Fuse Rating & Time-Current Fit Calculator
Compare documented AC or DC limits for two fuse candidates. Enter published minimum melting and maximum clearing points, then check a constant-current pulse or an overload clearing deadline. The log-log chart marks comparable data, missing limits and currents outside the entered curve. Interruption rating is a separate comparison.
Compare documented fuse limits
Check entered ratings and time-current boundaries for two candidates using comparable datasheet conditions.
Edit circuit, fuse data and events
Use documented ratings and time bounds for the same test conditions. Leave unconfirmed ratings blank.
Edit Fuse A ratings and curve
Enter increasing current points. Keep a bound blank at any row where it is unconfirmed.
Edit Fuse B ratings and curve
Enter increasing current points. Keep a bound blank at any row where it is unconfirmed.
Constant-current event checks
Startup pulse
Required overload clearing
Outside chart
At minimum melt
At maximum clearing
Circuit scope and interruption ratings
DC · 24 V maximum circuit voltage · 1,200 A available fault current
Fuse A · DC
- Voltage · 32 V
- Within entered rating
- Interruption · 2,000 A
- Within entered rating
Fuse B · DC
- Voltage · 32 V
- Within entered rating
- Interruption · 1,000 A
- Below entered requirement
Time-current curve comparison
Time (s)
Current (A)
- Minimum melting
- Maximum clearing
- Pulse
- Clearing deadline
Event and datasheet ledger
Each event checks one bound. “Estimated” means an interpolation between adjacent entered points.
Startup pulse
Pulse duration · 12 A · 0.5 s
- Fuse A
- Outside entered time bound
- 0.44444444 s · Estimated bound
- Fuse B
- Within entered time bound
- 0.88888889 s · Estimated bound
Required overload clearing
Clearing deadline · 24 A · 0.3 s
- Fuse A
- Within entered time bound
- 0.22222222 s · Estimated bound
- Fuse B
- Outside entered time bound
- 0.33333333 s · Estimated bound
Outside chart
Pulse duration · 40 A · 0.01 s
- Fuse A
- Current outside entered range
- Fuse B
- Current outside entered range
At minimum melt
Pulse duration · 8 A · 1 s
- Fuse A
- At the entered melting limit
- 1 s · Entered bound
- Fuse B
- Within entered time bound
- 2 s · Entered bound
At maximum clearing
Clearing deadline · 16 A · 0.5 s
- Fuse A
- At the entered clearing deadline
- 0.5 s · Entered bound
- Fuse B
- Outside entered time bound
- 0.75 s · Entered bound
Show entered curve points
| Current | Min. melt | Max. clear |
|---|---|---|
| 4 A | 4 s | 8 s |
| 8 A | 1 s | 2 s |
| 16 A | 0.25 s | 0.5 s |
| 32 A | 0.0625 s | 0.125 s |
| Current | Min. melt | Max. clear |
|---|---|---|
| 4 A | 8 s | 12 s |
| 8 A | 2 s | 3 s |
| 16 A | 0.5 s | 0.75 s |
| 32 A | 0.125 s | 0.1875 s |
Show selectable CSV
How to use this calculator
- Open Edit circuit, fuse data and events. Enter AC or DC, maximum voltage and any documented available fault current.
- Enter each candidate's matching AC or DC voltage and interruption ratings. Leave unknown ratings blank.
- Copy published minimum melting and maximum total clearing points in increasing current order. Mark missing bounds blank.
- Enter independent constant-current pulse durations or clearing deadlines. Use the curve and event text together to identify documented limits and missing data.
- Export the CSV to retain the entered ratings, curve points, bound sources and individual comparisons.
The Formula
The mathematical logic powering this calculation is:
Enter the circuit's maximum open-circuit voltage and the documented prospective current available to interrupt. Use matching rating data for DC or for AC, where entered amperes are RMS. A rated voltage equal to or above the circuit requirement meets that entered limit. A rated interruption current equal to or above the available prospective current meets that entered limit only when the entered AC/DC type and voltage are compatible. Missing comparison values remain unknown. Do not use a fuse's ampere rating or nominal load as the prospective interruption current.
Copy points from the same fuse type and stated test conditions, with ascending currents. A row has a current and either an entered minimum melting time, maximum total clearing time, both, or two blanks to mark explicitly unavailable data at that current. Never enter typical or average melting times as a guaranteed lower or upper bound. Enter nonincreasing time bounds as current rises. At each current, an entered maximum clearing time must be at least the entered minimum melting time.
At an exact plotted current, use that row's bound. Between adjacent rows with the needed bound present, the model interpolates linearly in log current and log time. For current I between I₀ and I₁, fraction w = ln(I/I₀) ÷ ln(I₁/I₀), and estimated bound = t₀ × exp(w × ln(t₁/t₀)). A blank at either adjacent row stops evaluation for that bound. The other bound can still be available. Currents outside the range of entered points are unavailable. The interruption rating neither expands nor narrows this curve range. If the voltage or mode scope is missing or incompatible, no event result is reported for that candidate.
A pulse duration must be shorter than the minimum melting bound to produce a within-bound result. Equality is marked as the entered melting limit. A clearing deadline must be at least the maximum clearing bound. Exact equality is separately identified as the entered clearing deadline. Near-equality for an interpolated value is specifically labeled estimated at the boundary because an interpolation has no exact margin. Event checks use independent constant-current examples. The tool does not accumulate pulse energy or extrapolate curves.
Use 0.000001 through 1,000 V for voltage. Use 0.000001 through 1,000,000 A or seconds for currents and times. All accept up to six decimals. Use up to eight curve rows per fuse and six event checks. Exact inputs and rating/equality comparisons use a micro-unit grid. Only curve interpolation and plot coordinates use floating-point logarithms.
This worksheet compares entered documentation. It does not choose a fuse from operating current, establish installation suitability, calculate fault current, coordinate protective devices, predict effects of repetitive pulses or validate a circuit. Manufacturer test conditions, ambient temperature, waveform, AC frequency or DC time constant, terminal conditions and the application all affect real behavior. Use a qualified design review and application verification where needed.Worked Example
If you input:
- Circuit scope: 24 V DC with 1,200 A of available fault current
- Candidate ratings: Both 32 V DC. A 2,000 A interrupt rating. B 1,000 A interrupt rating.
- Pulse and deadline: 12 A for 0.5 s and 24 A with a 0.3 s clearing deadline. All curve points are synthetic examples.
Result:
Fuse A meets the entered interruption rating but exceeds its estimated minimum melting time for the startup pulse. Fuse B stays within its estimated pulse bound and falls below the entered interruption requirement. The 40 A event is outside the entered curves.
Frequently Asked Questions
Is the interruption rating the biggest current on the time-current curve?
They describe different limits. The interruption rating is a separate breaking-capacity comparison. Only your entered curve points define the time-current domain.
Can I use an average melting line as minimum melting data?
Use an explicit lower melting bound or leave that column blank. Average values cannot establish the lower bound.
Why can one event be inside the graph but lack a bound?
The current is inside the entered range, but the needed bound is blank at that point or a neighboring row. The calculator leaves the result unavailable.
What does estimated at the boundary mean?
An interpolated value is too close to the event duration to show a meaningful numerical margin. Read the manufacturer's data at that condition.
Does a within-bound label choose a fuse for my design?
It reports the result of one comparison using the entered data. Other ratings, conditions and circuit verification determine design suitability.
Similar Calculators
DC Voltage Drop & Cable Loss Calculator
Compare DC cable voltage drop, power losses and load limits with separate conductor lengths, connection resistance, constant-power loads and visual sweeps.
Electrical Load & Phase Balance Planner
Compare three-phase load assignments. Calculate conductor current and fundamental neutral current from a shared set of line-to-neutral loads.
Transformer kVA, Load & Loss Calculator
Compare transformer kVA ratings, currents and profile energy losses. Model energized idle versus switched off, inspect load curves and export exact energy and cost ledgers.