | |
| 30 Δ °C | ≈ 13.6168 L/min | 10 L/min | Yes | |
| 35 Δ °C | ≈ 11.6716 L/min | 10 L/min | Yes | |
| 40 Δ °C | ≈ 10.2126 L/min | 10 L/min | Yes | Selected |
| 45 Δ °C | ≈ 9.07788 L/min | ≈ 9.07788 L/min | Yes | |
| 50 Δ °C | ≈ 8.17009 L/min | ≈ 8.17009 L/min | Yes | |
| 55 Δ °C | ≈ 7.42736 L/min | ≈ 7.42736 L/min | Yes | |
| 60 Δ °C | ≈ 6.80841 L/min | ≈ 6.80841 L/min | Yes | |
| 65 Δ °C | ≈ 6.28469 L/min | ≈ 6.28469 L/min | Yes | |
| 70 Δ °C | ≈ 5.83578 L/min | ≈ 5.83578 L/min | Yes | |
| 75 Δ °C | ≈ 5.44673 L/min | ≈ 5.44673 L/min | Yes | |
| 80 Δ °C | ≈ 5.10631 L/min | ≈ 5.10631 L/min | Yes |
Fixture mixing ledger — Winter inlet
| Fixture | Hot fraction | Heater flow | Cold bypass | Heat rate | Mixed volume | Hot volume | Cold volume | Useful energy |
|---|---|---|---|---|---|---|---|---|
| Kitchen | ≈ 0.875 | ≈ 3.5 L/min | ≈ 0.5 L/min | ≈ 9.76733 kW | 40 L | 35 L | 5 L | ≈ 1.62789 kWh |
| Shower | ≈ 0.75 | 6 L/min | 2 L/min | ≈ 16.744 kW | 80 L | 60 L | 20 L | ≈ 2.79067 kWh |
Water assumption: 1 kg/L and 4.186 kJ/(kg·K), with instantaneous mixing. Hot volume plus bypass volume equals mixed volume. Heating is calculated from the fixture target and inlet temperature. Manufacturer curves, supply capacity, pressure, scaling, recirculation, temperature safety and installation requirements need separate assessment.
How to use this calculator
- Choose Overlapping fixtures example or Staggered fixtures example. Select Celsius/Fahrenheit and litres/US gallons, then enter the authored window duration and heater setpoint.
- Enter one to three inlet-temperature cases based on measured or deliberately assumed conditions. Every fixture target must be at least as warm as every inlet and no warmer than the heater setpoint.
- Enter each fixture’s mixed flow, target temperature and start/end minutes. Add intervals for repeated uses. Overlap is summed; end times are excluded.
- Enter candidate rated input power, steady heat-conversion efficiency, minimum activation flow, maximum heater flow and compatible input-energy tariff. Do not substitute a seasonal UEF rating for the modeled efficiency.
- Choose inlet and candidate detail. Inspect the stepwise demand chart, every unmet reason, full seasonal comparison and ideal flow-capacity curve. Staggering can reduce a peak without changing total water volume.
- Review the interval and fixture ledgers and download or copy exact CSV. Confirm manufacturer curves, supply capacity, pressure, temperature safety and installation requirements separately.
The Formula
The mathematical logic powering this calculation is:
For each inlet case, heater setpoint Th is above inlet Ti. A fixture mixed target Td is between Ti and Th. Hot fraction = (Td − Ti)/(Th − Ti); heater flow = mixed fixture flow × hot fraction; cold bypass = mixed flow − heater flow. Mixed fixture flow is not the same as the flow through the heater. Equal target/inlet temperature requires no heating.
Assume water density 1 kg/L and specific heat 4.186 kJ/(kg·K). Required useful kW = mixed flow in L/min × 4.186 × (Td − Ti)/60, equivalently heater flow × 4.186 × (Th − Ti)/60. Draw volume = flow × duration minutes. Useful thermal kWh = kW × minutes/60. No storage, recirculation, pipe losses, standby, startup delay or cycling is modeled.
Fixture intervals include their start and exclude their end. Partition the authored window at every start and end, sum all simultaneous demands and retain idle gaps. Two touching intervals are not concurrent. Exact per-draw and interval totals reconcile. Inlet cases are evaluated separately and are not weighted into an annual forecast.
Candidate useful output = rated input kW × steady conversion efficiency/100. Thermal-limited heater flow = useful kW ×60/(4.186 × heater temperature rise). Ideal available heater flow is the smaller of that thermal limit and the entered maximum flow. The ideal curve includes 1°C rise, every 5°C through 80°C and the selected exact rise. It is not a manufacturer performance curve.
A positive-heating interval is unmet if heater flow is below minimum activation, above maximum flow, or required useful kW exceeds useful output. Equality meets a numerical limit. Multiple reasons can apply to the same interval; total unmet minutes count their union. Cold-only fixture flow is idle for heating. Within entered limits does not establish equipment suitability.
Only when the entire window has no unmet interval: modeled input kWh = required thermal kWh / conversion efficiency fraction; cost = input kWh × entered USD/input-kWh tariff. Unmet profiles have null input energy and cost rather than a partial bill. Tariffs for different energy sources must be expressed on a comparable input-kWh basis. Cost excludes installation, taxes and other charges.
Unit conversion uses 1 US gallon = 3.785411784 litres and °F = 1.8 × °C +32. Temperature differences convert by the scale alone, without the offset. All related drafts convert atomically; incomplete or unrepresentable converted fields leave the original draft intact. Canonical model/CSV results use Celsius, litres, L/min, minutes, kW, kWh and USD.
Bounds: authored duration greater than zero through 1440 minutes; heater setpoint greater than zero through 80°C and above all inlets; inlet 0–40°C; fixture mixed flow greater than zero through 100 L/min, with target between every inlet and setpoint; candidate input greater than zero through 1000 kW; efficiency greater than zero through 100%; minimum heater flow 0–100 L/min and maximum greater than zero through 100 L/min, at least the minimum; tariff 0–100 USD/input-kWh. Up to three inlet cases, 24 fixtures and three candidates. Numeric drafts accept six decimal places and 12 significant digits or exact fractions with numerator/denominator up to 32 digits. Invalid inputs suppress dependent results and exports.Method sources
Worked Example
If you input:
- Window and temperatures: 30 minutes; heater setpoint 50°C; winter inlet 10°C and summer 20°C.
- Fixture schedule: Shower 8 L/min at 40°C from minute 0 through 10 (end excluded); kitchen 4 L/min at 45°C from 5 through 15.
- Candidates: 30 kW input at 95% conversion and18 kW at 100%; both minimum 0.5 and maximum 10 L/min, tariff $0.20 per input kWh.
Result:
Both inlet cases use 120 litres of mixed fixture water. Winter requires 95 litres through the heater and 39,767/9,000 ≈ 4.41856 kWh of useful heat. Peak simultaneous mixed flow is 12 L/min, heater flow 9.5 L/min and useful heat 26.5113 kW. The 30 kW/95% candidate supplies 28.5 kW and meets all entered limits, using 2,093/450 ≈ 4.65111 input kWh at a modeled cost of 2,093/2,250 ≈ $0.930222. The 18 kW candidate is unmet for the 5-minute overlap, so no partial input-energy bill is shown. Summer requires 260/3 ≈ 86.6667 hot litres and 27,209/9,000 ≈ 3.02322 useful kWh. Staggering the kitchen to minutes 10–20 keeps winter volume and energy unchanged but lowers peak useful heat to 16.744 kW, within both candidates’ entered limits.
Frequently Asked Questions
Is this a tankless heater GPM sizing calculator?
It includes exact US-gallon-per-minute input and output, but evaluates mixed fixture flow, hot fraction, temperature rise and simultaneous use together. A heater flow rating must be interpreted at its specified rise and conditions. This model does not select a standard unit or replace the manufacturer’s sizing data.
Why is mixed fixture flow higher than heater flow?
A fixture target below the heater setpoint blends hot water with cold bypass water. The hot fraction depends on both inlet and target temperatures. Enter total mixed flow at the fixture; the model computes the portion passing through the heater. At target equal to setpoint all fixture flow is heated.
Does raising the setpoint reduce the required heat?
For the same inlet, mixed target and mixed fixture flow, the ideal required heat is unchanged. A higher heater setpoint reduces the hot fraction while increasing the rise of that hot stream. It can affect flow and activation constraints. The calculation is not a recommendation to change temperature settings.
Can a larger heater still show unmet demand?
Yes. A low hot-flow interval can fall below minimum activation even when useful power is ample, or required heater flow can exceed the entered hydraulic maximum. The diagnostic ledger separates these flags and counts overlapping problem durations only once.
Why is the energy bill unavailable for an unmet candidate?
This model does not simulate delivered temperature, demand curtailment or dynamic behavior after a limit is exceeded. Quoting a partial energy bill could make a candidate that cannot meet the planned demand appear cheaper. Input energy and cost are shown only for a fully supported window under the stated assumptions.
Does staggered use save energy?
For unchanged fixture temperatures, durations and flows, this ideal model has the same water and thermal energy totals. Staggering can reduce simultaneous peak power or flow. Real startup, standby and cycling effects are outside this model, so it does not claim real-world energy savings from scheduling alone.
Can I use UEF as conversion efficiency?
UEF reflects test-cycle performance and is not the same quantity as the constant steady heat-conversion efficiency used here. Obtain compatible data for your candidate. Manufacturer output curves, minimum firing behavior, service capacity and operating conditions may materially affect suitability.
Does this include installation cost or annual savings?
No. Cost covers the explicitly authored demand window and entered input-energy tariff only. No annual repetition, climate distribution, installation prices, incentives, taxes, standby, pipe losses or recirculation are assumed. Use separate project budgeting and verified product data for those decisions.
Similar Calculators
Pipe Pressure Drop Calculator
Compare pipe pressure loss across inside diameters. Calculate Darcy friction, fitting losses, velocity and Reynolds number with explicit transition limits.
Bathroom Remodel Cost & Quote Calculator
Compare bathroom remodeling quotes, allowances, changes and missing scope. Plan contingency and contractor payments with a cash timeline, exact tables and CSV.
Electricity Cost Calculator
Estimate appliance electricity cost from wattage, daily use, electricity rate, and billing fees.