Electric Demand Ratchet Calculator
Find out when lower measured peak demand can change a bill under a lookback ratchet. Enter one set of historical peaks, an explicit lookback rule and two monthly plans. The calculator rolls each option’s measured peak into its own future history, shows the binding demand value, and identifies the first month with a lower rounded demand charge.
Compare two demand charge paths
See when a measured peak stops setting the rolling billing floor.
Enter one peak per lookback period, oldest first, separated by commas.
Use one line per period. Enter period | peak A (kW) | peak B (kW) | rate (USD/kW).
Option B first reduces the demand charge in April.
Compare billed demand by period
Dark bars show current measured demand. The lighter portion reaches the billable value when a floor applies.
- Option A
- Option B
Option A · 160 kW billed
Option B · 160 kW billed
Option A · 160 kW billed
Option B · 160 kW billed
Option A · 160 kW billed
Option B · 160 kW billed
Option A · 154 kW billed
Option B · 100 kW billed
Option A · 150 kW billed
Option B · 100 kW billed
Trace the ratchet and charge ledger
Show the selected period’s charge details
January · $10.00/kW
Option A · $1,600.00
Current peak 160 kW
Prior peak 200 kW from History 3
Lookback floor 160 kW
Binding values · Current peak, Lookback floor
Option B · $1,600.00
Current peak 100 kW
Prior peak 200 kW from History 3
Lookback floor 160 kW
Binding values · Lookback floor
How to use this calculator
- Enter the written number of preceding periods, the ratchet percentage and any minimum demand.
- Copy one comparable measured peak for each historical period, from oldest to newest, separated by commas.
- Enter forecast rows as period | option A peak kW | option B peak kW | demand rate USD/kW.
- Compare which values set billed demand and which periods first change the rounded charge. Use the ledger to see the controlling historical peak.
The Formula
The mathematical logic powering this calculation is:
Use L previous measured billing-period peaks, with the current period outside the lookback. The ratchet floor equals the largest preceding peak times the entered percentage. Billed demand is the maximum of current measured kW, ratchet floor and entered contract minimum. Report every value that ties for the maximum. Multiply billed kW by that period’s entered USD/kW rate. Round each period charge to cents with halves up, then sum charges and compare the rounded bills.
Start both options with the same measured history. For each future period, retain its own current measured peak in that option’s next lookback and discard the oldest included measurement. Each later period can therefore have a different floor. When multiple lookback entries tie for highest, the ledger names the most recent. Savings in period j equals A’s rounded charge minus B’s. The model covers one demand component and one rolling measured-peak rule copied from the applicable tariff. Energy, fixed fees, taxes, power factor corrections and schedules based on prior billed demand require separate inputs or arithmetic.Worked Example
If you input:
- History: 100, 100 and 200 kW from oldest to newest
- Tariff: Three-period measured-peak lookback, 80%, 70 kW minimum
- Forecast: January through May, each at $10.00/kW
Result:
Both options are billed 160 kW for January through March. The historical 200 kW peak then leaves the window. In April, A is billed 154 kW and B is billed 100 kW, a $540.00 difference. B saves $1,040.00 across all five periods.
Frequently Asked Questions
Why can a lower measured peak leave the demand charge unchanged?
If the earlier measured peak still establishes a higher floor, both current values can lead to the same billed demand. The earlier peak affects the comparison until it leaves the lookback or a later peak takes its place.
Do both options use the same history throughout?
They start from the same authored history. Once future peaks begin, each only adds its own entered measurements to the rolling window.
Which peak values should I enter?
Use the measured demand definition specified by your tariff. If the written rule uses adjusted demand, use comparable adjusted values in both options. This calculator starts with your entered values.
What happens if two inputs tie for billed demand?
Both are listed as binding values. The billed demand and rounded charge are the same for the tied values.
Can I model a rate that changes each period?
Yes, enter the appropriate rate in each row. Both options use that row’s rate. Separate tariff schedules or multiple demand components need their own calculations.
Similar Calculators
Electricity Bill & Rate Comparison Calculator
Compare electricity bills with flat, time-of-use or tiered rates. Enter usage and fees, then find how much peak electricity you would need to shift to break even.
Colocation Power Contract & Metered Quote
Compare a flat colocation power quote and a metered quote at the same peak kVA and monthly kWh. Check each contracted draw cap and find the exact energy price crossover.
Server Power Cost Calculator
Compare server fleets with active, idle and standby schedules, PUE, time-of-use rates and coincident demand. Visualize hourly power, monthly costs and upgrade payback.
Electricity Cost Calculator
Estimate appliance electricity cost from wattage, daily use, electricity rate, and billing fees.
Solar Battery Sizing & Backup Planner
Compare solar battery sizes with hourly solar and load profiles, storage losses, power limits, signed tariffs and grid outages. Visualize energy flows and export the complete ledger.