Sump Pump Cycle & Storage Calculator
Use the measured effective basin area and switch band, or enter the usable volume directly. Compare two pumps at documented discharge rates under the same inflow. Count starts during an observation window and see whether each enters a repeating cycle.
Compare pump cycles in one sump
Compare fill and pump-down times, start counts and the active storage implied by each entered limit.
Edit basin, flows and start limits
Use a documented usable band and flows at the same operating conditions. The observation begins with the pump off at the lower switch.
Only pump A meets its entered start-rate limit while cycling.
Active basin storage
- Usable storage between switches
- 10 L
- Observation from the lower switch
- 150 s
Pump A · 20 L/min
30 starts/h
Meets the entered start-rate limit.
- Starts in observation window
- 1
- Entered maximum
- 30 starts/h
- Pump-off fill time
- 60 s
- Pump-on drawdown time
- 60 s
- Repeating cycle time
- 120 s
Pump B · 30 L/min
40 starts/h
Exceeds the entered start-rate limit.
- Starts in observation window
- 2
- Entered maximum
- 30 starts/h
- Pump-off fill time
- 60 s
- Pump-on drawdown time
- 30 s
- Repeating cycle time
- 90 s
Inspect the cycle trace and storage check
Active volume over time
Liters above the lower switch
Volume axis 0 L to 10 L
Solid fill, dashed pump-on phase, dotted upper switch. Rings mark starts.
Pump B · storage at entered limit
- Net pump-down flow
- 20 L/min
- First start from lower switch
- 60 s
- Minimum usable storage
- 13.33333333 L
- Additional usable storage
- 3.33333333 L
- Minimum band at this area
- 26.66666667 mm
Exceeds the entered start-rate limit.
Review the exact pump-cycle ledger
Exact fractions preserve the rate and limit comparison before display rounding.
| Pump | Net drawdown (L/min) | Fill (s) | Pump-down (s) | Cycle (s) | Steady starts/h | Observed starts | Minimum storage (L) | Minimum band (mm) |
|---|---|---|---|---|---|---|---|---|
| A | 10 | 60 | 60 | 120 | 30 | 1 | 10 | 20 |
| B | 20 | 60 | 30 | 90 | 40 | 2 | 40/3 | 80/3 |
How to use this calculator
- Choose area and band or measured usable liters. Use only the volume between your documented switch levels.
- Enter a steady inflow and both discharge values for the same chosen hydraulic conditions.
- Enter each documented starts-per-hour limit and your observation length. Compare cycle timings and starts before the endpoint.
- Inspect the level trace or storage comparison, then export the exact ledger.
The Formula
The mathematical logic powering this calculation is:
Usable volume V is the liquid volume between the pump-stop and pump-start levels. Enter it directly or multiply the effective area in square meters by the measured vertical switch band in millimeters. One square meter times one millimeter equals one liter. Use the band's effective horizontal area after accounting for displaced volume. For a basin with varying section, use a measured usable volume or an average area for that band.
At constant inflow I and discharge P in liters per minute, when 0 < I < P, pump-off fill time is 60V/I seconds and pump-on drawdown time is 60V/(P − I) seconds. One start occurs in each repeating cycle. Divide 3,600 by the cycle seconds to find steady starts per hour. It meets the entered limit S when the rate is at most S. At this same inflow and discharge, minimum usable storage for that one limit is 60I(P − I)/(PS) liters. Divide by the area in area mode to find the implied switch band in millimeters.
The observation starts at the lower switch with the pump off. If the observation ends before the first fill, the start count is zero. Otherwise count the first start and each whole cycle after it through the endpoint. A start exactly at the observation endpoint counts. If pump discharge equals positive inflow, the volume stays at the upper switch once it starts. If discharge is lower, the modeled volume continues to rise. Neither case has a repeating cycle or a storage solution for cycling. Zero inflow produces zero starts from the stated initial condition.
Enter positive direct volume from 0.000001–1,000,000 L, area from 0.000001–1,000 m², switch band from 0.000001–1,000 mm, flow from 0–10,000 L/min, an entered positive maximum from 0.000001–3,600 starts/hour, and an observation window from 0.000001–86,400 seconds. Inputs support six decimals. The trace shows through the observation endpoint or the end of two cycles, whichever comes first. It models relative volume above the lower switch and does not infer basin capacity, overflow, variable inflow or discharge, control delays, pump suitability or allowable switch settings.Worked Example
If you input:
- Usable storage: Effective 0.5 m² area × 20 mm band = 10 L
- Flow and limits: 10 L/min inflow, A 20 L/min, B 30 L/min, each limited to 30 starts/hour
- Observation: 150 seconds from lower switch with pump off
Result:
A has 60 seconds off and 60 seconds on, exactly 30 starts/hour, with one observed start. B has 60 seconds off and 30 seconds on, 40 starts/hour, with two observed starts. B needs 13⅓ L at the entered rate limit and its second start occurs exactly at 150 seconds.
Frequently Asked Questions
Why subtract inflow from discharge?
Water continues entering during operation. The basin only falls at the difference between the two rates.
Why is the observation count different from starts per hour?
The observation counts individual events from the stated lower-switch start. The steady rate describes a repeated cycle and can be fractional.
What if inflow matches the pump?
The initial fill can reach the upper switch. Once running, the pump balances inflow and has no modeled return to the lower switch.
Can I use a measured volume for a tapered basin?
Yes. Enter the measured volume between the switch levels directly.
Does the minimum band establish equipment limits?
It is the geometric band that meets the entered starts-per-hour comparison at the entered rates. Use the supplier’s limits and project conditions to evaluate an actual installation.
Why can the volume go over the upper switch in the plot?
The upper switch marks when the pump starts. When inflow is higher than discharge, modeled volume continues to rise after that point.
Similar Calculators
Pump Flow per Hour Calculator
Pump Flow per Hour for the exact fields in this tool, with clear inputs and an immediate result for planning or comparison.
Well Pressure Tank Size & Pump Cycle Calculator
Compare well pressure tanks by usable drawdown, zero-demand refill time and starts per hour. See which tank count meets entered pump targets.
Sloped-Bottom Tank Volume & Stage Calculator
Calculate liquid volume at two measured levels in a rectangular tank or trough with two sloping floor runs. See wetted lengths and compare against an entered minimum.