PoE Switch Power Budget & Port Planner
Check whether a switch can reserve power for a mix of cameras, access points or other powered Ethernet devices. The planner evaluates port-class compatibility and aggregate PoE watts independently. Compare two manifests under their entered primary and degraded budgets, then see how many additional devices of a selected class could fit.
Compare PoE budgets and compatible ports
Use one device inventory to check two switches under their primary and documented degraded power budgets.
Only Switch B fits the primary plan.
Open switch and device inputs
Device inventory by class
The reserve column shows the source-side class values.
PoE watts against each budget
Switch A
2 compatible ports missing · 20 entered ports
Switch B
All device classes have compatible ports · 20 entered ports
Port capacity by class threshold
Higher-class ports appear in each lower threshold they support. The tightest row identifies the port shortage.
| Threshold | Needed | Available | Spare |
|---|---|---|---|
| All classes | 14 | 20 | 6 |
| Class 4+ | 6 | 8 | 2 |
| Class 5+ | 2 | 0 | -2 |
| Class 6+ | 2 | 0 | -2 |
| Class 7+ | 0 | 0 | 0 |
| Class 8+ | 0 | 0 | 0 |
2 devices remain unmatched.
Room for additional class-4 devices
Each additional device reserves 30 W. The calculation holds all existing devices fixed.
Switch A
Primary
Expansion unavailable
Port shortfall
Degraded
Expansion unavailable
Budget unconfirmed
Switch B
Primary
Up to 1 additional
6 by ports · 1 by watts
Degraded
Expansion unavailable
Budget shortfall
Reservation and placement ledger
| Class | Devices | Per device | Group total |
|---|---|---|---|
| 3 | 8 | 15.4 W | 123.2 W |
| 4 | 4 | 30 W | 120 W |
| 6 | 2 | 60 W | 120 W |
| Total | 14 | — | 363.2 W |
Show selectable CSV
How to use this calculator
- Enter the confirmed device count for each PoE class. Start with the shared class-based reservation or enter documented per-port switch allocations.
- Enter both switches’ available PoE budgets and the count of usable ports at each documented maximum class. Count a port once.
- If the same set of ports stays active on a documented degraded supply, enter its aggregate PoE budget. Leave the field blank if you do not have that figure.
- Compare watt headroom and compatible port thresholds. Choose an expansion class and compare how many identical added devices fit under each condition.
- Use the ledger to reconcile reservations and placement by class. Download or copy its CSV for review.
The Formula
The mathematical logic powering this calculation is:
Enter each counted powered device in its confirmed PoE class. For class-based planning the switch-side PSE reservation in watts is 15.4, 4, 7, 15.4, 30, 45, 60, 75 or 90 for classes 0 through 8. The listed powered-device (PD) reference numbers are at the device side. They are displayed for context, while the switch budget uses source-side allocation. In documented allocation mode, copy a confirmed reserved amount at the switch, including any accounted link losses. The entered amount may be below the class-based reservation, while the device still requires the same documented compatibility class.
Count each usable port once at its documented highest supported class: 3, 4, 5, 6, 7 or 8. The worksheet treats eligible classes as nested, so a port entered at class 6 can take any recorded device up to class 6. It examines devices from highest class to lowest and chooses the lowest ceiling that fits. For each threshold c, supply is the count of ports whose ceilings reach c and demand is the device count at or above c. Also compare all ports with all devices. The smallest signed spare across these nested groups identifies the worst port shortfall. Overlapping shortages cannot be added together. The placement is the topology check, independently of aggregate watts.
Required milliwatts are the sum of device count times reserved milliwatts. Headroom = aggregate budget − required. A base plan fits only if the port assignment places all devices and headroom is nonnegative. Enter a documented degraded aggregate PoE budget to check the same ports with a different available supply. Blank means no degraded budget was confirmed. Zero watts is an entered budget. This comparison assumes the same ports remain enabled, so enter another switch manifest if the relevant port count changes.
For a fitting configuration, the expansion probe checks one selected device class. The port ceiling is the unused compatible port count after the lowest-compatible assignment. The watt ceiling is floor(headroom ÷ reserve of one added device). The lower ceiling gives the maximum number of those additional devices while holding every existing device fixed. A failed or unconfirmed base plan has no combined expansion count. The probe applies to one class at a time.
Counts are whole 0–1,024 per group. Budgets are 0–100,000 W, with up to three decimals. A documented active reservation is 0.001 W through its class reference, with up to three decimals. The model counts integer milliwatts and one powered device per port. Verify actual switch and device capabilities, cable conditions, mode and power-supply documentation separately. The worksheet does not predict feature negotiation, simultaneous per-module caps, shared chassis power changes, or what happens to individual ports during a supply incident.Worked Example
If you input:
- Device counts: 8 class 3, 4 class 4, and 2 class 6
- Reserve method: Class-based switch watts
- Switch A: 12 class-3 ceiling ports and 8 class-4 ceiling ports. 410 W primary.
- Switch B: 8 class-3, 8 class-4 and 4 class-6 ceiling ports. 410 W primary and 340 W degraded.
- Expansion class: Class 4
Result:
The requested source allocation is 363.2 W. Switch A has 46.8 W of primary headroom but lacks two compatible ports. Switch B fits under its 410 W primary budget and can accept one more class-4 device. Its entered degraded budget is 23.2 W short.
Frequently Asked Questions
Why can enough watts still leave a device unmatched?
Each device also needs a port whose documented ceiling supports its class. A group of lower-ceiling ports cannot substitute for a single high-class port.
Which power number should I copy from the equipment documentation?
For the aggregate budget use the switch’s available PoE watts under the stated configuration. For documented allocation mode use the reservation at the switch for one device. The PD rating and the switch power supply’s nameplate are different quantities.
Does class 0 mean zero watts?
The reference allocation for class 0 is 15.4 W on the switch side. Use the actual classification of each device and confirm its compatibility.
What happens if a degraded condition removes ports as well as watts?
The second budget uses the same entered ports. To model a smaller enabled inventory, enter that inventory as a separate switch manifest.
Why do port deficits across multiple rows overlap?
Each threshold includes its higher classes and the ports they share. An unplaced higher-class device can appear in several threshold counts. The worst signed spare describes the total shortfall.
Can I add the expansion counts for different classes?
Each expansion count assumes only one class is added. For mixed growth, add all planned devices to the counts and rerun the comparison.
Does a passing result verify every PoE feature or a failover?
It confirms the arithmetic with the entered port ceilings and budgets. Negotiation, cable limits, per-module caps, firmware behavior and continued port availability depend on the equipment.
Similar Calculators
Transformer kVA, Load & Loss Calculator
Compare transformer kVA ratings, currents and profile energy losses. Model energized idle versus switched off, inspect load curves and export exact energy and cost ledgers.
IPv4 Subnet & VLSM Planner
Plan IPv4 subnets with VLSM, reserve address blocks, compare allocation order, and inspect masks, host ranges and free CIDRs on a zoomable map.
Server Power Cost Calculator
Compare server fleets with active, idle and standby schedules, PUE, time-of-use rates and coincident demand. Visualize hourly power, monthly costs and upgrade payback.