Geothermal Thermal Response Test Calculator

Paste the elapsed hours, entering and leaving fluid temperatures, and recorded heat input for one borehole test. Fit two intervals of the trace against logarithmic elapsed time to see how the selected start changes effective ground conductivity and the measured power spread.

Measured borehole response

Which observations change the geothermal fit?

Both windows meet the entered power spread limit.
Window A · Effective conductivity
1.124 W/(m·K)
8 readings · 3.41% power spread
Window B · Effective conductivity
1.481 W/(m·K)
5 readings · 0.98% power spread

Window B changes the estimate by +31.8% relative to A.

Mean fluid temperature and fit windows

Window A uses 8 samples and Window B uses 5. Elapsed time is on a logarithmic axis.

  • Measured
  • Window A
  • Window B
Fit windows and measured trace

One row per reading with elapsed hours, entering °C, leaving °C, and heat input in watts. Separate columns with commas or tabs.

Review observation ledger and CSV
Measured temperatures, power and fit residuals
HoursEntering °CLeaving °CMean °CHeat input WA residual KB residual K
618.717.518.14,200-0.141515Outside window
1220.819.620.24,120-0.056513Outside window
1822.1820.9821.584,1000.144788Outside window
2423.1521.9522.554,0600.278488-0.000318
3023.6422.4423.044,1000.1198030.000024
3624.0422.8423.444,080-0.01021-0.000055
4224.3823.1823.784,080-0.1183310.001682
4824.6723.4724.074,100-0.21651-0.001334

How to use this calculator

  1. Paste one row per observation. Enter elapsed hours, entering °C, leaving °C and measured heat input in watts, separated by commas or tabs.
  2. Enter the active bore length, the first hour of each fit and their common end. Set a power spread limit from the method used for your test.
  3. Compare the two conductivity fits. Switch from the temperature trace to residuals to inspect the effect of including earlier observations.
  4. Open the observation ledger or download both fits and their underlying rows as CSV.

The Formula

The mathematical logic powering this calculation is:

For each row, the mean fluid temperature T is (entering + leaving)/2. For each fitted window, keep samples within its entered start and shared end, with endpoints included. Compute x = ln(t/t₀), where t is the elapsed time and t₀ is the first included time. Shifting the log-time reference leaves the fitted slope unchanged.

Fit T to a straight line by unweighted least squares. The slope m is the sum of centered x × centered T divided by the sum of centered x². Use the arithmetic mean of the included recorded heat input P and the active bore length L in k = P/(4πLm), reported as effective thermal conductivity in W/(m·K). A flat or descending temperature fit leaves conductivity unavailable. Compare the two available k estimates using (k_B/k_A − 1) × 100%.

Power spread is 100 × (largest − smallest included W) / mean included W. It describes the sample range, with every recorded row equally weighted. The worksheet compares this value with the caller's entered limit. It always shows the observed residuals, RMSE and R² where defined. A flat series has undefined R². Each residual is observed minus fitted mean fluid temperature and RMSE divides the sum of their squares by the included sample count.

The line-source fit assumes a suitable later period of positive, approximately steady heat injection. Review the trace and residuals along with the reported spread. A small residual and power range alone cannot establish that a period satisfies the model. Time spacing, ambient and equipment effects and how heat input was measured all matter. Conductivity is one input to a separate loopfield design. The worksheet estimates no loop length or number of bores.

Enter 3 to 200 rows with unique times in 0.001–2,000 h, temperatures from −50 to 150 °C, and positive heat input of 0.001–1,000,000 W. Bore length is 0.1–2,000 m, power limit 0–200%, and decimal precision up to six places. Windows must each contain at least three measured times. The CSV preserves up to twelve significant digits for numeric results.

Worked Example

If you input:

  • Active bore length: 100 m
  • Window A: 6 through 48 hours
  • Window B: 24 through 48 hours
  • Samples: Eight recorded temperature and power rows, with an illustrative 5% power spread limit

Result:

Window A estimates 1.124 W/(m·K) and Window B estimates 1.481 W/(m·K), an increase of 31.80%. Their measured power spreads are 3.41% and 0.98%.

Frequently Asked Questions

Why use logarithmic elapsed time?

In the late-time infinite line-source approximation with steady heat input, mean circulating fluid temperature is linear in ln(elapsed time). The slope links heat input per metre to effective thermal conductivity.

What can a later starting point tell me?

It shows how much earlier samples influenced the slope, conductivity estimate and residuals. Inspect the sample count and the remaining time span before interpreting either result.

How is the power limit applied?

Each window's maximum minus minimum recorded power is divided by its arithmetic mean. The selected limit is compared with that percentage. The limit and calculation purpose are set by the user.

Can I use this to determine loop length?

The calculator estimates conductivity from a measured test. Loop design also needs loads, ground and borehole properties, system limits and design assumptions.