Rectangular Duct Offset & Clearance Calculator

Test two possible jog locations for the same rectangular duct envelope in one elevation view. Enter the measured horizontal extent, the proposed final center offset, and the clear vertical space over each constrained section. Compare the tightest margins, then see the full range of final offsets each layout can accommodate.

Measured duct clearance

Compare rectangular duct offsets

Edit span, jogs and clearance windows

One start x, end x, lower elevation, upper elevation entry per line.

Layout A
Layout B

Only Layout A fits the entered clearance windows.

Final offset +150 mm · 10 mm vertical reserve per side

Layout A

Within all windows

0 mm

Tightest vertical margin after reserve

Jog through 200 to 800 mm · 14.036°

Allowed final offset +146.666667 to +150 mm

Layout B

Misses entered clearance

-40 mm

Tightest vertical margin after reserve

Jog through 100 to 600 mm · 16.699°

No common final offset

Inspect the duct and clearance windows

Duct side elevation

Layout A · elevation in mm

  • Duct envelope
  • With vertical reserve
  • Selected window

Window 1 · 300 to 400 mm

Clear elevation -40 to +110 mm

Centerline endpoints +25 to +50 mm

Lower margin after reserve
+5 mm
Upper margin after reserve
0 mm
Review the exact clearance ledger
Exact window endpoints and margins
LayoutWindowCenterline start (mm)Centerline end (mm)Lower margin (mm)Upper margin (mm)Within window
A1255050Yes
A2225/2275/25/225/2Yes
B1609040-40No
B2150150400Yes

How to use this calculator

  1. Choose a common side-elevation origin with the incoming centerline at zero. Enter the span, signed final offset, documented vertical envelope and desired vertical reserve.
  2. Enter the start and horizontal run of the jog for two layouts.
  3. Enter one clearance window per line as start x, end x, lower elevation, upper elevation in millimeters. Include every relevant interval along the modeled plane.
  4. Compare clearance margins and inverse offset ranges. Use the profile controls to inspect the selected window’s two endpoints.
  5. Export the exact measurements, margins and comparison results.

The Formula

The mathematical logic powering this calculation is:

Use one side-elevation datum. The initial centerline is y = 0. Let a be the horizontal jog start and b its positive horizontal run. For a station x, progress t = clamp((x − a)/b, 0, 1), and center elevation is tD for a final signed offset D. The layout has no in-span jog when a + b exceeds the available span. The plotted side envelope has a constant documented vertical height H. Its evaluated half-height including reserve is h = H/2 + reserve per side. Use the vertical envelope on the drawing rather than a height measured perpendicular to the slope.
Each clearance window applies over an entered closed horizontal interval with lower and upper elevations L and U. Centerline elevation is monotone across the jog, so the minimum and maximum occur at the window endpoints. Lower margin = min(t_start D, t_end D) − (L + h). Upper margin = (U − h) − max(t_start D, t_end D). A layout fits when every margin is nonnegative. Equality fits. Margins include the entered reserve.
To solve the allowable final offset, intersect [−100,000, 100,000] mm with (L + h)/t ≤ D ≤ (U − h)/t at every endpoint with positive progress. At zero progress, require 0 within [L + h, U − h] for any final offset to work. Crossed bounds or a blocked zero-progress station give no allowable offset. Displayed angle is arctan(D/b); exact rational values govern margins and comparisons.
Enter 1–8 windows, with zero-width intervals supported for single stations. Horizontal bounds must be between zero and the entered span. Elevation bounds and the final offset may be signed. Dimensions accept up to three decimals. Span, height and jog run are positive up to 100,000 mm. The model compares the stated envelope in one plane and at the entered windows. Turning radius, joint geometry, material fit, pressure loss, insulation and installation depend on separate documents.

Worked Example

If you input:

  • Duct and site: 1,000 mm span, +150 mm final offset, 100 mm vertical envelope, 10 mm reserve per side
  • Jogs: A starts at 200 mm and runs 600 mm. B starts at 100 mm and runs 500 mm.
  • Windows: x = 300–400 mm with y = −40 to 110 mm, and x = 650–750 mm with y = 50–210 mm

Result:

A reaches the upper boundary of Window 1 exactly and has an allowable final offset from 146⅔ to 150 mm. B exceeds the upper clearance by 40 mm and has no common allowable offset. Lowering the first window’s upper edge to 109.999 mm leaves neither layout fitting the entered offset.

Frequently Asked Questions

Which duct dimension does the envelope field use?

Use the documented vertical outside envelope through the layout shown in side elevation. The modeled height stays constant vertically along the path.

What does a negative margin mean?

It is the additional vertical space needed at that side of the limiting window for this entered offset and reserve.

What if the allowed final-offset range is empty?

The entered windows conflict for that jog start and run, or the fixed incoming center already misses a window. The comparison assumes the same initial datum.

Do the endpoints capture the worst clearance?

Yes for the modeled monotone centerline, constant height and constant window bounds. Divide the area into more windows when the bounds change.