LED Strip Power Supply & Distributed Voltage Drop Calculator
Use a documented nominal current or power per unit length and separate feed-lead and strip loop resistance. Trace voltage along one low-voltage strip, compare where the modeled minimum occurs, and audit your entered limits.
Compare LED strip load and local voltage
Trace local voltage along one low-voltage strip using the entered nominal load and loop resistance.
Only the two-end profile meets the entered limits.
Nominal source draw 3.6 A · 86.4 W.
Entered output limit minus load 33.6 W.
One-end feed
22.2 V
Lowest at 16 ft from the first end.
Voltage minus floor -0.8 V.
Lead drop 0.36 V · strip drop 1.44 V at that position.
Entered length limit minus length 4 ft.
Outside at least one entered limit.
Equal two-end feeds
23.46 V
Lowest at 8 ft from the first end.
Voltage minus floor 0.46 V.
Lead drop 0.18 V · strip drop 0.36 V at that position.
Entered length limit minus length 4 ft.
Meets entered limits.
Local voltage from end to end
At 8 ft from the first end.
- One-end feed 22.56 V
- Equal two-end feeds 23.46 V
Nominal power and modeled resistive loss
Edit strip and loop measurements
Use one length unit, and enter resistances for both conductors together. In the two-end model the lead loops have equal resistance.
Edit voltage, power and documented limits
Copy the limits you want to compare. Leave a documented length limit blank if you have no applicable value for that arrangement.
Review exact strip voltage and power calculations
Nominal strip current 9/40 A/ft × 16 ft = 18/5 A.
One-end feed
Feed terminal 591/25 V · lowest 111/5 V.
Lead loss 162/125 W · strip loss 432/125 W.
Modeled local loads 10206/125 W.
Equal two-end feeds
Feed terminal 1191/50 V · lowest 1173/50 V.
Lead loss 81/125 W · strip loss 108/125 W.
Modeled local loads 10611/125 W.
Show LED strip CSV text
How to use this calculator
- Choose feet or meters. Enter the strip length, nominal supply voltage and documented draw per unit.
- Enter the lead loop and strip loop resistances separately.
- Copy your minimum local voltage, continuous source output and any applicable documented length limits.
- Inspect local volts along the strip and compare the nominal power and modeled resistive losses.
- Download the exact run comparison.
The Formula
The mathematical logic powering this calculation is:
Enter one consistent length basis in feet or meters. Let strip length be L, the source voltage be V₀, and the nominal current per length be j. If the input is nominal power per length, divide it by V₀ to obtain j. Modeled source current is jL and nominal source power is V₀jL.
Use the combined resistance of supply and return for a strip-length unit r and the combined resistance of one feed lead loop R. With one end supplied, the lead drop is jLR. At distance x from that feed, strip drop is rj(Lx − x²/2). Voltage is V₀ minus the lead and strip drops. The lowest voltage occurs at the far end, where strip drop is rjL²/2.
The symmetric two-end model uses one common ideal source, identical lead loops on both ends and the same strip. Each feed carries half the modeled load, giving a lead drop jLR/2. Strip drop at x is rj x(L − x)/2. The minimum is at the center, where strip drop is rjL²/8.
Lead resistive loss is I²R for one feed and I²R/2 for equal feeds. Integrating squared strip current over both traces gives rj²L³/3 for one feed and rj²L³/12 for equal feeds. Subtract both losses from nominal source power for the power reaching the modeled local loads. The model uses exact fractions for all entered limits and inspection positions.
This is a uniformly distributed fixed-current approximation at the nominal operating point. The minimum voltage can change as the strip's actual load changes with local voltage, brightness setting and temperature. A nonpositive modeled minimum leaves the profile unavailable. Optional entered length limits come from the documentation for that arrangement. The worksheet compares entered limits. It does not model brightness, thermal or connection limits, wire sizing, mains wiring or installation.Worked Example
If you input:
- Nominal strip: 16 ft at 24 V and 0.225 A/ft
- Illustrative loop data: 0.10 Ω per lead loop and 0.05 Ω/ft on the strip
- Illustrative limits: 23 V minimum and 120 W source output
Result:
The modeled nominal source draw is 3.6 A and 86.4 W. The one-end profile reaches 22.2 V at the end. The symmetric profile reaches 23.46 V at the center. The entered 23 V floor is met only by the latter.
Frequently Asked Questions
Does the loop resistance include both conductors?
Yes. Enter the sum of the supply and return resistances. Each modeled lead loop in the equal two-end case uses the same entered value.
Why do the two arrangements draw the same source current?
The model uses the same fixed nominal current density and strip length. Splitting the feed changes which lead and strip segments carry the current.
Why can the distant end and center have different drops?
The current in each strip segment depends on the total load it supplies. In the symmetric profile, the highest drop is at the point farthest from both equal feed terminals.
What if the datasheet lists both amps and watts per foot?
Choose the published basis you want to compare. Quoted nominal values can be rounded independently, so both inputs are retained separately.
How does the calculator handle a model value at or below zero?
That result is outside the fixed-current approximation. The source load and entered limits remain visible and the voltage curve is omitted.
Similar Calculators
DC Voltage Drop & Cable Loss Calculator
Compare DC cable voltage drop, power losses and load limits with separate conductor lengths, connection resistance, constant-power loads and visual sweeps.
LED Resistor Quick Calculator
Calculate a safe current-limiting resistor and power rating for a single LED.
Power Calculator
Calculate electrical power in watts from voltage and current, or find current from power and voltage.
Battery Runtime Calculator & Duty Cycle Planner
Compare steady and repeating load profiles. Estimate battery runtime from amp-hours, inverter loads, reserve charge and an optional discharge-rate correction.