Rectangular Duct Weight & Module Calculator

Compare two documented rectangular duct builds on the same straight run. Work from shell area, lining mass and fixed extra mass per module, then solve the smallest equal-module count that fits the stated mass and blank length. Inspect nearby counts to see the effect of repeated ends.

Measured sheet-metal inventory

Compare rectangular duct module weight

Edit duct dimensions, limits and builds
Build A
Build B

Only Build A meets the entered module limits.

Limits of 24 kg per module and 3 modules

Build A

Meets entered limits

3 modules

Mass sets the longest module

24 kg each · 72 kg total · 2,000 mm body per module

Build B

Exceeds module count cap

4 modules

Blank length sets the longest module

16.5 kg each · 66 kg total · 1,500 mm body per module

Inspect the equal-module layout

Equal modules along the body run

Build A · 3 modules

0 mm6,000 mm

Mass per module

Dashed cap 24 kg

  • Body and lining
  • Fixed extra per module

3 modules · Within entered limits

Body length 2,000 mm each

Blank required 2,050 mm · within length

Module mass 24 kg · within cap

Within the maximum count

72 kg total · 6 kg repeated fixed mass

Review the exact duct mass ledger
Exact module counts, dimensions and mass
BuildModulesBody (mm)Blank (mm)Module mass (kg)Repeated extras (kg)Run total (kg)Within limits
A23000305035470No
A32000205024672Yes
A41500155037/2874No
B320002050201860No
B41500155033/22466No
B51200125072/53072No

How to use this calculator

  1. Enter the straight-run body length and documented rectangular shell dimensions.
  2. Enter the maximum recorded mass per module and module count for this comparison.
  3. Enter each documented shell sheet mass, longitudinal seam allowance, added linear mass and fixed extra mass per assembled module.
  4. Enter the axial blank length and end allowance. Compare the minimum equal module count and inspect a neighboring scenario.
  5. Review the exact dimensions and mass ledger and download both builds.

The Formula

The mathematical logic powering this calculation is:

For measured width W and height H, use the developed shell width 2(W + H) plus the entered total longitudinal seam allowance. Convert that width from mm to metres and multiply by the documented sheet mass in kg/m² to obtain shell mass per metre. Add the entered linear lining and other mass in kg/m. Use these dimensions and product data for the same shell basis. The fixed mass per module includes the full collection of repeated attachments and material counted separately from the linear values.
For body run D split into n equal modules, each body is D/n mm. Axial blank length required equals body length plus twice the entered allowance per end. Module mass equals linear kg/m × body length in metres plus fixed extra mass. Full run mass is linear mass per metre × D in metres plus n times the fixed mass. Enter the repeated end mass separately from blank length allowances; the worksheet does not infer mass from an end allowance.
Maximum positive body length from the mass cap is (cap − fixed mass) ÷ linear kg/m, converted to mm. Maximum from stock is available blank minus twice the end allowance. If either maximum is nonpositive, no positive equal module fits. Otherwise, minimum count is the ceiling of D divided by the smaller maximum. Equality qualifies for all entered limits, including the maximum module count. The interactive comparison covers the limiting count, its neighbors and the entered count cap. All calculations and exported fractions use exact decimal arithmetic.
Dimensions and masses support up to 1,000,000 in their stated units, with up to three decimals. The count limit is 1–999,999. Inputs describe one straight, constant rectangular section. Pressure class, gauge selection, reinforcement, equipment and lifting requirements rely on their own documentation.

Worked Example

If you input:

  • Run: 6,000 mm long with a 500 × 250 mm rectangular shell
  • Limits: 24 kg per module, at most 3 modules
  • Build A: 6 kg/m² shell and 2 kg/m lining, 2 kg fixed per module, 2,550 mm blank length
  • Build B: 4 kg/m² shell and 1 kg/m lining, 6 kg fixed per module, 1,550 mm blank length

Result:

Build A needs three 2,000 mm modules at exactly 24 kg each, for 72 kg total. The available blank length means Build B needs four modules, at 16.5 kg each and 66 kg total. A 23.999 kg maximum moves Build A to four modules and 74 kg total, beyond the entered count cap.

Frequently Asked Questions

Why can more modules make the run heavier?

The body and lining mass over the same distance stay constant. Fixed end or attachment mass is counted once for each additional module.

What if a fixed assembly alone uses the entire mass limit?

Any positive body length adds positive sheet mass. The worksheet therefore reports no positive length within the cap.

What if my sheet mass already includes seam material?

Use a common input basis. Added longitudinal seam width is for sheet area omitted from the bare rectangular circumference. Fixed extras and lining are quantities outside the entered sheet mass.

Does the required number of modules make the installation suitable?

It satisfies only the entered geometric and mass limits in the worksheet. Fabrication, supports, clearances, allowable material and handling procedures have separate requirements.